DC Inverter Multi VRF System
31
Status:
Error
Code
Content
Error
Code
Content
A0
Unit waiting for debugging
n0
SE operation setting of system
A2
Refrigerant recovery operation of after-sales
n3
Compulsory defrosting
A3
Defrosting
n4
Limit setting for max. capacity/output capacity
A4
Oil-return
n5
Compulsory excursion of engineering code of IDU
A6
Heat pump function setting
n6
Inquiry of malfunction
A7
Quiet mode setting
n7
Inquiry of parameters
A8
Vacuum pump mode
n8
Inquiry of project code of IDU
AH
Heating
n9
Check quantity of IDU on line
AC
Cooling
nA
Heat pump unit
AL
Charging refrigerant automatically
nH
Heating only unit
AE
Charging refrigerant manually
nC
Cooling only unit
AF
Fan
nE
Negative sign code
AJ
Alarm for cleaning filter
nF
Fan model
AP
Debugging confirmation for startup of unit
nJ
High temperature prevention when heating
AU
Long-distance emergency stop
nU
Eliminate the long-distance shielding command of
IDU
Ab
Emergency stop of operation
nb
Bar code inquiry
Ad
Limit operation
nn
Length modification of connection pipe of ODU
An
Child lock status
Ay
Shielding status
8 Maintenance and Care
Regular check, maintenance and care can extend unit’s service life. Please have specialized
person in charge of the management of air conditioners.
8.1 Outdoor Heat Exchanger
Outdoor heat exchanger shall be cleaned regularly, which is at least once every two months. You
can use a dust catcher with nylon brush to clean away the dust on the heat exchanger. If compressed
air source is available, it also can be used to clean the heat exchanger. Do not clean it with water.
8.2 Drain Pipe
Please check regularly whether drain pipe is blocked or not. Make sure condensate can be
drained out smoothly.
8.3 Notice before Seasonal Use
(1) Check whether air inlets and air outlets of indoor and outdoor units are blocked.
(2) Check whether ground connection is reliable or not.
(3) Check whether batteries in the remote controller are replaced or not.
(4) Check whether air filter is properly installed.
(5) If unit starts up after not operating for a long time, it should be power on 8 hours before
operation starts so as to preheat the outdoor compressor.
(6) Check whether outdoor unit is securely installed. If there is any problem, please contact
Gree authorized service center.