background image

4

ensure lines are adequately protected and sealed.

Refrigerant Line Connections

NOTICE

THIS UNIT IS SHIPPED WITH A NITROGEN/HELIUM
HOLDING CHARGE ONLY.  UNIT MUST BE EVACUATED
AND CHARGED PER INSTALLATION INSTRUCTIONS
WITH REFRIGERANT LISTED ON SERIAL RATING PLATE.

NOTICE

UNITS SHIPPED WITH A HOLDING CHARGE ARE
INTENDED FOR COMPONENT REPLACEMENT ONLY ON
EXISTING SYSTEMS, AND NOT INTENDED FOR USE IN
NEW SYSTEMS OR NEWLY CONSTRUCTED HOMES.
EPA REGULATIONS PROHIBIT THE SALE OR
DISTRIBUTION OF APPLIANCES PRE-CHARGED WITH
THE REFRIGERANT R-22 IF THOSE APPLIANCES ARE
MANUFACTURED AFTER JANUARY 1, 2010.
COMPONENTS OF EXISTING R-22 SYSTEMS MAY BE
REPAIRED AND/OR REPLACED.

NOTICE

UNITS MUST ONLY BE USED AS REPLACEMENT
COMPONENTS FOR PRE-2010 INSTALLED SYSTEMS.

NOTE:

 Holding charge must be removed before brazing.  Open

service valves slowly to remove holding charge.  Close valves
before brazing to prevent contaminants from entering system.

IMPORTANT

To avoid overheating the service valve, TXV valve, or filter
drier while brazing, wrap the component with a wet rag, or
use a thermal heat trap compound. Be sure to follow the
manufacturer’s instruction when using the heat trap
compound. Note: Remove Schrader valves from service
valves before brazing tubes to the valves. Use a brazing
alloy of 2% minimum silver content. Do not use flux.

Torch heat required to braze tubes of various sizes is
proportional to the size of the tube. Tubes of smaller size
require less heat to bring the tube to brazing temperature
before adding brazing alloy. Applying too much heat to
any tube can melt the tube. Service personnel must use
the appropriate heat level for the size of the tube being
brazed. Note: The use of a heat shield when brazing is
recommended to avoid burning the serial plate or the finish
on the unit.

1. The ends of the refrigerant lines must be cut square, de-

burred, cleaned, and be round and free from nicks or dents.
Any other condition increases the chance of a refrigerant
leak.

2.  “Sweep” the refrigerant line with nitrogen or inert gas dur-

ing brazing to prevent the formation of copper-oxide in-

side the refrigerant lines.  This may cause a blockage or
failure of the metering device.

3. After brazing, quench the joints with water or a wet cloth

to prevent overheating of the service valve.

4. Ensure the filter drier paint finish is intact after brazing.  If

the paint of the steel filter drier has been burned or chipped,
repaint or treat with a rust preventative.  This is especially
important on suction line filter driers which are continu-
ally wet when the unit is operating.

NOTE: 

 Be careful not to kink or dent refrigerant lines.  Kinked

or dented lines will cause poor performance or compressor
damage.

Do NOT make final refrigerant line connection until plugs are
removed from refrigerant tubing.

NOTE:  

Before brazing, verify indoor piston size by checking

the piston kit chart packaged with indoor unit.

Leak Testing (Nitrogen or Nitrogen-Traced)

To avoid the risk of fire or explosion, never use
oxygen, high pressure air or flammable gases for leak
testing of a refrigeration system.

WARNING

To avoid possible explosion, the line from the
nitrogen cylinder must include a pressure regulator
and a pressure relief valve. The pressure relief valve
must be set to open at no more than 150 psig.

WARNING

Pressure test the system using dry nitrogen and soapy water
to locate leaks.  If you wish to use a leak detector, charge the
system to 10 psi using the appropriate refrigerant then use
nitrogen to finish charging the system to working pressure then
apply the detector to suspect areas. If leaks are found, repair
them. After repair, repeat the pressure test. If no leaks exist,
proceed to system evacuation.

System Evacuation

Condensing unit liquid and suction valves are closed.  The unit
is shipped with the valve stems closed and caps installed.

REFRIGERANT UNDER PRESSURE!

 

Failure to follow proper procedures may cause 
property damage, personal injury or death.

WARNING

NOTE: 

Scroll compressors should never be used to evacuate

Содержание IO-402K

Страница 1: ...it upright laying the unit on its side or top may cause equipment damage Shipping damage and subse quent investigation is the responsibility of the carrier Verify the model number specifications elect...

Страница 2: ...not shift or settle To reduce the possibility of sound transmission the foundation slab should not be in contact with or be an integral part of the building foundation Ensure the foundation is suffici...

Страница 3: ...ooling Service Manual or TP 106 Long Line Set Application R 22 or contact your distributor for assistance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4...

Страница 4: ...dents Any other condition increases the chance of a refrigerant leak 2 Sweep the refrigerant line with nitrogen or inert gas dur ing brazing to prevent the formation of copper oxide in side the refri...

Страница 5: ...ring this period If the pressure rises to 1000 microns or less and remains steady the system is considered leak free proceed to startup 5000 4500 4000 3500 3000 2500 2000 1500 1000 500 0 1 2 3 4 5 6 7...

Страница 6: ...a possible refrigerant leak open the service valves until the top of the stem is 1 8 from the retainer CAUTION When opening valves with retainers open each valve only until the top of the stem is 1 8...

Страница 7: ...OR OTHER PENALTIES Operating the compressor with the suction valve closed may cause serious compressor damage CAUTION Final Charge Adjustment The outdoor temperature must be 60 F or higher Set the ro...

Страница 8: ...25 n a 435 n a 445 n a 475 n a 500 n a 525 n a 550 n a 575 n a 600 n a 625 n a SATURATED LIQUID PRESSURE TEMPERATURE CHART SUCTION PRESSURE SATURATED SUCTION TEMPERATURE F PSIG R 22 50 26 52 28 54 29...

Страница 9: ...essure to stabilize 2 Temporarily install thermometer on liquid small line near liquid line service valve with adequate contact and insu late for best possible reading 3 Check subcooling and superheat...

Страница 10: ...it Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resis...

Страница 11: ...11 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually c...

Отзывы: