background image

function of outdoor ambient temperature and return air
temperature of the conditioned space. It is the installing

contractors responsibility to ensure the proper refrigerant

superheat at the compressor is adjusted for each application.

For example, 10 degree refrigerant superheat level is adequate

for a 95 degree outdoor ambient temperature and a 78 - 80

degree for indoor return air temperature. As the outdoor
ambient temperature rises the superheat decreases and as

the outdoor ambient temperature lowers the superheat

increases. Proper superheat adjustment optimizes cooling
performance.

Cooling Operation

NOTE: Mechanical cooling cannot be reliably provided at ambient

temperatures below 50° F.

1. Turn on the electrical power supply to the unit.

2. Place the room thermostat selector switch in the COOL

position (or AUTO if available, and if automatic changeover

from cooling to heating is desired).

3. Set the room thermostat to the desired temperature.

TROUBLESHOOTING

IGNITION CONTROL ERROR CODES

The following presents probable causes of questionable unit

operation. Refer to Diagnostic indicator Chart for an

interpretation of the signal and to this section for an explanation.

Remove the control box access panel and note the number of

diagnostic LED flashes. Refer to Diagnostic Indicator Chart
for an interpretation of the signal and to this section for an
explanation.

ABNORMAL OPERATION - HEATING

Internal Control Failure

If the integrated ignition control in this unit encounters an

internal fault, it will go into a "hard" lockout and turn off the
diagnostic LED. If diagnostic LED indicates an internal fault,
check power supply to unit for proper voltage, check all

fuses, circuit breakers and wiring. Disconnect electric power

for five seconds. If LED remains off after restoring power,

replace control.

External Lockout

An external lockout occurs if the integrated ignition control

determines that a measurable combustion cannot be

established within three (3) consecutive ignition attempts.

If flame is not established within the seven (7) second trial

for ignition, the gas valve is deenergized, 15 second inter-

purge cycle is completed, and ignition is reattempted. The
control will repeat this routine three times if a measurable
combustion is not established. The control will then shut

off the induced draft blower and go into a lockout state.

If flame is established but lost, the control will energize the

circulator blower at the heat speed and then begin a new

ignition sequence. If flame is established then lost on

subsequent attempts, the control will recycle for four (4)
consecutive ignition attempts (five attempts total) before
locking out.

The diagnostic fault code is 1 flash for a lockout due to

failed ignition attempts or flame dropouts. The integrated

control will automatically reset after one hour, or it can be
reset by removing the thermostat signal or disconnecting

the electrical power supply for over five seconds. If the

diagnostic LED indicates an external lockout, perform the

following checks;

 Check the supply and manifold pressures
• Check the gas orifices for debris
 Check gas valve for proper operation
 Check secondary limit

A dirty filter, excessive duct static, insufficient air flow, a
faulty limit, or a failed circulator blower can cause this

limit to open. Check filters, total external duct static,
circulator blower motor, blower motor speed tap (see

wiring diagram), and limit. An interruption in electrical

power during a heating cycle may also cause the auxiliary

limit to open. The secondary limit is located on top of the
circulator blower assembly. The automatic reset auxiliary
limit is located on the circulator blower scroll.

 Check rollout limit

If the burner flames are not properly drawn into the heat

exchanger, the flame rollout protection device will open.
Possible causes are restricted or blocked flue passages,
blocked or cracked heat exchanger, a failed induced draft

blower, or insufficient combustion air. The rollout

protection device is a manual reset limit located on the
burner bracket. The cause of the flame rollout must be

determined and corrected before resetting the limit.

 Check flame sensor

A drop in flame signal can be caused by nearly invisible

coating on the sensor. Remove the sensor and carefully
clean with steel wool.

 Check wiring

Check wiring for opens/shorts and miswiring.

Important: If you have to frequently reset your gas/electric

package unit, it means that a problem exists that should be
corrected. Contact a qualified servicer for further information.

Pressure Switch Stuck Open

A pressure switch stuck open can be caused by a faulty

pressure switch, faulty wiring, a disconnected or damaged
hose, a blocked or restricted flue, or a faulty induced draft
blower.
If the control senses an open pressure switch during the

pre-purge cycle, the induced draft blower only will be
energized. If the pressure switch opens after ignition has
begun the gas valve is deenergized, the circulator blower
heat off cycle begins, and the induced draft blower remains

on. The diagnostic fault code is two flashes.

Pressure Switch Stuck Closed

A stuck closed pressure switch can be caused by a faulty

pressure switch or faulty wiring. If the control encounters a
pressure switch stuck closed, the induced draft blower
remains off. The diagnostic LED code for this fault is three

(3) flashes.

Open Thermal Protection Device

If the primary limit switch opens, the gas valve is immediately

deenergized, the induced draft and air circulating blowers

are energized. The induced draft and air circulator blowers

remain energized until the limit switch recloses. The
diagnostic fault code for an open limit is four (4) flashes.

A primary limit will open due to excessive supply air
temperatures. This can be caused by a dirty filter, excessive

duct static, insufficient airflow, or a faulty limit. Check filters,

total external duct static, blower motor, blower motor speed

tap (see wiring diagram), and limit This limit will automatically

reset once the temperature falls below a preset level.

14

Содержание GPG10

Страница 1: ...h this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the customer on it...

Страница 2: ......

Страница 3: ...H DEFECTS OR OTHER REPRODUCTIVE HARM HEATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASONABLE ROUTINE INSPECTION MAINTENANCE AND SUPERVISION F THE BUILIDNG IN WHICH ANY SUCH DEVICE IS LOCATED WILL BE VA...

Страница 4: ...for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructe...

Страница 5: ...any visible damage to shipment or container 2 Notify carrier promptly and request an inspection 3 In case of concealed damage carrier should be notified as soon as possible preferabiy within 5 days 4...

Страница 6: ...ing of equipment do not under size the natural propane gas piping from the meter tank to the unit When sizing a trunk line as shown in Table 2 include all appliances on that line that could be operate...

Страница 7: ...he unit PROPANE GAS INSTALLATIONS TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK INSTALL A GAS DETECTING WARNING DEVICE SINCE RUST CAN REDUCE T...

Страница 8: ...may use thermostats with one or two stages of cooling To AVOID INJURY ELECTRICAL SHOCK OR DEATH DISCONNECT ELECTRICAL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING The units are designed f...

Страница 9: ...static and review the blower performance charts before performing the installation In some installations it will be necessary to change the blower speed to provide proper air flow Horizontal Air Flow...

Страница 10: ...E RETURN AIR SYSTEM Even though a return air filter is not supplied with this unit there must be a means of filtering all return air The PG1248 and PG1260 models are provided with internal filter rack...

Страница 11: ...ons in or near the blower motors Duct covers must be removed before operating unit Heat Anticipator Setting Set the heat anticipator on the room thermostat to 0 4 amps to obtain the proper number of h...

Страница 12: ...r having a scale range from 0 to 12 inches of water should be used for this measurement The manifold pressure must be measured with the burners operating To adjust the pressure regulator remove the ad...

Страница 13: ...nutes of operation by blocking the return air grille s 1 After several minutes the main burners must go OFF Blower will continue to run 2 Remove air restrictions and main burners will relight after a...

Страница 14: ...supply for over five seconds If the diagnostic LED indicates an external lockout perform the following checks Check the supply and manifold pressures Check the gas orifices for debris Check gas valve...

Страница 15: ...many hardware stores Permanent filters should last several years However should one become torn or uncleanable it should be replaced CABINET FINISH MAINTENANCE Use a fine grade automotive wax on the...

Страница 16: ...onnect electrical power and gas supply LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION ALWAYS VERIFY PROPER OPERATION AFTER SERV...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Отзывы: