Flame Detected with Gas Valve Closed
If flame is detected with the gas valve deenergized, the
combustion and air circulator blowers are energized. The
diagnostic fault code is five (5) flashes for this condition.
The control can be reset by removing the power supply to
the unit or it will automatically reset after one hour. Miswiring
is the probable cause for this fault.
ABNORMAL OPERATION - COOLING
Short Cycle Compressor Delay
The automatic ignition control has a built-in feature that prevents
damage to the compressor in short cycling situations. In the
event of intermittent power losses or intermittent thermostat
operation, the ignition control will delay output to the compressor
contactor for three minutes from the time power is restored,
(Compressor is off a total of three minutes). The diagnostic
LED will flash six (6) times to indicate the compressor contactor
output is being delayed.
NOTE: Some electronic thermostats also have a built-in compressor
short cycle timer that may be longer than the three minute delay
given above. If you are using an electronic thermostat and the
compressor has not started after three minutes, wait an additional
five minutes to allow the thermostat to complete its short cycle delay
time.
MAINTENANCE
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK,
DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY MAINTENANCE.
Have the gas heating section of the unit checked at least once
a year before the heating season begins, to be sure that the
combustion air inlet and flue outlet hoods are not blocked by
debris, which would prevent adequate combustion air and a
properly operating vent system.
FILTER REPLACEMENT OR CLEANING
A return air filter is not supplied with this unit; however, there
must be a means of filtering all of the return air. The filter(s)
may be located in the return air duc(s), or return air filter grille(s).
Consult with your installing dealer for the actual location of the
return air filter(s) for your unit.
Dirty filters are the most common cause of inadequate heating
or cooling performance. Filter inspection should be made at
least every two months; more often if necessary because of
local conditions and usage.
Dirty throwaway filters should be discarded and replaced with
a new, clean filter Dirty permanent filters should be washed
with water, thoroughly dried and sprayed with a filter adhesive
before being reinstalled. (Filter adhesives may be found at many
hardware stores.) Permanent filters should last several years.
However, should one become torn or uncleanable, it should
be replaced.
CABINET FINISH MAINTENANCE
Use a fine grade automotive wax on the cabinet finish to
maintain the finish's original high luster. This is especially
important in installations with extended periods of direct sunlight.
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)
The coil with the outside air flowing over it should be inspected
annually and cleaned as frequently as necessary to keep the
finned areas free of lint, hair and debris.
CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS
Bearings on the air circulating blower motor, condenser motor
and the combustion fan motor are permanently lubricated. No
additional oiling is required.
FLAME SENSOR (QUALIFIED SERVICER ONLY)
A drop in the flame current can be caused by a nearly invisible
coating on the flame sensor. This coating, created by the fuel or
combustion air supply, can be removed by carefully cleaning
the flame sensor with steel wool (Figure 18).
NOTE: After cleaning, the microamp signal should be stable and in
the range of 4 - 6 microamps DC.
Flame Sensor
F L U E PASSAGES (QUALIFIED SERVICER O N L Y )
At the start of each heating season, inspect and, if necessary,
clean the unit flue passage.
CLEANING F L U E PASSAGES (QUALIFIED SERVICER O N L Y )
1. Shut off electric power and gas supply to the unit.
2. Remove burner assembly by disconnecting the gas line and
removing the manifold bracket from the partition panel.
3. Remove the flue from the induced draft blower and the
collector box cover from the partition panel.
4. The primary heat exchanger tubes can be cleaned using a
round wire brush attached to a length of high grade stainless
steel cable, such as drain cleanout cable. Attach a variable
speed reversible drill to the other end of the spring cable.
Slowly rotate the cable with the drill and insert it into one of
the primary heat exchanger tubes. While reversing the drill,
work the cable in and out several times to obtain sufficient
cleaning. Use a large cable for the large tube, and then repeat
the operation with a small cable for the smaller tube. Repeat
for each tube.
5. When all heat exchanger tubes have been cleaned, replace
the parts in the reverse order in which they were removed.
6. To reduce the chances of repeated fouling of the heat
exchanger, perform the steps listed in "Startup, Adjustments,
and Checks".
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY)
Flames should be stable, soft and blue (dust may cause orange
tips but must not be yellow). The flames must extend directly
outward from the burner without curling, floating or lifting off.
15