COMET 145 – INSTALLATION/OPERATION MANUAL 

 

5IM-OB-COM0-00

 

 

 

Mar/11

 

7

SMOKE TEST 

Adjust air control until a clean and symmetrical flame with “0-1” smoke 
is obtained and then open to “0” smoke. 

 

CO

2

 TEST 

CO

2

 should be 11 – 13% when burner is at “0” to trace smoke.  If flame 

will not clean up, replace nozzle. 

 

TRIM BURNER AIR 

Always leave burner set at “0” smoke with CO

reading about 1% of 

CO

lower than the peak efficiency achieved with a smoke trace (e.g. 

12% CO

2

 should be set back 1% to 11%).  This gives better allowance 

for fuel and draft variations and maintains a better seasonal efficiency. 

 

3.0  OIL TANKS & PIPING 

 

Tank installation should conform to local requirements. 

 

Install according to the applicable code.  Minimize number of connections in suction line and 
make all connections as tight as possible.  Use a pipe joint compound suitable for oil on all 
pipe threads.  To reduce possibility of air leaks, tighten stem packing gland nut on any valves 
installed in the suction line.  Also, be sure the oil filter is tight, as filter gaskets often shrink.  
Check for kinks in the oil lines as well as for possible air pockets and for loose connections.  
Two filters as shown in Figure - 2 are recommended.  Optional tank gauge protectors and 
outlet protectors are available at your local dealer. 

 

ONE PIPE SYSTEM

 

Where the tank is above the burner and when the oil flows by gravity 
to the oil pump, a single-stage fuel unit with a single oil line to the 
pump may be used. 

 

TWO PIPE SYSTEM 

When single line is unsuitable, use double line or see your dealer for 
special oil line fittings. 

 

4.0

 

BOILER RETURN WATER TEMPERATURE

 

 

Steel boilers are very susceptible to corrosion caused by condensation of flue gases.  In order 
to prevent this, the return water temperature must not fall below 140°F.  Most hydronic 
systems are designed for a delta T of 20°F.  Therefore, the low limit should be set at no lower 
than 170°F, which accounts for the -10°F differential of the triple aquastat.  Heating systems 
that require lower temperatures such as cast iron radiators and radiant systems require some 
form of mixing device to ensure the return water is at or above 140°F. 

 

The warranty will not be valid for steel boilers with return temperatures below 140°F.  
For more information refer to B214-01 Installation Code for Hydronic Heating Systems 
(or equivalent). 

 

5.0 CABINET 

ASSEMBLY    

See Figure – 6

 

 

BOILER WRAP 

Wrap boiler with insulation, foil side out and secure with foil tape provided.  
Cut holes for fittings as required. 

 

SIDES & TOP 

Secure Left, Right and Top with sheet metal screws as shown. 

 

REAR 

Attach Rear and secure with screws. 

 

Содержание Comet 145

Страница 1: ...THAT MAY DIFFER FROM THIS MANUAL Please read this complete manual before beginning installation These instructions must be kept with the boiler for future reference CERTIFIED TO CAN CSA Std B140 0 St...

Страница 2: ...0 Installation 4 2 1 Important 4 2 2 Caution 4 2 3 General Instructions 4 2 4 Placement Venting 4 2 5 Boiler Configuration 5 2 6 Assemble Boiler 5 2 7 Domestic Hot Water 6 2 8 Assemble Install Burner...

Страница 3: ...lation Figure 5 Cleaning Figure 6 Cabinet Assembly Figure 7 Dimensions Figure 8 Exploded Parts Table 1 Parts List Keep this manual in a safe place for future reference Follow manual carefully for the...

Страница 4: ...DO NOT ATTEMPT TO START BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN UNIT IS FULL OF VAPOUR OR COMBUSTION ZONE IS VERY HOT NEVER BURN GARBAGE OR PAPER IN THE UNIT AND NEVER STORE COMBUSTIBLE MATERIAL A...

Страница 5: ...ION INSTALLATION MUST COMPLY WITH REGULATIONS OF AUTHORITIES HAVING JURISDICTION DO NOT START THE BURNER UNTIL ALL FITTINGS COVERS AND DOORS ARE IN PLACE DO NOT TAMPER WITH THE BOILER OR CONTROLS 2 3...

Страница 6: ...e section 2 8 ASSEMBLE INSTALL BURNER AQUASTAT Honeywell L8124L1029 and White Rogers 8B43A 601 or certified equivalent For remote bulb use Honeywell L8151A1052 The Triple Aquastat can be located on th...

Страница 7: ...o correspond with boiler settings table shown on operating decal or section 7 0 BURNER SPECIFICATIONS INSTALL NOZZLE Install selected nozzle and make sure it is tight in the nozzle adapter ELECTRODES...

Страница 8: ...nk gauge protectors and outlet protectors are available at your local dealer ONE PIPE SYSTEM Where the tank is above the burner and when the oil flows by gravity to the oil pump a single stage fuel un...

Страница 9: ...NER Make sure power and fuel are off CLEAN TUBES Clean the tubes carefully with a 2 fiber bristle brush DO NOT DAMAGE TARGET WALL VACUUM Vacuum out lower burner chamber REPLACE BURNER Check insertion...

Страница 10: ...31 CB5 2 1 00 3 79 0 85 60B 7 00 pin 0 118 000 35 CB5 3 1 18 4 47 1 00 60B 7 50 pin 0 140 000 41 Direct Vent BCF V2 0110 10 15 CV3 1 Riello 40 BF3 0 61 3 48 0 50 80B 150 4 10 1 00 74 000 22 CV3 2 0 73...

Страница 11: ...ar as possible 5 Insert the threaded tube end into the pierced hole of the flue vent pipe 6 Install the securing nut on the safety switch tube which protrudes into the flue vent pipe Tighten the nut s...

Страница 12: ...ue temperature is 575 F DRAFT non Direct Vent only Breech Pressure 0 04 wc CONTROLS AQUASTAT Honeywell L8124L1029 L8124G1020 White Rodgers 8B43A 601 Erie Boss 2400 Series Optional Remote Honeywell L81...

Страница 13: ...8 Liters 73 89 SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE FOR MOST RECENT UPDATES PLEASE VISIT www GranbyIndustries com The following form MUST be completed for the warranty to be valid Insta...

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ...00 COMET 145 10B Pressure Vessel Assembly BCF CB 0110 00 COMET 145 11A Cabinet Top BCA CB 0110 00 COMET 145 11B Cabinet Top BCF CB 0010 00 COMET 145 12 Boiler Jacket 3CC 00 WALL 03 COMET 145 13 Targe...

Отзывы: