3.11.3 Selection of air switch and power cord
Model
Power Supply
Circuit
Breaker
Capacity (A)
Minimum Sectional
Area of
Ground Wire
(mm
2
/AWG)
Minimum Sectional Area of
Power
Cord
(mm
2
/AWG)
GMV-ND24A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND30A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND36A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND42A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND48A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND54A/A-T(U)
208/230V~60Hz
15
1.0/AWG18
1.0/AWG18
3.12 Installation of AHU-KIT type Indoor Unit
3.12.1 Outline and installation dimension
Size of EXV box for GMV-N12U/A-T(U)
、
GMV-N24U/A-T(U)
、
GMV-N48U/A-T(U) and
GMV-N96U/A-T(U) (Unit: mm(in.)):
326 (12 7/
8)
203 (8)
85
(3 3/8)
150(6)
40
(1 4/7)
250 (9 7/
8)
174 (6 7/8)
200 (7 7/8)
290 (11 7/1
6)
4×Φ6
4×Φ12
Size of EXV box for GMV-N192U/A-T(U) (Unit: mm(in.)):
Содержание GMV-N07G/A3A-D(U)
Страница 1: ...Multi Variable Air Conditioners Indoor Unit for North America Service Manual R410A R410A 60Hz GC201609...
Страница 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Страница 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Страница 37: ...Multi Variable Air Conditioners Indoor Unit for North America 31 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Страница 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Страница 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...