GREE DC Inverter Multi VRF System II Service Manual
81
2.3.2 Cool & Heat Function
This function can set operation modes and prevent mode collision that is caused by setting different
modes for different indoor units. It is especially suitable for hotels and other small business areas. There
are 3 levels for this setting:
Level A
—
Mode Lock Control
Upon entering this function setting, main board of outdoor unit will display as below:
LED1
LED2
LED3
Function code
Current progress
Display
Current status
Display
A6
nC
Blink
nC
Blink
Press SW1 button (▲) and SW2 button (▼) to select the following functions:
LED1
LED2
LED3
Function code
Display
Current progress/mode
Display
Current status
Display
A6
On
nC
Blink
nC
Blink
A6
On
nH
Blink
nH
Blink
A6
On
nA
Blink
nA
Blink
A6
On
nF
Blink
nF
Blink
When applicable mode is selected, press SW7 to confirm. The related display is as below:
LED1
LED2
LED3
Function code
Display
Current progress/mode
Display
Current status
Display
A6
On
nC
On
nC
On
A6
On
nH
On
nH
On
A6
On
nA
On
nA
On
A6
On
nF
On
nF
On
This setting will be memorized by master unit and can’t be cancelled even when power is on or off.
Then press SW6 on the master unit to return to the previous step.
If then no motion is taken to the master unit for 5min, unit will exit and resume displaying the current
status.
(If this button is pressed when function is being set, system will return to the previous step. If SW6
is pressed when setting is finished, system will resume displaying the current operation status.)
Default setting is
“nA” cooling and heating type.
Level B
—
IDU Mode Auto Control
When Level A is disabled or outdoor unit is set to be cooling and heating type, the operation mode
within one system depends on the master-salve setting of indoor units.
Содержание GMV-100WL/A-T
Страница 1: ...DC INVERTER VRF SYSTEM SERVICE MANUAL R410A...
Страница 4: ...DC INVERTER VRF SYSTEM II SERVICE MANUAL R410A PRODUCT...
Страница 15: ...GREE DC Inverter Multi VRF System II Service Manual 11 GMV 80WL C T GMV 100WL C T GMV 121WL C T...
Страница 16: ...GREE DC Inverter Multi VRF System II Service Manual 12 GMV 141WL C T...
Страница 18: ...GREE DC Inverter Multi VRF System II Service Manual 14 CONTROL...
Страница 33: ...GREE DC Inverter Multi VRF System II Service Manual 29 z Click Next z Installation is in progress...
Страница 58: ...GREE DC Inverter Multi VRF System II Service Manual 54 Step 4 Then click Port Settings in the dialog box...
Страница 64: ...GREE DC Inverter Multi VRF System II Service Manual 60 INSTALLATION...
Страница 72: ...GREE DC Inverter Multi VRF System II Service Manual 68 DEBUGGING MAINTENANCE...
Страница 104: ...GREE DC Inverter Multi VRF System II Service Manual 100 GMV 141WL C T GMV 120WL A T GMV 140WL A T GMV 160WL A T...
Страница 107: ...GREE DC Inverter Multi VRF System II Service Manual 103 GMV H280WL A X GMV 280WL C X GMV H335WL A X GMV 335WL C X...
Страница 173: ...JF00302323...