DC Inverter Multi VRF System
5
If the ODU is totally surrounded by walls, please refer to Fig.3.1 for space dimension:
Fig.3.1
3.3 Piping Work Requirements
Refer to the table below for piping work requirements:
R410A Refrigerant System
Outer diameter (mm/inch)
Wall thickness (mm/inch)
Φ
6.35(
Φ
1/4)
≥0.8
(1/32)
Φ
9.52(
Φ
3/8)
≥0.8
(1/32)
Φ
12.7(
Φ
1/2)
≥0.8
(1/32)
Φ
15.9(
Φ
5/8)
≥1.0
(1/25)
Φ
19.05(
Φ
3/4)
≥1.0
(1/25)
4 Installation Instruction
Graphics here are only for reference. Please refer to actual products.
4.1 Dimension of Outdoor Unit and Mounting Hole
Unit Outline and Installation Dimension.
Fig.4.1