COMET 145 – INSTALLATION/OPERATION MANUAL
5IM-OB-COM0-00
Mar/11
11
9.0 GENERAL
SPECIFICATIONS
CLEARANCE TO COMBUSTIBLES
Top
6”
(152 mm)
Front 24”
(610
mm)
Rear - includes access
18”
(457 mm)
Side (access)
2”
(51 mm)
Side (access)
24”
(610 mm)
Flue Pipe
9”
(229 mm)
Floor
Combustible or non-combustible
SMOKE/VENT
See Code B139
Smoke/Vent
5” vent pipe, Type “L”
Chimney/Vent See
B139
Code
Vent Systems
KPV-SS1C Venter
Direct
Vent
KPV-SS1C Settings
Certified for use with Type “L” Vent. Maximum flue temperature is 575°F.
DRAFT
(non-Direct Vent only)
Breech Pressure
-0.04” wc
CONTROLS
AQUASTAT
Honeywell L8124L1029
L8124G1020
White Rodgers 8B43A-601
Erie Boss 2400 Series
Optional Remote
Honeywell L8151A1052
RELIEF VALVE
Watts 335, 30 psig ASME or equivalent
TRIDICATOR
70 psi/320°F or equivalent
BAROMETRIC
5” CSA Approved or greater
CLEANOUTS
Breech, burner opening
OIL INPUT
0.61 – 1.22 USGPH
2.31 – 4.62 L/h
FUEL
No heavier than No. 2 furnace oil
DIMENSIONS
Overall depth, less burner
28 1/4”
(1118 mm)
Cabinet depth
28 1/4”
(1118 mm)
Cabinet height
32 1/2”
(940 mm)
Cabinet width
21”
(660 mm)
OPENING HEIGHTS
Burner center line
9 1/4”
(235 mm)
Smoke pipe center line
20 1/4”
(514 mm)