Multi Variable Air Conditioners Indoor Unit for North America
123
6. Remove
reversion loop
and centrifugal
blade
●Remove 4 screws fixing the
reversion loop and then remove the
reversion loop
‘ remove nuts on blade
and then remove the centrifugal
blade.
4.5 High Static Pressure Duct Type Indoor Uint
NOTICE!
The following steps are specific for GMV-ND18PHS/A-T(U) units. For other units, the
assembly and disassembly procedure is similar except the specifications of centrifugal fans and motors.
Motor and fan
Precondition: The power supply has been disconnected.
Step
Diagram
Operation Procedure
1. Remove the line
connecting to the
motor.
●Use a screwdriver to unscrew the
electric box cover.
●Remove from the master board the
line connecting to the motor and
remove the tie.
2. Disassemble the
seal plate and cover
plate.
●Use a screwdriver to unscrew the
seal plate and cover plate and then
remove them.
3. Remove the
cover plate
component.
●Use a screwdriver to unscrew the
cover plate component.
Содержание GMV-N07G/A3A-D(U)
Страница 1: ...Multi Variable Air Conditioners Indoor Unit for North America Service Manual R410A R410A 60Hz GC201609...
Страница 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Страница 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Страница 37: ...Multi Variable Air Conditioners Indoor Unit for North America 31 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Страница 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Страница 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...