![Gree GMV-100WL/A-T Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/gree/gmv-100wl-a-t/gmv-100wl-a-t_service-manual_2260293023.webp)
GREE DC Inverter Multi VRF System II Service Manual
19
z
HBS interface: When HBS converter is under HBS communication mode, connect air
conditioner’s HBS data
interface. HBS interface exhibits no polarity (This interface is not yet
available for Gree debugger and the monitoring software).
z
RS485 interface: When RS485 converter is under RS485 communication mode, connect air
conditioner’s RS485 data
interface. RS485 interface exhibits polarity and terminal A and B are
different.
3.3.2.4 Installation notice
z
Install indoors. To avoid collision, it is suggested to place it in the monitoring room together with
the computer.
z
No need of power supply. Power is supplied through computer’s USB
interface.
3.3.3 Communication board
Communication board is mainly used for transferring data. It functions similar with a patching board.
Provided that units are far away from the monitoring computer, communication board can be used for
connection.
3.3.4 Communication cord
3.3.4.1 USB wire
z
Connect USB wire with
computer’s USB
interface at one end and with the USB interface of USB
data converter at the other end, as indicated below:
3.3.4.2 Board Connection Wire
z
There are 2 board connection wires supplied for the commissioning tool kits. One is 1 me
ter’s
long and the other is 5.5 meter
s’
long. They are only different in length. One end of the wire shall
connect with
air conditioner’s communication
interface and the other end shall connect with CAN
interface of Gree USB converter. As shown below, the wire can be connected to the
communication interface of outdoor unit or the communication interface of indoor unit:
USB Wire
Содержание GMV-100WL/A-T
Страница 1: ...DC INVERTER VRF SYSTEM SERVICE MANUAL R410A...
Страница 4: ...DC INVERTER VRF SYSTEM II SERVICE MANUAL R410A PRODUCT...
Страница 15: ...GREE DC Inverter Multi VRF System II Service Manual 11 GMV 80WL C T GMV 100WL C T GMV 121WL C T...
Страница 16: ...GREE DC Inverter Multi VRF System II Service Manual 12 GMV 141WL C T...
Страница 18: ...GREE DC Inverter Multi VRF System II Service Manual 14 CONTROL...
Страница 33: ...GREE DC Inverter Multi VRF System II Service Manual 29 z Click Next z Installation is in progress...
Страница 58: ...GREE DC Inverter Multi VRF System II Service Manual 54 Step 4 Then click Port Settings in the dialog box...
Страница 64: ...GREE DC Inverter Multi VRF System II Service Manual 60 INSTALLATION...
Страница 72: ...GREE DC Inverter Multi VRF System II Service Manual 68 DEBUGGING MAINTENANCE...
Страница 104: ...GREE DC Inverter Multi VRF System II Service Manual 100 GMV 141WL C T GMV 120WL A T GMV 140WL A T GMV 160WL A T...
Страница 107: ...GREE DC Inverter Multi VRF System II Service Manual 103 GMV H280WL A X GMV 280WL C X GMV H335WL A X GMV 335WL C X...
Страница 173: ...JF00302323...