Grandaire WFAR Series Скачать руководство пользователя страница 24

24

440 04 7113 02

Specifications subject to change without notice.

SEQUENCE OF OPERATION

NOTE

:

Furnace control must be grounded for proper

operation or control will lock out. Control is grounded
through green/yellow wire routed to gas valve and manifold
bracket screw. Using the schematic diagram in Fig. 16,
follow the sequence of operation through the different
modes. Read and follow the wiring diagram very carefully.

NOTE

: If a power interruption occurs during a call for heat

(W), the control will start a 90--sec blower--only ON period
two sec after power is restored, if the thermostat is still
calling for gas heating. The Amber LED light will flash code
12 during the 90--sec period, after which the LED will be ON
continuous, as long as no faults are detected. After the
90--sec period, the furnace will respond to the thermostat
normally.
The blower door must be installed for power to be

conducted through the blower door interlock switch ILK to

the furnace control CPU, transformer TRAN, inducer motor

IDM, blower motor BLWM, hot--surface igniter HSI, and gas

valve GV.

1.

Heating

(See Fig. 2 for thermostat connections.)

The wall thermostat “calls for heat,” closing the

R--to--W circuit. The furnace control performs a self--

check, verifies the pressure switch contacts collector

box--LPS and housing pressure switch--HPS are

open, and starts the inducer motor IDM.
a.

Inducer Prepurge Period

-- As the inducer motor

IDM comes up to speed the collector box pressure

switch contacts LPS close to begin a 15 second pre-

purge period. The inducer housing pressure switch

contacts HPS are ignored until one minute after the

gas valve closes.

b.

Igniter Warm--Up

-- At the end of the prepurge

period, the Hot--Surface igniter HSI is energized for

a 17--sec igniter warm--up period.

c.

Trial--for--Ignition Sequence

-- When the igniter

warm--up period is completed, the main gas valve

relay contacts GVR close to energize the gas valve

GV, the gas valve opens. The gas valve GV permits

gas flow to the burners where it is ignited by the HSI.

Five sec after the GVR closes, a 2--sec flame proving

period begins. The HSI igniter will remain energized

until the flame is sensed or until the 2--sec flame

proving period begins.

d.

Flame--Proving

-- When the burner flame is proved

at the flame--proving sensor electrode FSE, the

furnace control CPU begins the blower--ON delay

period and continues to hold the gas valve GV open.

If the burner flame is not proved within two sec, the

control CPU will close the gas valve GV, and the

control CPU will repeat the ignition sequence for up

to three more Trials--For--Ignition before going to

Ignition--Lockout.

Lockout

will

be

reset

automatically after three hours or by momentarily

interrupting 115 vac power to the furnace, or by

interrupting 24 vac power at SEC1 or SEC2 to the

furnace control CPU (not at W, G, R, etc.).

If flame is proved when flame should not be present,

the furnace control CPU will lock out of Gas--Heating

mode and operate the inducer motor IDM until flame

is no longer proved.

e.

Blower--On Delay

-- If the burner flame is proven, the

blower motor is energized on HEAT speed 25 sec

after the gas valve GV is energized.

Simultaneously, the electronic air cleaner terminal

EAC--1 is energized and remains energized as long

as the blower motor BLWM is energized.

f.

Blower--Off Delay

-- When the thermostat is

satisfied, the R--to--W circuit is opened, de--

energizing the gas valve GV, stopping gas flow to the

burners, and de--energizing the humidifier terminal

HUM. The inducer motor IDM will remain energized

for a 15--sec post--purge period. The blower motor

BLWM and air cleaner terminal EAC--1 will remain

energized for 90, 120, 150, or 180 sec (depending

on the blower--OFF delay selection). The furnace

control CPU is factory--set for a 120--sec blower--

OFF delay.

2.

Cooling Mode

The thermostat “calls for cooling.”
(See Fig. 2 for thermostat connections)

The thermostat closes the R--to--G--and--Y circuits. The

R--to--Y

circuit

starts

the

outdoor

unit,

and

the

R--to--G--and--Y circuits start the furnace blower motor

BLWM on COOL speed.

The electronic air cleaner terminal EAC--1 is energized with

115 vac when the blower motor BLWM is operating. When

the thermostat is satisfied, the R--to--G--and--Y circuits are

opened. The outdoor unit will stop, and the furnace blower

motor BLWM will continue operating on the COOL speed for

an additional 90 sec.

3.

Continuous Blower Mode

When the R--to--G circuit is closed by the thermostat,

the blower motor BLWM will operate on HEAT speed.

Terminal EAC--1 is energized as long as the blower

motor BLWM is energized. During a call for heat, the

blower BLWM will stop during igniter warm--up (17

sec), ignition (7 sec), and blower--ON delay (25 sec),

allowing the furnace heat exchangers to heat up more

quickly, then restarts at the end of the blower--ON

delay period at HEAT speed.

When the thermostat “calls for cooling”, the blower

motor BLWM will operate at COOL speed. When the

thermostat is satisfied, the blower motor BLWM will

operate an additional 90 sec on COOL speed before

reverting back to continuous--blower (HEAT speed).

When the R--to--G circuit is opened, the blower motor

BLWM will continue operating for an additional 5 sec,

if no other function requires blower motor BLWM

operation.

4.

Heat Pump

When installed with a heat pump, the furnace control

automatically changes the timing sequence to avoid

long blower off times during demand defrost cycles.

When the R--to--Wand-- Y or R--to--W--and--Y--and--G

circuits are energized the furnace control CPU will

continue to turn on the blower motor BLWM at HEAT

speed, and begin a heating cycle. The blower motor

BLWM will remain on until the end of the prepurge

period, then shut off for 24 sec then come back on at

HEAT speed. When the W input signal disappears,

the furnace control begins a normal inducer post--

purge period and the blower switches to COOL speed

after a 3 sec delay. If the R--to--W--and--Y--and--G

signals disappear at the same time, the blower motor

BLWM will remain on for the selected blower-- OFF

delay period. If the R--to--W--and--Y signals disappear,

leaving the G signal, the blower motor BLWM will

continue running the blower motor at HEAT speed

after the selected blower--OFF delay period is

completed.

Component Self-Test

Refer to page 15 for instructions.

Содержание WFAR Series

Страница 1: ...nual in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING is used throughout this...

Страница 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Страница 3: ...1 115vac terminal is energized whenever blower operates HUM 24vac terminal is only energized when the low pressure switch LPS is closed on a call for heat Prime Condensate Trap with Water CARBON MONO...

Страница 4: ...ns to match the required orifice to the manifold pressure to the heat content and specific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas sup...

Страница 5: ...ld be clear blue almost transparent See Fig 12 i Remove jumper R to W j Reinstall manifold pressure tap plug from gas valve 2 Verify natural gas input rate by clocking meter NOTE Contact your HVAC dis...

Страница 6: ...e S Shortened furnace life S Component damage Temperature rise must be within limits specified on furnace rating plate Recommended operation is at midpoint of rise range or slightly above CAUTION Jump...

Страница 7: ...thermostat per thermostat instructions and install on sub base or wall 5 Install blower access door Electronic thermostat Set cycle rate for 3 cycles per hr Check Safety Controls The flame sensor gas...

Страница 8: ...0 2743 3048 18 20 0 81 Derate multiplier factors are based on midpoint altitude for altitude range ON OFF Switch Regulator Seal Cap Regulator Adjustment Regulator Seal Cap under Cap 1 2 NPT Outlet 1 8...

Страница 9: ...290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 9...

Страница 10: ...10 440 04 7113 02 Specifications subject to change without notice 338309 201 Rev E A11602 Fig 5 Service Label Information...

Страница 11: ...2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3...

Страница 12: ...4 2134 700 43 3 5 43 3 7 43 3 8 42 3 2 725 44 3 8 43 3 4 43 3 5 43 3 6 750 44 3 5 44 3 7 44 3 8 43 3 4 8000 775 44 3 3 44 3 4 44 3 5 44 3 7 2438 800 44 3 1 44 3 2 44 3 3 44 3 4 825 44 2 9 44 3 0 44 3...

Страница 13: ...0 1110 1100 1090 1065 1035 990 935 870 805 Red 3 2 0 433 940 920 910 890 865 830 790 745 690 625 100C048C SIDE BOTTOM Black 4 0 373 1715 1660 1610 1555 1490 1420 1340 1245 1150 1065 Yellow 3 3 5 379 1...

Страница 14: ...ECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death There may be more than one electrical supply to the furnace Check accessories and cooling unit for additio...

Страница 15: ...s shown If any of the original wire as supplied must be replaced use same type or equivalent wire W Y GND THERMOSTAT TERMINALS 1 2 3 A11387 Fig 7 Typical Single Stage Wiring Diagram Component Self Tes...

Страница 16: ...ene cigarette lighter fluid dry cleaning fluids or other volatile fluids 3 Paint thinners and other painting compounds paper bags or other paper products Exposure to these materials could lead to corr...

Страница 17: ...wer compartment Disconnect the vent and combustion air pipe by a Loosen the clamps on the vent couplings and combustion air pipe external to the furnace b Separate the pipes from the couplings and mov...

Страница 18: ...hut off or gas meter 3 Remove control door and set aside 4 Turn electric switch on gas valve to OFF 5 Disconnect the gas pipe from gas valve and remove pipe from the furnace casing 6 Remove individual...

Страница 19: ...ng could result in personal injury death and or property damage Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service Follow the...

Страница 20: ...a problem exists which needs to be corrected such as improper adjustment of manifold pressure insufficient or poor quality combustion air improper vent termination incorrect size or damaged manifold...

Страница 21: ...may occur CAUTION 1 Obtain propylene glycol RV swimming pool antifreeze or equivalent 2 Turn off gas and electrical supplies to your furnace 3 Remove furnace control door 4 Remove the top unused rubbe...

Страница 22: ...Fig 12 Burner Flame SET SCREW MOTOR WHEEL HUB MOTOR SHAFT FLAT SCREW MOTOR ARM GROMMET SCREW LOCATION BLO HSG ASSY BRACKET BRACKET ENGAGEMENT SEE DETAIL A CAPACITOR OR POWER CHOKE WHEN USED BRACKET SC...

Страница 23: ...440 04 7113 02 23 Specifications subject to change without notice FLAME SENSOR BELOW BURNER FLAME ROLLOUT SWITCH BRACKET IGNITER IGNITER BURNER SUPT ASSY BURNER ASSY A11403 Fig 14 Burner Assembly...

Страница 24: ...If the burner flame is proven the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 is energized and remains e...

Страница 25: ...flash the status code of the previous fault or status code 11 1 short and 1 long flash if there was no previous fault After the control repeats the code 4 times the control will go through a brief co...

Страница 26: ...control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check t...

Страница 27: ...440 04 7113 02 27 Specifications subject to change without notice 339236 2 Rev A Fig 16 Wiring Diagram...

Страница 28: ...on service or maintenance can cause personal injury property damage or death Consult a qualified installer service agency or your local gas supplier for information or assistance The qualified install...

Отзывы: