background image

18

440 04 7113 02

Specifications subject to change without notice.

NOTE

: Be sure to attach ground wire and reconnect blower

harness plugs to blower motor.

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal

injury or death.
Blower door switch opens 115--v power to control. No

component operation can occur unless switch is closed.

Caution must be taken when manually closing this

switch for service purposes.

!

WARNING

16. Downflow or horizontal furnaces with vent pipe

through furnace only:
a. Install and connect short piece of vent pipe inside

furnace to existing vent.

b. Connect vent connector to vent elbow.

17. Turn on electrical supply. Manually close blower door

switch. Use a piece of tape to hold switch closed.

Check for proper rotation and speed changes

between heating and cooling by jumpering R to G and

R to Y/Y2 on furnace control thermostat terminals. If

outdoor temperature is below 70

_

F (21

_

C), turn off

circuit breaker to outdoor unit before running furnace

in the cooling cycle. Turn outdoor circuit breaker on

after completing cooling cycle. (See Fig. 2.)

NOTE

: If R--W/W1 thermostat terminals are jumpered at the

time blower door switch is closed, blower will run for 90 sec
before beginning a heating cycle.

a. Perform component self--test as shown at the bottom

of the SERVICE label, located on the control door.

b. Verify blower is rotating in the correct direction

18. If furnace is operating properly, RELEASE BLOWER

DOOR SWITCH. Remove any jumpers or reconnect

any disconnected thermostat leads. Replace blower

door.

19. Turn on gas supply and cycle furnace through one

complete

heating

cycle.

Verify

the

furnace

temperature rise as shown in Adjustments Section.

Adjust temperature rise as shown in Adjustments

Section.

Cleaning Burners and Flame Sensor

The following items must be performed by a qualified

service technician. If the burners develop an accumulation

of light dirt or dust, they may be cleaned by using the

following procedure:

NOTE

: Use a back-up wrench on the gas valve to prevent

the valve from rotating on the manifold or damaging the
mounting to the burner assembly.

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personal

injury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace

and install lockout tag before performing any

maintenance or service. Follow the operating

instructions on the label attached to the furnace.

!

WARNING

Refer to Fig

.

14.

1. Disconnect power at external disconnect, fuse or

circuit breaker.

2. Turn off gas at external shut-off or gas meter.

3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect the gas pipe from gas valve and remove

pipe from the furnace casing.

6. Remove individual wires from terminals on gas valve.
7. Disconnect Hot Surface Igniter (HSI) wires from HSI.
8. Disconnect Flame Sensor wire from Flame Sensor.
9. Support the manifold and remove the 4 screws that

secure the manifold assembly to the burner assembly

and set aside. Note the location of the green/yellow

wire and ground terminal.

10. Inspect the orifices in the manifold assembly for

blockages or obstructions. Remove orifice and clean

or replace orifice.

11. Remove the four screws that attach the top plate of

the casing to the furnace.

12. Raise top plate up slightly and prop it up with a small

piece of wood or folded cardboard.

13. Support the burner assembly and remove the screws

that attach the burner assembly to the heat

exchanger cell panel.

14. Remove wires from both rollout switches.
15. Slide one--piece burner out of slots on sides of burner

assembly.

16. Remove the flame sensor from the burner assembly.
17. (Optional) Remove the Hot Surface Igniter (HSI) and

bracket from the burner assembly.

18. Check igniter resistance. Nominal resistance is 40 to

70 ohms at room temperature and is stable over the

life of the igniter.

19. Clean burner with a brush and a vacuum.
20. Clean the flame sensor with fine steel wool (0000

grade). Do not use sand paper or emery cloth.

To reinstall burner assembly:

1. Install the Hot Surface Igniter (HSI) and bracket in

burner assembly.

2. Install flame sensor on burner.
3. Align the edges of the one-piece burner with the slots

in the burner assembly and slide the burners forward

until they are fully seated in the burner assembly.

4. Align the orifices in the manifold assembly with the

support rings on the end of the burner.

5. Insert the orifices in the support rings of the burners.

NOTE

: If manifold does not fit flush against the burner, do

not force the manifold on the burner assembly. The burners
are not fully seated forward in the burner assembly. Remove
the manifold and check burner positioning in the burner
assembly assembly before re-installing the manifold.

6. Attach the green/yellow wire and ground terminal to

one of the manifold mounting screws.

7. Install the remaining manifold mounting screws.
8. Check the igniter alignment. See Fig. 8, 9 and 14.
9. Attach the wires to the roll-out switches.

10. Align the burner assembly with the openings in the

primary cell inlet panel and attach the burner

assembly to the cell panel.

11. Connect the wire for the flame sensor.

12. Connect the wire for the Hot Surface Igniter.

NOTE

: Use propane-resistant pipe dope to prevent leaks.

Do not use Teflon tape.

13. Install the gas pipe to the gas valve.

Содержание WFAR Series

Страница 1: ...nual in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING is used throughout this...

Страница 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Страница 3: ...1 115vac terminal is energized whenever blower operates HUM 24vac terminal is only energized when the low pressure switch LPS is closed on a call for heat Prime Condensate Trap with Water CARBON MONO...

Страница 4: ...ns to match the required orifice to the manifold pressure to the heat content and specific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas sup...

Страница 5: ...ld be clear blue almost transparent See Fig 12 i Remove jumper R to W j Reinstall manifold pressure tap plug from gas valve 2 Verify natural gas input rate by clocking meter NOTE Contact your HVAC dis...

Страница 6: ...e S Shortened furnace life S Component damage Temperature rise must be within limits specified on furnace rating plate Recommended operation is at midpoint of rise range or slightly above CAUTION Jump...

Страница 7: ...thermostat per thermostat instructions and install on sub base or wall 5 Install blower access door Electronic thermostat Set cycle rate for 3 cycles per hr Check Safety Controls The flame sensor gas...

Страница 8: ...0 2743 3048 18 20 0 81 Derate multiplier factors are based on midpoint altitude for altitude range ON OFF Switch Regulator Seal Cap Regulator Adjustment Regulator Seal Cap under Cap 1 2 NPT Outlet 1 8...

Страница 9: ...290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 9...

Страница 10: ...10 440 04 7113 02 Specifications subject to change without notice 338309 201 Rev E A11602 Fig 5 Service Label Information...

Страница 11: ...2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3...

Страница 12: ...4 2134 700 43 3 5 43 3 7 43 3 8 42 3 2 725 44 3 8 43 3 4 43 3 5 43 3 6 750 44 3 5 44 3 7 44 3 8 43 3 4 8000 775 44 3 3 44 3 4 44 3 5 44 3 7 2438 800 44 3 1 44 3 2 44 3 3 44 3 4 825 44 2 9 44 3 0 44 3...

Страница 13: ...0 1110 1100 1090 1065 1035 990 935 870 805 Red 3 2 0 433 940 920 910 890 865 830 790 745 690 625 100C048C SIDE BOTTOM Black 4 0 373 1715 1660 1610 1555 1490 1420 1340 1245 1150 1065 Yellow 3 3 5 379 1...

Страница 14: ...ECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death There may be more than one electrical supply to the furnace Check accessories and cooling unit for additio...

Страница 15: ...s shown If any of the original wire as supplied must be replaced use same type or equivalent wire W Y GND THERMOSTAT TERMINALS 1 2 3 A11387 Fig 7 Typical Single Stage Wiring Diagram Component Self Tes...

Страница 16: ...ene cigarette lighter fluid dry cleaning fluids or other volatile fluids 3 Paint thinners and other painting compounds paper bags or other paper products Exposure to these materials could lead to corr...

Страница 17: ...wer compartment Disconnect the vent and combustion air pipe by a Loosen the clamps on the vent couplings and combustion air pipe external to the furnace b Separate the pipes from the couplings and mov...

Страница 18: ...hut off or gas meter 3 Remove control door and set aside 4 Turn electric switch on gas valve to OFF 5 Disconnect the gas pipe from gas valve and remove pipe from the furnace casing 6 Remove individual...

Страница 19: ...ng could result in personal injury death and or property damage Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service Follow the...

Страница 20: ...a problem exists which needs to be corrected such as improper adjustment of manifold pressure insufficient or poor quality combustion air improper vent termination incorrect size or damaged manifold...

Страница 21: ...may occur CAUTION 1 Obtain propylene glycol RV swimming pool antifreeze or equivalent 2 Turn off gas and electrical supplies to your furnace 3 Remove furnace control door 4 Remove the top unused rubbe...

Страница 22: ...Fig 12 Burner Flame SET SCREW MOTOR WHEEL HUB MOTOR SHAFT FLAT SCREW MOTOR ARM GROMMET SCREW LOCATION BLO HSG ASSY BRACKET BRACKET ENGAGEMENT SEE DETAIL A CAPACITOR OR POWER CHOKE WHEN USED BRACKET SC...

Страница 23: ...440 04 7113 02 23 Specifications subject to change without notice FLAME SENSOR BELOW BURNER FLAME ROLLOUT SWITCH BRACKET IGNITER IGNITER BURNER SUPT ASSY BURNER ASSY A11403 Fig 14 Burner Assembly...

Страница 24: ...If the burner flame is proven the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 is energized and remains e...

Страница 25: ...flash the status code of the previous fault or status code 11 1 short and 1 long flash if there was no previous fault After the control repeats the code 4 times the control will go through a brief co...

Страница 26: ...control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check t...

Страница 27: ...440 04 7113 02 27 Specifications subject to change without notice 339236 2 Rev A Fig 16 Wiring Diagram...

Страница 28: ...on service or maintenance can cause personal injury property damage or death Consult a qualified installer service agency or your local gas supplier for information or assistance The qualified install...

Отзывы: