background image

16

440 04 7113 02

Specifications subject to change without notice.

4. For approximately 2 sec, short (jumper) the COM-24v

terminal on control to the TEST/TWIN 3/16—in. (5

mm) quick-connect terminal on control until the LED

goes off. Remove jumper from terminals. (See Fig. 2.)

NOTE

:

If TEST/TWIN and COM-24v terminals are

jumpered longer than 2 sec, LED will flash rapidly and

ignore component test request.
Component test sequence is as follows:

a. LED will display previous status code 4 times.
b. Inducer motor starts and continues to run until Step

f of component test sequence.

c. After 7 sec the hot surface igniter is energized for

15 sec., then off.

d. Blower motor operates on HEAT speed for 10 sec.
e. Blower motor operates on COOL speed for 10 sec.

f. Inducer motor stops.

5. Reconnect R lead to furnace control, remove tape

from blower door switch, and re-install blower door.

6. Verify furnace shut down by lowering thermostat

setting below room temperature.

7. Verify that furnace restarts by raising thermostat

setting above room temperature.

Checklist

1. Put away tools and instruments. Clean up debris.
2. Verify that the jumper is removed from the TEST/

TWIN terminal. Verify that there is nothing plugged

into the PLT connector. (Note: If there is a jumper

connector plugged into PLT, remove it and discard.)

(See Fig. 2.)

3. Verify that the Blower/Heat Off Delay jumpers are set

as desired. (See Fig. 2.)

4. Verify that the blower and control (“Main”) doors are

properly installed.

5. Verify that the Status LED glows. If not, check that the

power supply is energized and that the blower door is

secure. (See Fig. 5.)

6. Cycle test furnace with room thermostat to be sure

that it operates properly with the room thermostat.

Check all modes including Heat, Cool and Fan.

7. Check operation of accessories per manufacturer’s

instructions.

8. Review Owner’s Manual with owner.
9. Attach entire literature packet to furnace.

Care and Maintenance

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal

injury, death and/or property damage.
Never store flammable or combustible materials on,

near, or in contact with the furnace, such as:

1. Spray or aerosol cans, rags, brooms, dust

mops, vacuum cleaners, or other cleaning

tools.

2. Soap powders, bleaches, waxes or other

cleaning

compounds,

plastic

or

plastic

containers, gasoline, kerosene, cigarette lighter

fluid, dry cleaning fluids, or other volatile fluids.

3. Paint thinners and other painting compounds,

paper bags, or other paper products. Exposure

to these materials could lead to corrosion of the

heat exchangers.

!

WARNING

For continuing high performance and to minimize possible

furnace failure, periodic maintenance must be performed on

this furnace. Consult your local dealer about proper

frequency of maintenance and the availability of a

maintenance contract.

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personal

injury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace

and install lockout tag before performing any

maintenance or service. Follow the operating

instructions on the label attached to the furnace.

!

WARNING

CARBON MONOXIDE POISONING AND FIRE

HAZARD

Failure to follow this warning could result in personal

injury, death and/or property damage.
Never operate furnace without a filter or filtration

device installed. Never operate a furnace with filter or

filtration device access doors removed.

!

WARNING

CUT HAZARD

Failure to follow this caution may result in personal

injury.
Sheet metal parts may have sharp edges or burrs.

Use care and wear appropriate protective clothing,

safety glasses and gloves when handling parts, and

servicing furnaces.

CAUTION

!

The minimum maintenance on this furnace is as follows:

1. Check and clean air filter each month or more

frequently if required. Replace if torn.

2. Check blower motor and wheel for cleanliness each

heating and cooling season. Clean as necessary.

3. Check electrical connections for tightness and

controls for proper operation each heating season.

Service as necessary.

4. Inspect burner compartment before each heating

season for rust, corrosion, soot or excessive dust. If

necessary, have furnace and burner serviced by a

qualified service agency.

5. Inspect the vent pipe/vent system before each

heating season for water leakage, sagging pipes or

broken fittings. Have vent pipes/vent system serviced

by a qualified service agency.

6. Inspect any accessories attached to the furnace such

as a humidifier or electronic air cleaner. Perform any

service or maintenance to the accessories as

recommended in the accessory instructions.

Cleaning and/or Replacing Air Filter

The air filter type may vary depending on the application or

orientation. The filter is external to the furnace casing. There

are no provisions for an internal filter with this furnace. See

Содержание WFAR Series

Страница 1: ...nual in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING is used throughout this...

Страница 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Страница 3: ...1 115vac terminal is energized whenever blower operates HUM 24vac terminal is only energized when the low pressure switch LPS is closed on a call for heat Prime Condensate Trap with Water CARBON MONO...

Страница 4: ...ns to match the required orifice to the manifold pressure to the heat content and specific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas sup...

Страница 5: ...ld be clear blue almost transparent See Fig 12 i Remove jumper R to W j Reinstall manifold pressure tap plug from gas valve 2 Verify natural gas input rate by clocking meter NOTE Contact your HVAC dis...

Страница 6: ...e S Shortened furnace life S Component damage Temperature rise must be within limits specified on furnace rating plate Recommended operation is at midpoint of rise range or slightly above CAUTION Jump...

Страница 7: ...thermostat per thermostat instructions and install on sub base or wall 5 Install blower access door Electronic thermostat Set cycle rate for 3 cycles per hr Check Safety Controls The flame sensor gas...

Страница 8: ...0 2743 3048 18 20 0 81 Derate multiplier factors are based on midpoint altitude for altitude range ON OFF Switch Regulator Seal Cap Regulator Adjustment Regulator Seal Cap under Cap 1 2 NPT Outlet 1 8...

Страница 9: ...290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 9...

Страница 10: ...10 440 04 7113 02 Specifications subject to change without notice 338309 201 Rev E A11602 Fig 5 Service Label Information...

Страница 11: ...2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3...

Страница 12: ...4 2134 700 43 3 5 43 3 7 43 3 8 42 3 2 725 44 3 8 43 3 4 43 3 5 43 3 6 750 44 3 5 44 3 7 44 3 8 43 3 4 8000 775 44 3 3 44 3 4 44 3 5 44 3 7 2438 800 44 3 1 44 3 2 44 3 3 44 3 4 825 44 2 9 44 3 0 44 3...

Страница 13: ...0 1110 1100 1090 1065 1035 990 935 870 805 Red 3 2 0 433 940 920 910 890 865 830 790 745 690 625 100C048C SIDE BOTTOM Black 4 0 373 1715 1660 1610 1555 1490 1420 1340 1245 1150 1065 Yellow 3 3 5 379 1...

Страница 14: ...ECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death There may be more than one electrical supply to the furnace Check accessories and cooling unit for additio...

Страница 15: ...s shown If any of the original wire as supplied must be replaced use same type or equivalent wire W Y GND THERMOSTAT TERMINALS 1 2 3 A11387 Fig 7 Typical Single Stage Wiring Diagram Component Self Tes...

Страница 16: ...ene cigarette lighter fluid dry cleaning fluids or other volatile fluids 3 Paint thinners and other painting compounds paper bags or other paper products Exposure to these materials could lead to corr...

Страница 17: ...wer compartment Disconnect the vent and combustion air pipe by a Loosen the clamps on the vent couplings and combustion air pipe external to the furnace b Separate the pipes from the couplings and mov...

Страница 18: ...hut off or gas meter 3 Remove control door and set aside 4 Turn electric switch on gas valve to OFF 5 Disconnect the gas pipe from gas valve and remove pipe from the furnace casing 6 Remove individual...

Страница 19: ...ng could result in personal injury death and or property damage Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service Follow the...

Страница 20: ...a problem exists which needs to be corrected such as improper adjustment of manifold pressure insufficient or poor quality combustion air improper vent termination incorrect size or damaged manifold...

Страница 21: ...may occur CAUTION 1 Obtain propylene glycol RV swimming pool antifreeze or equivalent 2 Turn off gas and electrical supplies to your furnace 3 Remove furnace control door 4 Remove the top unused rubbe...

Страница 22: ...Fig 12 Burner Flame SET SCREW MOTOR WHEEL HUB MOTOR SHAFT FLAT SCREW MOTOR ARM GROMMET SCREW LOCATION BLO HSG ASSY BRACKET BRACKET ENGAGEMENT SEE DETAIL A CAPACITOR OR POWER CHOKE WHEN USED BRACKET SC...

Страница 23: ...440 04 7113 02 23 Specifications subject to change without notice FLAME SENSOR BELOW BURNER FLAME ROLLOUT SWITCH BRACKET IGNITER IGNITER BURNER SUPT ASSY BURNER ASSY A11403 Fig 14 Burner Assembly...

Страница 24: ...If the burner flame is proven the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 is energized and remains e...

Страница 25: ...flash the status code of the previous fault or status code 11 1 short and 1 long flash if there was no previous fault After the control repeats the code 4 times the control will go through a brief co...

Страница 26: ...control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check t...

Страница 27: ...440 04 7113 02 27 Specifications subject to change without notice 339236 2 Rev A Fig 16 Wiring Diagram...

Страница 28: ...on service or maintenance can cause personal injury property damage or death Consult a qualified installer service agency or your local gas supplier for information or assistance The qualified install...

Отзывы: