background image

Flame Detected with Gas Valve Closed

If flame is detected with the gas valve deenergized, the

combustion and air circulator blowers are energized. The
diagnostic fault code is five (5) flashes for this condition.
The control can be reset by removing the power supply to

the unit or it will automatically reset after one hour. Miswiring

is the probable cause for this fault.

ABNORMAL OPERATION - COOLING

Short Cycle Compressor Delay

The automatic ignition control has a built-in feature that prevents
damage to the compressor in short cycling situations. In the
event of intermittent power losses or intermittent thermostat
operation, the ignition control will delay output to the compressor
contactor for three minutes from the time power is restored,
(Compressor is off a total of three minutes). The diagnostic

LED will flash six (6) times to indicate the compressor contactor

output is being delayed.

NOTE: Some electronic thermostats also have a built-in compressor

short cycle timer that may be longer than the three minute delay
given above. If you are using an electronic thermostat and the
compressor has not started after three minutes, wait an additional

five minutes to allow the thermostat to complete its short cycle delay

time.

MAINTENANCE

TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK,

DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY MAINTENANCE.

Have the gas heating section of the unit checked at least once

a year before the heating season begins, to be sure that the
combustion air inlet and flue outlet hoods are not blocked by
debris, which would prevent adequate combustion air and a

properly operating vent system.

FILTER REPLACEMENT OR CLEANING

A return air filter is not supplied with this unit; however, there

must be a means of filtering all of the return air. The filter(s)

may be located in the return air duc(s), or return air filter grille(s).
Consult with your installing dealer for the actual location of the

return air filter(s) for your unit.
Dirty filters are the most common cause of inadequate heating

or cooling performance. Filter inspection should be made at
least every two months; more often if necessary because of

local conditions and usage.

Dirty throwaway filters should be discarded and replaced with
a new, clean filter Dirty permanent filters should be washed

with water, thoroughly dried and sprayed with a filter adhesive

before being reinstalled. (Filter adhesives may be found at many

hardware stores.) Permanent filters should last several years.
However, should one become torn or uncleanable, it should
be replaced.

CABINET FINISH MAINTENANCE

Use a fine grade automotive wax on the cabinet finish to
maintain the finish's original high luster. This is especially

important in installations with extended periods of direct sunlight.

CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)

The coil with the outside air flowing over it should be inspected

annually and cleaned as frequently as necessary to keep the

finned areas free of lint, hair and debris.

CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS

Bearings on the air circulating blower motor, condenser motor

and the combustion fan motor are permanently lubricated. No

additional oiling is required.

FLAME SENSOR (QUALIFIED SERVICER ONLY)

A drop in the flame current can be caused by a nearly invisible

coating on the flame sensor. This coating, created by the fuel or

combustion air supply, can be removed by carefully cleaning

the flame sensor with steel wool (Figure 18).

NOTE: After cleaning, the microamp signal should be stable and in

the range of 4 - 6 microamps DC.

Flame Sensor

F L U E PASSAGES (QUALIFIED SERVICER  O N L Y )

At the start of each heating season, inspect and, if necessary,

clean the unit flue passage.

CLEANING  F L U E PASSAGES (QUALIFIED SERVICER  O N L Y )

1. Shut off electric power and gas supply to the unit.

2. Remove burner assembly by disconnecting the gas line and

removing the manifold bracket from the partition panel.

3. Remove the flue from the induced draft blower and the

collector box cover from the partition panel.

4. The primary heat exchanger tubes can be cleaned using a

round wire brush attached to a length of high grade stainless

steel cable, such as drain cleanout cable. Attach a variable
speed reversible drill to the other end of the spring cable.
Slowly rotate the cable with the drill and insert it into one of

the primary heat exchanger tubes. While reversing the drill,
work the cable in and out several times to obtain sufficient

cleaning. Use a large cable for the large tube, and then repeat

the operation with a small cable for the smaller tube. Repeat
for each tube.

5. When all heat exchanger tubes have been cleaned, replace

the parts in the reverse order in which they were removed.

6. To reduce the chances of repeated fouling of the heat

exchanger, perform the steps listed in "Startup, Adjustments,
and Checks".

MAIN BURNER FLAME (QUALIFIED SERVICER ONLY)

Flames should be stable, soft and blue (dust may cause orange

tips but must not be yellow). The flames must extend directly

outward from the burner without curling, floating or lifting off.

15

Содержание GPG10

Страница 1: ...h this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the customer on it...

Страница 2: ......

Страница 3: ...H DEFECTS OR OTHER REPRODUCTIVE HARM HEATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASONABLE ROUTINE INSPECTION MAINTENANCE AND SUPERVISION F THE BUILIDNG IN WHICH ANY SUCH DEVICE IS LOCATED WILL BE VA...

Страница 4: ...for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructe...

Страница 5: ...any visible damage to shipment or container 2 Notify carrier promptly and request an inspection 3 In case of concealed damage carrier should be notified as soon as possible preferabiy within 5 days 4...

Страница 6: ...ing of equipment do not under size the natural propane gas piping from the meter tank to the unit When sizing a trunk line as shown in Table 2 include all appliances on that line that could be operate...

Страница 7: ...he unit PROPANE GAS INSTALLATIONS TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK INSTALL A GAS DETECTING WARNING DEVICE SINCE RUST CAN REDUCE T...

Страница 8: ...may use thermostats with one or two stages of cooling To AVOID INJURY ELECTRICAL SHOCK OR DEATH DISCONNECT ELECTRICAL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING The units are designed f...

Страница 9: ...static and review the blower performance charts before performing the installation In some installations it will be necessary to change the blower speed to provide proper air flow Horizontal Air Flow...

Страница 10: ...E RETURN AIR SYSTEM Even though a return air filter is not supplied with this unit there must be a means of filtering all return air The PG1248 and PG1260 models are provided with internal filter rack...

Страница 11: ...ons in or near the blower motors Duct covers must be removed before operating unit Heat Anticipator Setting Set the heat anticipator on the room thermostat to 0 4 amps to obtain the proper number of h...

Страница 12: ...r having a scale range from 0 to 12 inches of water should be used for this measurement The manifold pressure must be measured with the burners operating To adjust the pressure regulator remove the ad...

Страница 13: ...nutes of operation by blocking the return air grille s 1 After several minutes the main burners must go OFF Blower will continue to run 2 Remove air restrictions and main burners will relight after a...

Страница 14: ...supply for over five seconds If the diagnostic LED indicates an external lockout perform the following checks Check the supply and manifold pressures Check the gas orifices for debris Check gas valve...

Страница 15: ...many hardware stores Permanent filters should last several years However should one become torn or uncleanable it should be replaced CABINET FINISH MAINTENANCE Use a fine grade automotive wax on the...

Страница 16: ...onnect electrical power and gas supply LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION ALWAYS VERIFY PROPER OPERATION AFTER SERV...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Отзывы: