The United States Environmental Protection Agency (EPA)
has issued various regulations regarding the introduc-
tion and disposal of refrigerants. Failure to follow these
regulations may harm the environment and can lead to
the imposition of substantial fines. 

Should you have any

questions please contact the local office of the EPA.

If replacing a condensing unit or air handler, the system must
be manufacturer approved and Air Conditioning, Heating and
Refrigeration Institute (AHRI) matched.  

NOTE: 

Installation of

unmatched systems is strongly discouraged.

Operating the unit in a structure that is not complete (either as
part of new construction or renovation) will void the warranty.

Installation Clearances

Special consideration must be given to location of the con-
densing unit(s) in regard to structures, obstructions, other units,
and any/all other factors that may interfere with air circulation.
Where possible, the top of the unit should be completely unob-
structed; however, if vertical conditions require placement be-
neath an obstruction 

there should be a minimum of 60

inches between the top of the unit and the obstruction(s).

The specified dimensions meet requirements for air circulation
only. Consult all appropriate regulatory codes prior to deter-
mining final clearances.

Another important consideration in selecting a location for the
unit(s) is the angle to obstructions.  Either side adjacent the
valves can be placed toward the structure provided the side
away from the structure maintains minimum service clearance.
Corner installations are strongly discouraged.

OK!

OK!

AA

AA

A

A

C

C

C

C

OK!

OK!

OK!

OK!

NOT

RECOMMENDED

AA

AA

AA

AA

AA

B

B

B

B

Model Type

A

B

C

AA

Residential

10"

10"

18"

20"

Light Commercial

12"

12"

18"

24"

Minimum Airflow Clearance

This unit can be located at ground floor level or on flat roofs. At
ground floor level, the unit must be on a solid, level foundation
that will not shift or settle. To reduce the possibility of sound
transmission, the foundation slab should not be in contact with
or be an integral part of the building foundation. Ensure the
foundation is sufficient to support the unit. A concrete slab
raised above ground level provides a suitable base.

Rooftop Installations

If it is necessary to install this unit on a roof structure, ensure
the roof structure can support the weight and that proper con-
sideration is given to the weather-tight integrity of the roof. Since
the unit can vibrate during operation, sound vibration transmis-
sion should be considered when installing the unit. Vibration
absorbing pads or springs can be installed between the con-
densing unit legs or frame and the roof mounting assembly to
reduce noise vibration.

Safe Refrigerant Handling

While these items will not cover every conceivable situation,
they should serve as a useful guide.

To avoid possible injury, explosion or death, practice
safe handling of refrigerants.

WARNING

Refrigerants are heavier than air. They can "push out"
the oxygen in your lungs or in any enclosed space.To
avoid possible difficulty in breathing or death:

•  

Never purge refrigerant into an enclosed room or

   space. By law, all refrigerants must be reclaimed.

•  

If an indoor leak is suspected, throughly ventilate the

   area before beginning work.
•  Liquid refrigerant can be very cold. To avoid possible
   frostbite or blindness, avoid contact and wear gloves
   and goggles.  If liquid refrigerant does contact your
   skin or eyes, seek medical help immediately.
•  Always follow EPA regulations. Never burn refrig-
   erant, as poisonous gas will be produced.

WARNING

To avoid possible explosion:
  Never apply flame or steam to a refrigerant cylinder.
    If you must heat a cylinder for faster charging,
    partially immerse it in warm water.

Never fill a cylinder more than 80% full of liquid re-

    frigerant.
•   Never add anything other than R-22 to an R-22 cy-
    linder . The service equipment used must be listed
    or certified for the type of refrigerant used.
•   Store cylinders in a cool, dry place. Never use a cy-
    linder as a platform or a roller.

•  

•   

Содержание IO-402K

Страница 1: ...it upright laying the unit on its side or top may cause equipment damage Shipping damage and subse quent investigation is the responsibility of the carrier Verify the model number specifications elect...

Страница 2: ...not shift or settle To reduce the possibility of sound transmission the foundation slab should not be in contact with or be an integral part of the building foundation Ensure the foundation is suffici...

Страница 3: ...ooling Service Manual or TP 106 Long Line Set Application R 22 or contact your distributor for assistance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4...

Страница 4: ...dents Any other condition increases the chance of a refrigerant leak 2 Sweep the refrigerant line with nitrogen or inert gas dur ing brazing to prevent the formation of copper oxide in side the refri...

Страница 5: ...ring this period If the pressure rises to 1000 microns or less and remains steady the system is considered leak free proceed to startup 5000 4500 4000 3500 3000 2500 2000 1500 1000 500 0 1 2 3 4 5 6 7...

Страница 6: ...a possible refrigerant leak open the service valves until the top of the stem is 1 8 from the retainer CAUTION When opening valves with retainers open each valve only until the top of the stem is 1 8...

Страница 7: ...OR OTHER PENALTIES Operating the compressor with the suction valve closed may cause serious compressor damage CAUTION Final Charge Adjustment The outdoor temperature must be 60 F or higher Set the ro...

Страница 8: ...25 n a 435 n a 445 n a 475 n a 500 n a 525 n a 550 n a 575 n a 600 n a 625 n a SATURATED LIQUID PRESSURE TEMPERATURE CHART SUCTION PRESSURE SATURATED SUCTION TEMPERATURE F PSIG R 22 50 26 52 28 54 29...

Страница 9: ...essure to stabilize 2 Temporarily install thermometer on liquid small line near liquid line service valve with adequate contact and insu late for best possible reading 3 Check subcooling and superheat...

Страница 10: ...it Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resis...

Страница 11: ...11 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually c...