Troubleshooting
3A2175Z
55
Acceptable Size and Duration of Power Line Voltage Fluctuations
The Motor Control Module is designed to withstand
voltage fluctuations from the incoming power supply. If
the incoming power supply goes outside of the tolera
-
ble range, an over-voltage condition is flagged and the
system shuts down in an alarm state. Excessive or
repeated over-voltage may permanently damage hard
-
ware. The chart below shows the permissible magni
-
tude and duration of temporary over-voltage events.
Consult a qualified electrician if there are any concerns
about the available power supply.
Maximum Permissible Transient Voltage Surges
* Constructed from ITIC 1996 curve, referenced by IEC 61000-2-4
1200Vac, 1697Vdc
264Vac, 373Vdc
336Vac, 475Vdc
288Vac, 407Vdc
480Vac, 679Vdc
<--1 MW Max Surge Power
<--150 KW Max Surge Power
<--50 KW Max Surge Power
<--No Power Limit
0
200
400
600
800
1000
1200
1400
Time (seconds)
Voltage (Volts RMS)
0.000001 0.00001 0.0001 0.001 0.01
0.1
1
10