GREE DC Inverter Multi VRF System II Service Manual
95
13) Loop malfunction of driven charging for compressor
Wired
controller
displays P0
LED3 dual-8
nixie tube
displays PF
Check whether the
wires for PFC
induction is correct/
Reinsert the
wires for PFC
Replace main
board
yes
no
Work normally
14) Malfunction of memory chip for inverter compressor
LED3 dual-8 nixie
tube displays PA
Whether the
memory chip is
inserted inversely
yes
Work normally
Adjust the memory
chip
Whether the
memory chip is
loose
˛
Insert the memory
chip tightly
yes
no
no
Wire controller
displays P0
Replace main
board
Содержание GMV-100WL/A-T
Страница 1: ...DC INVERTER VRF SYSTEM SERVICE MANUAL R410A...
Страница 4: ...DC INVERTER VRF SYSTEM II SERVICE MANUAL R410A PRODUCT...
Страница 15: ...GREE DC Inverter Multi VRF System II Service Manual 11 GMV 80WL C T GMV 100WL C T GMV 121WL C T...
Страница 16: ...GREE DC Inverter Multi VRF System II Service Manual 12 GMV 141WL C T...
Страница 18: ...GREE DC Inverter Multi VRF System II Service Manual 14 CONTROL...
Страница 33: ...GREE DC Inverter Multi VRF System II Service Manual 29 z Click Next z Installation is in progress...
Страница 58: ...GREE DC Inverter Multi VRF System II Service Manual 54 Step 4 Then click Port Settings in the dialog box...
Страница 64: ...GREE DC Inverter Multi VRF System II Service Manual 60 INSTALLATION...
Страница 72: ...GREE DC Inverter Multi VRF System II Service Manual 68 DEBUGGING MAINTENANCE...
Страница 104: ...GREE DC Inverter Multi VRF System II Service Manual 100 GMV 141WL C T GMV 120WL A T GMV 140WL A T GMV 160WL A T...
Страница 107: ...GREE DC Inverter Multi VRF System II Service Manual 103 GMV H280WL A X GMV 280WL C X GMV H335WL A X GMV 335WL C X...
Страница 173: ...JF00302323...