background image

Main Burner Flame Check

Flames should be stable, soft and blue (dust may cause orange

tips but they must not be yellow) and extending directly outward
from the burner without curling, floating or lifting off.

Temperature Rise Check

Check the temperature rise through the unit by placing

thermometers in supply and return air registers as close to the

unit as possible. Thermometers must not be able to sample

temperature directly from the unit heat exchangers, or false

readings could be obtained.
1. All registers must be open; ail duct dampers must be in their

final (fully or partially open) position and the unit operated

for 15 minutes before taking readings.

2. The temperature rise must be within the range specified on

the rating plate.

NOTE: Air temperature rise is the temperature difference between
supply and return air.

With a properly designed system, the proper amount of
temperature rise will normally be obtained when the unit is

operated at rated input with the recommended blower speed,
if the correct amount of temperature rise is not obtained, it
may be necessary to change the blower speed. A higher blower

speed will lower the temperature rise. A slower blower speed

will increase the temperature rise.

NOTE: Blower speed MUST be set to give the correct air tempera-

ture rise through the unit as marked on the rating plate.

External Static Pressure Check

The total external static pressure must be checked on this unit

to determine if the airflow is proper.

Blower Speed Adjustments

TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE

ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE

BLOWER MOTOR.

Refer to the wiring diagram in the appendix to verify speed tap

settings.

Blower speeds are to be changed at the ignition control board.

Both heat speed and cool speed terminals are supplied on the
board along with two unused motor lead terminals.

Limit Check

Check limit control operation after 15 minutes of operation by
blocking the return air grille(s).
1. After several minutes the main burners must go OFF. Blower

will continue to run.

2. Remove air restrictions and main burners will relight after a

cool down period of a few minutes.

Adjust the thermostat setting below room temperature.

1. Main burners must go OFF.

2. Circulating Air Blower will continue to run for 120, 135 or

150 seconds, depending on the setting.

Control Board (Top)

NOTE: If necessary, adjust fan OFF delay settings to obtain satis-

factory comfort level.

THIS UNIT MUST NOT BE USED AS A -CONSTRUCTION HEATER- DURING THE

FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE. THIS TYPE OF

USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY

LOW RETURN AIR TEMPERATURES AND EXPOSURE TO CORROSIVE OR VERY

DIRTY ATMOSPHERES.

Unit Shutdown

1. Set the thermostat to lowest setting.

2. Turn off the electrical power supply to the unit.

3. Remove the heat exchanger door on the side of the unit by

removing screws.

4. Move (Figures 12 & 13) or rotate (Figure 14) the gas control

valve switch to the OFF position. Do not force.

5. Close manual gas shutoff valve external to the unit.

6. Replace the heat exchanger door on the unit.
7. If cooling and/or air circulation will be desired, turn ON the

electrical power.

COOLING STARTUP

NOTE: Check all manual reset limit controls in heating circuit if cool-

ing mode does not operate.

Compressor Protection Devices

The compressor includes components which are designed to

protect the compressor against abnormal operating conditions.

TO PREVENT PERSONAL INJURY OR DEATH, ALWAYS DISCONNECT ELECTRICAL,

POWER BEFORE INSPECTING OR SERVICING THE UNIT.  A L L COMPRESSOR

PROTECTION DEVICES RESET AUTOMATICALLY, ENERGIZING THE CONTACTOR

AND OUTDOOR FAN.

Cooling Refrigerant Charging

Check unit charge before putting the cooling section into full

operation. The unit is factory charged with R-22 for nominal air

flow and static pressure conditions. The unit has a piston
flowrator expansion device. To ensure the unit is properly

charged for the intended application, check the unit refrigerant
superheat at the compressor. The refrigerant superheat is a

13

Содержание GPG10

Страница 1: ...h this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the customer on it...

Страница 2: ......

Страница 3: ...H DEFECTS OR OTHER REPRODUCTIVE HARM HEATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASONABLE ROUTINE INSPECTION MAINTENANCE AND SUPERVISION F THE BUILIDNG IN WHICH ANY SUCH DEVICE IS LOCATED WILL BE VA...

Страница 4: ...for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructe...

Страница 5: ...any visible damage to shipment or container 2 Notify carrier promptly and request an inspection 3 In case of concealed damage carrier should be notified as soon as possible preferabiy within 5 days 4...

Страница 6: ...ing of equipment do not under size the natural propane gas piping from the meter tank to the unit When sizing a trunk line as shown in Table 2 include all appliances on that line that could be operate...

Страница 7: ...he unit PROPANE GAS INSTALLATIONS TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK INSTALL A GAS DETECTING WARNING DEVICE SINCE RUST CAN REDUCE T...

Страница 8: ...may use thermostats with one or two stages of cooling To AVOID INJURY ELECTRICAL SHOCK OR DEATH DISCONNECT ELECTRICAL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING The units are designed f...

Страница 9: ...static and review the blower performance charts before performing the installation In some installations it will be necessary to change the blower speed to provide proper air flow Horizontal Air Flow...

Страница 10: ...E RETURN AIR SYSTEM Even though a return air filter is not supplied with this unit there must be a means of filtering all return air The PG1248 and PG1260 models are provided with internal filter rack...

Страница 11: ...ons in or near the blower motors Duct covers must be removed before operating unit Heat Anticipator Setting Set the heat anticipator on the room thermostat to 0 4 amps to obtain the proper number of h...

Страница 12: ...r having a scale range from 0 to 12 inches of water should be used for this measurement The manifold pressure must be measured with the burners operating To adjust the pressure regulator remove the ad...

Страница 13: ...nutes of operation by blocking the return air grille s 1 After several minutes the main burners must go OFF Blower will continue to run 2 Remove air restrictions and main burners will relight after a...

Страница 14: ...supply for over five seconds If the diagnostic LED indicates an external lockout perform the following checks Check the supply and manifold pressures Check the gas orifices for debris Check gas valve...

Страница 15: ...many hardware stores Permanent filters should last several years However should one become torn or uncleanable it should be replaced CABINET FINISH MAINTENANCE Use a fine grade automotive wax on the...

Страница 16: ...onnect electrical power and gas supply LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION ALWAYS VERIFY PROPER OPERATION AFTER SERV...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Отзывы: