background image

5

or pump down a heat pump or air conditioning system.

NOTICE

THIS UNIT IS SHIPPED WITH A NITROGEN/HELIUM
HOLDING CHARGE ONLY.  UNIT MUST BE EVACUATED
AND CHARGED PER INSTALLATION INSTRUCTIONS
WITH REFRIGERANT LISTED ON SERIAL RATING PLATE.

NOTICE

UNITS SHIPPED WITH A HOLDING CHARGE ARE
INTENDED FOR COMPONENT REPLACEMENT ONLY ON
EXISTING SYSTEMS, AND NOT INTENDED FOR USE IN
NEW SYSTEMS OR NEWLY CONSTRUCTED HOMES.
EPA REGULATIONS PROHIBIT THE SALE OR
DISTRIBUTION OF APPLIANCES PRE-CHARGED WITH
THE REFRIGERANT R-22 IF THOSE APPLIANCES ARE
MANUFACTURED AFTER JANUARY 1, 2010.
COMPONENTS OF EXISTING R-22 SYSTEMS MAY BE
REPAIRED AND/OR REPLACED.

NOTICE

UNITS MUST ONLY BE USED AS REPLACEMENT
COMPONENTS FOR PRE-2010 INSTALLED SYSTEMS.

NOTE:

 Holding charge must be removed before brazing.

Prolonged operation at suction pressures less than 20 
psig for more than 5 seconds will result in overheating of 
the scrolls and permanent damage to the scroll tips, drive 
bearings and internal seal.

CAUTION

1. Open service valves before attaching vacuum pump.

2. Connect the vacuum pump with 250 micron capability to

the service valves.

3. Evacuate the system to 250 microns or less using suc-

tion 

and

 liquid service valves.  Using both valves is nec-

essary as some compressors create a mechanical seal
separating the sides of the system.

4. Close pump valve and hold vacuum for 10 minutes.  Typi-

cally pressure will rise during this period.

If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to
startup.

5000

4500

4000

3500

3000

2500

2000

1500

1000

500

0      1      2      3      4       5      6      7      8       9

10

LEAK(S)
PRESENT

MINUTES

V

ACU

U

M

 

IN

 

MI

CR

O

N

S

CONDENSIBLES OR SMALL
LEAK PRESENT

NO LEAKS
NO CONDENSIBLES

If pressure rises above 1000 microns but holds steady
below 2000 microns, moisture and/or noncondensibles
may be present or the system may have a small leak.
Return to step 2: If the same result is encountered check
for leaks as previously indicated and repair as necessary
then repeat evacuation.

If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as nec-
essary then repeat evacuation.

Electrical Connections

HIGH VOLTAGE!

 

Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death due to electric shock.
Wiring must conform with NEC or CEC and all
local codes. Undersized wires could cause
poor equipment performance, equipment damage
or fire.

WARNING

To avoid the risk of fire or equipment damage, use
copper conductors.

WARNING

NOTICE

UNITS WITH RECIPROCATING COMPRESSORS AND
NON-BLEED TXV’S REQUIRE A HARD START KIT.

The condensing unit rating plate lists pertinent electrical data
necessary for proper electrical service and overcurrent protec-
tion.  Wires should be sized to limit voltage drop to 2% (max.)
from the main breaker or fuse panel to the condensing unit.
Consult the NEC, CEC, and all local codes to determine the
correct wire gauge and length.

Содержание IO-402K

Страница 1: ...it upright laying the unit on its side or top may cause equipment damage Shipping damage and subse quent investigation is the responsibility of the carrier Verify the model number specifications elect...

Страница 2: ...not shift or settle To reduce the possibility of sound transmission the foundation slab should not be in contact with or be an integral part of the building foundation Ensure the foundation is suffici...

Страница 3: ...ooling Service Manual or TP 106 Long Line Set Application R 22 or contact your distributor for assistance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4...

Страница 4: ...dents Any other condition increases the chance of a refrigerant leak 2 Sweep the refrigerant line with nitrogen or inert gas dur ing brazing to prevent the formation of copper oxide in side the refri...

Страница 5: ...ring this period If the pressure rises to 1000 microns or less and remains steady the system is considered leak free proceed to startup 5000 4500 4000 3500 3000 2500 2000 1500 1000 500 0 1 2 3 4 5 6 7...

Страница 6: ...a possible refrigerant leak open the service valves until the top of the stem is 1 8 from the retainer CAUTION When opening valves with retainers open each valve only until the top of the stem is 1 8...

Страница 7: ...OR OTHER PENALTIES Operating the compressor with the suction valve closed may cause serious compressor damage CAUTION Final Charge Adjustment The outdoor temperature must be 60 F or higher Set the ro...

Страница 8: ...25 n a 435 n a 445 n a 475 n a 500 n a 525 n a 550 n a 575 n a 600 n a 625 n a SATURATED LIQUID PRESSURE TEMPERATURE CHART SUCTION PRESSURE SATURATED SUCTION TEMPERATURE F PSIG R 22 50 26 52 28 54 29...

Страница 9: ...essure to stabilize 2 Temporarily install thermometer on liquid small line near liquid line service valve with adequate contact and insu late for best possible reading 3 Check subcooling and superheat...

Страница 10: ...it Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resis...

Страница 11: ...11 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually c...

Отзывы: