Installation
309858K
11
Heaters for 4-Zone Control Panels
Temperature Controller Settings
The basic program settings for each temperature con-
troller meet the needs of most applications and are pre-
set at the factory.
The input type, temperature scale, and over temperature
alarm point are the critical controller settings that you
must check before doing an auto-tune or using any con-
troller in normal operation. See manual 309100 for oper-
ation of the temperature controls.
Graco Factory P, I, and d Settings
The table lists the P (proportional), I (integral), and d
(derivative) settings for standard control panels. These
settings are preset at the factory. Use the table for refer-
ence information only. See manual 309100 to assess
these values.
Graco Factory P, I, and d Settings
The P, I, and d values are usually generated by running
an auto-tune process for each heat zone. The control-
lers automatically find the proper P, I, and d values dur-
ing this auto-tune process. The values are selected to
allow the heat zones to reach their maximum tempera-
ture as fast as possible without significantly exceeding
desired temperature.
Zone
Component
Terminals
Value Range
Follower
3L1 & 3L3
98-127 ohms
3L2 & 3L3
Dispense
Gun
1532 & 1551
See Technical
Data supplied with
gun
Dispense
Hose
1602 & 1621
See Technical
Data supplied with
hose
Pump
5L1 & 5L2
187.2 ohms + 24
ohms
Component
P
I
d
Follower
29.5
210
52
Pump
87.3
1492
373
Hose
8.9
39
9
Gun
41.4
89
22
AL1
35
AL2
-35
Содержание Therm-O-Flow 20
Страница 43: ...Parts 309858K 43...
Страница 48: ...Electrical Schematic 48 309858K Electrical Schematic Part No 617300...
Страница 50: ...Electrical Schematic 50 309858K Part No 617484...
Страница 52: ...Electrical Schematic 52 309858K Part No 617485...
Страница 54: ...Electrical Schematic 54 309858K Part No 617349...
Страница 61: ...Dimensions 309858K 61 15 1 Pump President Air Motor Ram 52 1 in 1323 mm 75 in 1905 mm...
Страница 62: ...Dimensions 62 309858K...