GREE DC Inverter Multi VRF System II Service Manual
142
IDU
No.
IDU
ķ
IDU
ĸ
IDU
Ĺ
IDU
ĺ
Model
Duct type
GMV-ND72PL/B-T
Duct type
GMV-ND50PL/B-T
Duct type
GMV-ND36PL/B-T
Duct type
GMV-ND25PL/B-T
Liquid pipe:
No.
A
B
C
D
Pipe size
Φ
9.52
Φ
9.52
Φ
9.52
Φ
6.35
Length
10m
5m
5m
5m
No.
a
b
c
d
Pipe size
Φ
9.52
Φ
6.35
Φ
6.35
Φ
6.35
Length
3m
3m
2m
1m
Total length of each liquid pipe
Φ
9.52
˖
A+B+C+a=10+105+5+3=23m
Φ
6.35: D+b+c+d=5+3+2+1=11m
Note: Liquid pipe that is within 20m doesn’t need to be added with refrigerant.
Therefore, the minimum quantity of additional refrigerant = (23-20)×0.054+11×0.022
˙
0.404kg
˄
2
˅
Calculate the additional volume of refrigera
˄
GMV-80WL/C-T
ǃ
GMV-100WL/C-T
ǃ
GMV-121WL/C-T
ǃ
GMV-80WL/A-T
ǃ
GMV-100WL/A-T
ǃ
GMV-121WL/A-T
ǃ
GMV-120WL/C-T
ǃ
GMV-140WL/C-T
ǃ
GMV-160WL/C-T
ǃ
GMV-120WL/C-X
ǃ
GMV-140WL/C-X,GMV-160WL/C-X
˅
1) Refrigerant quantity of outdoor unit before delivery:
Model
GMV-
80WL
/A-T
GMV-
100W
L/A-T
GMV-
121W
L/A-T
GMV-
80WL
/C-T
GMV-
100W
L/C-T
GMV-
121W
L/C-T
GMV-
141W
L/C-T
GMV-
120W
L/C-T
GMV-
140W
L/C-T
GMV-
160W
L/C-T
GMV-
120W
L/C-X
GMV-
140W
L/C-X
GMV-
160W
L/C-X
Refrigerant
Qty (kg)
1.8
1.8
2.0
1.8
1.8
2.0
3.3
3.3
3.3
3.3
3.3
3.3
3.3
Note:
ķ
The refrigerant amount charged before delivery do
esn’t includ
e the amount that needs to be
added to indoor units and the connection pipeline.
ĸ
Length of connection pipe is decided on site. Therefore the amount of additional refrigerant
shall be decided on site according to the dimension and length of field-installed liquid pipe.
Ĺ
Record the amount of additional refrigerant for convenience of after-sales service.
2) Calculation of the amount of additional refrigerant
Calculation method of the quantity of additional refrigerant (based on liquid pipe)
Quantity of additi
onal refrigerant = ∑length of liquid pipe
×quantity of additional refrigerant per
meter+
˄
quantity of indoor unit -2
˅
×0.3
Quantity of additional refrigerant per meter for liquid pipe
˄
kg/m
˅
Φ
22.2
Φ
19.05
Φ
15.9
Φ
12.7
Φ
9.52
Φ
6.35
0.35
0.25
0.17
0.11
0.054
0.022
First confirm that there is no leakage from the system. When compressor is not working, charge
additional R410a with specific amount to the unit through the filling opening of the liquid pipe valve of the
outdoor unit. If required amount cannot be quickly filled due to pressure increase of the pipe, then set the
unit in cooling startup and fill refrigerant from the low pressure check valve of the outdoor unit.
Содержание GMV-100WL/A-T
Страница 1: ...DC INVERTER VRF SYSTEM SERVICE MANUAL R410A...
Страница 4: ...DC INVERTER VRF SYSTEM II SERVICE MANUAL R410A PRODUCT...
Страница 15: ...GREE DC Inverter Multi VRF System II Service Manual 11 GMV 80WL C T GMV 100WL C T GMV 121WL C T...
Страница 16: ...GREE DC Inverter Multi VRF System II Service Manual 12 GMV 141WL C T...
Страница 18: ...GREE DC Inverter Multi VRF System II Service Manual 14 CONTROL...
Страница 33: ...GREE DC Inverter Multi VRF System II Service Manual 29 z Click Next z Installation is in progress...
Страница 58: ...GREE DC Inverter Multi VRF System II Service Manual 54 Step 4 Then click Port Settings in the dialog box...
Страница 64: ...GREE DC Inverter Multi VRF System II Service Manual 60 INSTALLATION...
Страница 72: ...GREE DC Inverter Multi VRF System II Service Manual 68 DEBUGGING MAINTENANCE...
Страница 104: ...GREE DC Inverter Multi VRF System II Service Manual 100 GMV 141WL C T GMV 120WL A T GMV 140WL A T GMV 160WL A T...
Страница 107: ...GREE DC Inverter Multi VRF System II Service Manual 103 GMV H280WL A X GMV 280WL C X GMV H335WL A X GMV 335WL C X...
Страница 173: ...JF00302323...