Remote DataTrak Operation
334222B
15
Diagnostic Mode
Diagnostics
Remote DataTrak can diagnose several problems with
the supply system. When the monitor detects a problem,
the LED (LE, F
. 2) will flash and a diagnostic code will
appear on the display. See Table 2, page 19.
If the accessory light tower kit is installed a light will illu-
minate or flash on the tower. See T
NOTE:
Diagnostic screens will become the active
screen as soon as the diagnostic code condition is
detected. See T
To acknowledge the diagnosis and return to the normal
operating screen, press
once. To clear a diagnostic
code, see the section specific to the code.
. 2. Press and release
to access the Diag-
nostic screens. The system will enter Diagnostic Mode
only if active warnings/alarms are present.
Runaway Diagnostic Code Screen
. 10. If pump runaway occurs, the Runaway
screen becomes active, stopping the pump.
1. Correct the condition causing the diagnostic code.
2. Press and release
to acknowledge the diagnos-
tic code and return to the previous screen.
3. To clear the Runaway diagnostic code:
a. Press and release
to enter Diagnostic Mode
from Run Mode (F
. 4).
b. Press and release
to scroll to the Runaway
Diagnostic screen, or return to the previous Run
screen if no other Diagnostic screens are active.
c. Press and hold
for 3 seconds while on the
runaway Diagnostic screen to clear the diag-
nostic code and scroll to the next available
Diagnostic screen, or return to the previous Run
screen if no other Diagnostic screens are active.
NOTE:
To disable runaway monitoring, go to setup
mode and set runaway value to 0 (zero) or toggle (RT)
off. See F
F
IG
. 10: Runaway Diagnostic Code Screen
RS
NOTICE
Clearing this diagnostic code will immediately cause
the air solenoid to activate, applying air to the motor.