background image

DC Inverter Multi VRF System   

10 

Rated capacity of IDU C(Btu/h) 

Gas pipe (mm/inch) 

Liquid pipe (mm/inch) 

17000<

C≤

48000 

Φ

15.9 (

Φ

5/8) 

Φ

9.52 (

Φ

3/8) 

48000<

C≤

55000 

Φ

19.05 (

Φ

3/4) 

Φ

9.52 (

Φ

3/8) 

55000<

C≤

96000 

Φ

22.2 (

Φ

7/8) 

Φ

9.52 (

Φ

3/8) 

 

If the distance between IDU and its nearest branch is over 10m(33feet), then the liquid pipe of IDU 

(rated capacity ≤

17000Btu/h) shall be enlarged. 

4.3 Installation of Connection Pipe 

 

(1)  Conform to the following principles during pipe connection: Connection pipe should be as short as possible, so is 

the height difference between indoor and outdoor units. Keep the number of bends as little as possible. Radius of 
curvature should be as large as possible. 

(2)  Weld the connection pipe between indoor and outdoor units. Please strictly follow the requirements for welding 

process. Rosin joint or pin hole is not allowed. 

(3)  When laying the pipe, be careful not to distort it. Radius of bending parts should be over 200mm(8inch). Note that 

pipes cannot be repeatedly bent or stretched; otherwise the material will get harder. Do not bend or stretch the 
pipe for more than 3 times at the same position. 

4.3.1 Flaring Process 

(1)  Use pipe cutter to cut the connection pipe in case it is unshaped. 
(2)  Keep the pipe downward in case cutting scraps get into the pipe. Clear away the burrs after 

cutting. 

(3)  Remove the flared nut connecting indoor connection pipe and outdoor unit. Then use flaring 

tool to fix the flared nut into the pipe (as shown in Fig.4.8). 

(4)  Check if the flared part is flaring evenly and if there is any crack. 

 

Fig.4.8 

4.3.2 Pipe Bending 

(1)  Reshape the pipe by hand. Be careful not to damage the pipe. 
(2)  Do not bend the pipe over 90°. 
(3)  If pipe is repeatedly bent or stretched, it will get hard and difficult to bend and stretch again. 

Therefore, do not bend or stretch the bend for over 3 times. 

Содержание GMV-36WL/C-T

Страница 1: ...Owner s Manual Original Instructions Commercial Air Conditioners DC Inverter Multi VRF System Applicable Models GMV 60WL C T U GMV 48WL C T U GMV 36WL C T U...

Страница 2: ...All graphics in this manual is only for your reference For sales or production reasons these graphics are subject to change by manufacturer without prior notice 9 This appliance is not intended for u...

Страница 3: ...Hole 5 4 2 Connection Pipe 6 4 3 Installation of Connection Pipe 10 4 4 Disassembly of Compressor Feet 14 4 5 Vacuum Pumping Refrigerant Adding 15 4 6 Electric Wiring 17 5 Check Items after Installati...

Страница 4: ...ephone line 6 Be sure to use special accessories and parts for installation to prevent water leakage electric shock and fire hazard etc 7 If refrigerant leakage happens please ventilate the room immed...

Страница 5: ...tely and then contact Gree appointed service center If those abnormal circumstances still exit the unit may be damaged and it may lead to electric shock or fire hazard 27 Do not repair the unit by you...

Страница 6: ...s of DC Inverter Multi VRF System can be connected to various indoor units When any one of the indoor units receives operating command outdoor unit will start operation as per required capacity When a...

Страница 7: ...for heat exchange and maintenance so that unit can operate reliably with good ventilation 7 Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with go...

Страница 8: ...r piping work requirements R410A Refrigerant System Outer diameter mm inch Wall thickness mm inch 6 35 1 4 0 8 1 32 9 52 3 8 0 8 1 32 12 7 1 2 0 8 1 32 15 9 5 8 1 0 1 25 19 05 3 4 1 0 1 25 4 Installat...

Страница 9: ...inch Model A B C D E GMV 36WL C T U GMV 48WL C T U 900 35 3 8 340 13 3 8 1345 53 572 22 1 2 378 15 GMV 60WL C T U 940 37 320 12 9 16 1430 56 1 4 632 24 7 8 350 14 7 8 4 2 Connection Pipe 4 2 1 Schemat...

Страница 10: ...and Height Difference of Connection Pipe Piping parameters of GMV 36WL C T U GMV 48WL C T U GMV 60WL C T U Allowable value Fitting pipe m feet Total length actual length of fitting pipe 300 984 L1 L2...

Страница 11: ...le Pipe dimension Gas pipe mm inch Liquid pipe mm inch GMV 36WL C T U 15 9 5 8 9 52 3 8 GMV 48WL C T U 15 9 5 8 9 52 3 8 GMV 60WL C T U 19 05 3 4 9 52 3 8 4 2 4 Selection of Indoor Branches Select ind...

Страница 12: ...otal capacity of downstream indoor units C Btu h Pipe mm inch Liquid pipe mm inch C 19000 12 7 1 2 6 35 1 4 19000 C 48500 15 9 5 8 9 52 3 8 48500 C 76400 19 05 3 4 9 52 3 8 4 2 6 Dimension of Pipe bet...

Страница 13: ...le is not allowed 3 When laying the pipe be careful not to distort it Radius of bending parts should be over 200mm 8inch Note that pipes cannot be repeatedly bent or stretched otherwise the material w...

Страница 14: ...of nut will get damaged if the flared nut is twisted forcibly 3 Use torque wrench to twist on the flared nut tightly until the wrench gives out a click sound Hold the handle of wrench and make it at r...

Страница 15: ...ht or rear side Fig 4 13 2 Pipe connection for GMV 60WL C T U As shown in Fig 4 14 and Fig 4 15 open the outermost soundproof cotton and place a fire barrier between compressor and straight pipe Use a...

Страница 16: ...d remove burrs as well See Fig 4 17 3 Y type branch must be installed vertically or horizontally Fig 4 17 Branch shall be isolated by insulating material that can bear 120 C 248 F or even higher tempe...

Страница 17: ...perature For heat pump unit liquid pipe should bear 70 C 158 F or above and gas pipe should bear 120 C 248 F or above For cooling only unit both liquid pipe and gas pipe should bear 70 C 158 F or abov...

Страница 18: ...ds to be charged with additional refrigerant 2 Confirm whether outdoor liquid and gas valves are closed 3 Use vacuum pump to withdraw the air inside indoor unit and connection pipe from the outdoor va...

Страница 19: ...Quantity of IDU 2 0 3 kg 10 58oz First confirm that there is no leakage from the system When compressor is not working charge additional R410A with specific amount to the unit through the filling ope...

Страница 20: ...function and thermal trip function so that system can be protected from short circuit and overload 6 Air conditioner belongs to class I electrical appliance so it must be securely grounded 7 The yell...

Страница 21: ...ot being supplied to the indoor unit and outdoor unit 2 Match the terminal block numbers and connection cord colors with those of the indoor unit side Erroneous wiring may cause burning of the electri...

Страница 22: ...condition changes please adjust the specification according to national standard 3 Specification of circuit breaker is based on the working condition where ambient temperature of circuit breaker is 40...

Страница 23: ...DC Inverter Multi VRF System 20 Fig 4 26 Fig 4 27...

Страница 24: ...placing the main board of outdoor unit it is necessary to perform test operation and debugging Otherwise unit won t be able to work 2 Test operation and debugging must be performed by professional tec...

Страница 25: ...mmunication wire of IDU is correctly connected After the check connect power and start debugging from progress 01 If the number is then correct press main board s SW3 button to confirm Then the displa...

Страница 26: ...ts 08_ Confirm preheated compressor 08 U0 Display circularly Preheat time for compressor is less than 8 hours Display will be as in the left until the preheat time reaches 8 hours Press main board s S...

Страница 27: ...in this process through the L VALVE 15_ Cooling debugging 15 AC Display circularly Debugging for cooling mode If no malfunction occurs for 50min when compressor is running then the system is certifie...

Страница 28: ...ient temp is 25 35 C 77 95 F in cool mode system s high pressure value will be within 44 53 C 111 127 F In heat mode if ambient temp is above 5 C 23 F system s high pressure value is within 40 52 C 10...

Страница 29: ...or EXV varies within 40 480PLS 15 Communication parameters Communication data Number of IDUs detected by software is the same with the actual number No communication error 16 Drainage system Indoor un...

Страница 30: ...locked and dirty Clean the filter If problem cannot be solved after checking the above items please contact Gree service center and describe the cases and models Following circumstances are not malfun...

Страница 31: ...rossing malfunction of PG motor dU Malfunction of drainage pipe temperature sensor of generator LU Indoor unit s branch is not inconsistent for one to more unit of heat recovery system db Debugging st...

Страница 32: ...of outlet tube temperature sensor of condenser PA Malfunction of drive storage chip of compressor bJ High pressure sensor and low pressure sensor are connected reversely PH High voltage protection of...

Страница 33: ...en main control and DC DC controller U6 Alarm because valve is abnormal C2 Communication malfunction between main control and inverter compressor driver U7 Power grid DRED0 response protection C3 Comm...

Страница 34: ...connection pipe of ODU An Child lock status Ay Shielding status 8 Maintenance and Care Regular check maintenance and care can extend unit s service life Please have specialized person in charge of the...

Страница 35: ...ix oxygen C2H2 or other dangerous gas into the refrigerant circuit Otherwise it may lead to danger Use nitrogen or refrigerant to conduct the tests 9 After sales Service If there s quality defect or o...

Страница 36: ......

Отзывы: