50
MAN IAQ Surveyor
Issue 11 2004
3. MICROMANOMETER AND THERMOCOUPLE
3.3.6 Duct Averaging - Storing Readings
The IAQ Surveyor Pro provides a facility to record
measurements as a duct is traversed and then to
automatically calculate the average values.
To enter the duct averaging mode:
(1) Press
the
START/STOP
AVERAGE
button and then select
the Site and Location.
(2)
To indicate that the instrument is
in the averaging mode, the display will show the letters
AVG vertically on the right side of the screen.
(3)
Place the probe in the required location and wait for
the instrument reading to stabilise.
(4)
Log the displayed readings at the selected location by
pressing the
STORE (F2)
button.
(5)
Repeat steps (3) and (4) at all the required locations.
(6)
When all the required readings have been taken and
logged, press the
START/STOP AVERAGING
button.
(7)
When prompted to cancel the logging process, press
the
ACCEPT
button.
3.3.7 Duct Averaging - Viewing Readings
To view the readings taken:
(1) Press
the
MENU/METER
button to display the Main
Menu.
(2) Select
Duct Averaging
and press
ACCEPT
.
PaPrsr
°C Tc
A
V
m/s Vel
G
m3/s
Vfr
100.0
23.0
28.1
280.2
Содержание IAQ SURVEYOR II
Страница 2: ...2 MAN IAQ Surveyor Issue 11 2004...
Страница 16: ...16 MAN IAQ Surveyor Issue 11 2004...
Страница 44: ...44 MAN IAQ Surveyor Issue 11 2004...
Страница 52: ...52 MAN IAQ Surveyor Issue 11 2004...
Страница 72: ...72 MAN IAQ Surveyor Issue 11 2004...
Страница 93: ...93 MAN IAQ Surveyor Issue 11 2004 10 PITOT STATIC TUBES AND ACCESSORIES...
Страница 94: ...94 MAN IAQ Surveyor Issue 11 2004...