background image

UNIT LOCATION

TO PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL

INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED

WHEN INSTALLING THE UNIT.

IMPORTANT NOTE: Remove wood shipping rails prior to installa-

tion of the unit.

A L L INSTALLATIONS:

• For proper flame pattern within the heat exchanger and

proper condensate drainage, the unit must be mounted

level.

• The flue outlet hood must be at least 12 inches from any

opening through which flue gases could enter a building,
and at least three feet above any forced air inlet located

within ten feet The economizer/manual fresh air intake/

motorized fresh air intake and combustion air inlet mounted
on the unit are not affected by this restriction.

• To avoid possible corrosion of the heat exchanger, do not

locate the unit in an area where the outdoor air (i.e.
combustion air for the unit) will be frequently contaminated
by compounds containing chlorine or fluorine. Common

sources of such compounds include swimming pool

chemicals and chlorine bleaches, paint stripper, adhesives,
paints, varnishes, sealers, waxes (which are not yet dried)

and solvents used during construction and remodeling.
Various commercial and industrial processes may also

be sources of chlorine/fluorine compounds.

• To avoid possible illness or death of the building occupants,

do NOT locate outside air intake device (economizer,

manual fresh air intake, motorized fresh air intake) too

close to an exhaust outlet, gas vent termination, or

plumbing vent outlet. For specific distances required,

consult local codes.

• Allow minimum clearances from the enclosure for fire

protection, proper operation, and service access (see
appendix). These clearances must be permanently
maintained.

• The combustion air inlet and flue outlet hoods on the unit

must never be obstructed. If used, do not allow the

economizer/manual fresh air damper/ motorized fresh air
damper to become blocked by snow or debris. In some
climates or locations, it may be necessary to elevate the
unit to avoid these problems.

• When the unit is heating, the temperature of the return air

entering the unit must be between 50° F and 100° F.

G R O U N D LEVEL INSTALLATIONS  O N L Y :

• When the unit is installed on the ground adjacent to the

building, a level concrete (or equal) base is recommended.

Prepare a base that is 3" larger than the package unit

footprint and a minimum of 3" thick.

• The base should also be located where no runoff of water

from higher ground can collect in the unit.

Outside Slab Installation

R O O F T O P INSTALLATIONS  O N L Y :

• To avoid possible property damage or personal injury, the

roof must have sufficient structural strength to carry the

weight of the unit(s) and snow or water loads as required by

local codes. Consult a structural engineer to determine the

weight capabilities of the roof.

Rooftop Installation

• The unit may be installed directly on wood floors or on Class

A, Class B, or Class C roof covering material.

• To avoid possible personal injury, a safe, flat surface for

service personnel should be provided.

ROOF CURB INSTALLATIONS ONLY:

• Sufficient structural support must be determined prior to

locating and mounting the curb and package unit.

• Ductwork must be constructed using industry guidelines. The

duct work must be placed into the roof curb before mounting

the package unit.

• Curb insulation, cant strips, flashing and general roofing

material are furnished by the contractor.

Содержание GPG10

Страница 1: ...h this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the customer on it...

Страница 2: ......

Страница 3: ...H DEFECTS OR OTHER REPRODUCTIVE HARM HEATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASONABLE ROUTINE INSPECTION MAINTENANCE AND SUPERVISION F THE BUILIDNG IN WHICH ANY SUCH DEVICE IS LOCATED WILL BE VA...

Страница 4: ...for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructe...

Страница 5: ...any visible damage to shipment or container 2 Notify carrier promptly and request an inspection 3 In case of concealed damage carrier should be notified as soon as possible preferabiy within 5 days 4...

Страница 6: ...ing of equipment do not under size the natural propane gas piping from the meter tank to the unit When sizing a trunk line as shown in Table 2 include all appliances on that line that could be operate...

Страница 7: ...he unit PROPANE GAS INSTALLATIONS TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK INSTALL A GAS DETECTING WARNING DEVICE SINCE RUST CAN REDUCE T...

Страница 8: ...may use thermostats with one or two stages of cooling To AVOID INJURY ELECTRICAL SHOCK OR DEATH DISCONNECT ELECTRICAL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING The units are designed f...

Страница 9: ...static and review the blower performance charts before performing the installation In some installations it will be necessary to change the blower speed to provide proper air flow Horizontal Air Flow...

Страница 10: ...E RETURN AIR SYSTEM Even though a return air filter is not supplied with this unit there must be a means of filtering all return air The PG1248 and PG1260 models are provided with internal filter rack...

Страница 11: ...ons in or near the blower motors Duct covers must be removed before operating unit Heat Anticipator Setting Set the heat anticipator on the room thermostat to 0 4 amps to obtain the proper number of h...

Страница 12: ...r having a scale range from 0 to 12 inches of water should be used for this measurement The manifold pressure must be measured with the burners operating To adjust the pressure regulator remove the ad...

Страница 13: ...nutes of operation by blocking the return air grille s 1 After several minutes the main burners must go OFF Blower will continue to run 2 Remove air restrictions and main burners will relight after a...

Страница 14: ...supply for over five seconds If the diagnostic LED indicates an external lockout perform the following checks Check the supply and manifold pressures Check the gas orifices for debris Check gas valve...

Страница 15: ...many hardware stores Permanent filters should last several years However should one become torn or uncleanable it should be replaced CABINET FINISH MAINTENANCE Use a fine grade automotive wax on the...

Страница 16: ...onnect electrical power and gas supply LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION ALWAYS VERIFY PROPER OPERATION AFTER SERV...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Отзывы: