Multi Variable Air Conditioners Indoor Unit for North America
107
2 After-sales Emergency Masures
When some unrecoverable fault occurs to one module which is connected with several others in
parallel, the following emergency measures are recommended to guarantee the heating or cooling
capacity of the indoor units and the service life of modules except the faulted one are not affected.
Step 1: set all indoor uni
ts under ―Off‖ mode and cut off the power supply to the indoor and outdoor
units.
Step 2:.shut off all cutoff valves of the faulted outdoor unit, including the cutoff valves of the
liquid/gas pipe as well as the oil balancing valve.
Step 3: cut off the air switch of the module.
Step 4: remove the communication line between the faulted module and other modules which are
still kept connected through the communication line.
Step 5: readjust the address and quantity settings on the main board of the modules except the
faulted one.
Step 6: power and restart the unit.
3 Wiring Diagram
NOTICE!
This drawing is just for reference; please always refer to the electric wiring stuck to the unit for
actual wiring.
3.1 Low Static Pressure Duct Type Indoor Unit
Model
:
GMV-ND07PLS/A-T(U) ~ GMV-ND22PLS/A-T(U)
Содержание GMV-N07G/A3A-D(U)
Страница 1: ...Multi Variable Air Conditioners Indoor Unit for North America Service Manual R410A R410A 60Hz GC201609...
Страница 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Страница 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Страница 37: ...Multi Variable Air Conditioners Indoor Unit for North America 31 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Страница 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Страница 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...