background image

GAS PIPING

Natural Gas Connection

IMPORTANT NOTE: This unit is factory set to operate on natural
gas at the altitudes shown on the rating plate.

TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH WHEN EITHER

USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES, OBTAIN AND INSTALL

THE PROPER CONVERSION KIT(S). FAILURE TO DO SO CAN RESULT IN

UNSATISFACTORY OPERATION AND/OR EQUIPMENT DAMAGE. HLGH ALTITUDE

KITS ARE FOR  U . S . INSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE

IN CANADA.

The rating plate is stamped with the model number, type of gas and

gas input rating. Make sure the unit is equipped to operate on the

type of gas available. Conversion to LP gas is permitted with the

use of the factory authorized conversion kit LPT-OOA.

Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table

Above.

The minimum supply pressure should not vary from that shown in
the table above because this could prevent the unit from having

dependable ignition. In addition, gas input to the burners must not
exceed the rated input shown on the rating plate. Overfiring of the

unit could result in premature heat exchanger failure.

HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY)

IMPORTANT NOTE: The gas/electric units naturally derate with al-

titude. Do not attempt to increase the firing rate by changing orifices

or increasing the manifold pressure. This can cause poor combus-

tion and equipment failure. At all altitudes, the manifold pressure

must be within 0-3 inches W.C. of that listed on the nameplate for

the fuel used. At all altitudes and with either fuel, the air tempera-

ture rise must be within the range listed on the unit nameplate.

Refer to the Installation Manual provided with the LP kit for

conversion from natural gas to propane gas and for altitude
adjustments.

PIPING

IMPORTANT NOTE: To avoid possible unsatisfactory operation or
equipment damage due to under firing of equipment, do not under-

size the natural/propane gas piping from the meter/tank to the unit.

When sizing a trunk line as shown in Table 2, include all appliances

on that line that could be operated simultaneously.

The rating plate is stamped with the model number, type of gas and
gas input rating. Make sure the unit is equipped to operate on the

type of gas available. The gas line installation must comply with

local codes, or in the absence of local codes, with the latest edition
of the National Fuel Gas Code NFPA54/ANSI Z223.1.

Heating Value of Gas (BTU/Cubic_Foot)

Refer to the Proper Piping Practice drawing for the general layout at

the unit. The following rules apply:

1. Use black iron pipe and fittings for the supply piping. The

use of a flex connector and/or copper piping is permitted as
long as it is in agreement with local codes.

2. Use pipe joint compound on male threads only. Pipe joint

compound must be resistant to the action of the fuel used.

3. Use ground joint unions.

4. Install a drip leg to trap dirt and moisture before it can enter

the gas valve. The drip leg must be a minimum of three inches

long.

5. Use two pipe wrenches when making connection to the gas

valve to keep it from turning.

6. Install a manual shut-off valve in a convenient location (within

six feet of unit) between the meter and the unit.

7. Tighten all joints securely.

8. The unit must be connected to the building piping by one of

the following methods:

Rigid metallic pipe and fittings

• Semirigid metallic tubing and metallic fittings (Aluminum alloy

tubing must not be used in exterior locations)

Listed gas appliance connectors used in accordance with

the terms of their listing that are completely in the same

room as the equipment

• In the prior two methods above the connector or tubing

must be protected from physical and thermal damage.

Aluminum alloy tubing and connectors must be coated to

protect against external corrosion when in contact with
masonry, plaster or insulation or are subject to repeated

wettings by liquids (water - not rain water, detergents or

sewage)

6

Содержание GPG10

Страница 1: ...h this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the customer on it...

Страница 2: ......

Страница 3: ...H DEFECTS OR OTHER REPRODUCTIVE HARM HEATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASONABLE ROUTINE INSPECTION MAINTENANCE AND SUPERVISION F THE BUILIDNG IN WHICH ANY SUCH DEVICE IS LOCATED WILL BE VA...

Страница 4: ...for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructe...

Страница 5: ...any visible damage to shipment or container 2 Notify carrier promptly and request an inspection 3 In case of concealed damage carrier should be notified as soon as possible preferabiy within 5 days 4...

Страница 6: ...ing of equipment do not under size the natural propane gas piping from the meter tank to the unit When sizing a trunk line as shown in Table 2 include all appliances on that line that could be operate...

Страница 7: ...he unit PROPANE GAS INSTALLATIONS TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK INSTALL A GAS DETECTING WARNING DEVICE SINCE RUST CAN REDUCE T...

Страница 8: ...may use thermostats with one or two stages of cooling To AVOID INJURY ELECTRICAL SHOCK OR DEATH DISCONNECT ELECTRICAL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING The units are designed f...

Страница 9: ...static and review the blower performance charts before performing the installation In some installations it will be necessary to change the blower speed to provide proper air flow Horizontal Air Flow...

Страница 10: ...E RETURN AIR SYSTEM Even though a return air filter is not supplied with this unit there must be a means of filtering all return air The PG1248 and PG1260 models are provided with internal filter rack...

Страница 11: ...ons in or near the blower motors Duct covers must be removed before operating unit Heat Anticipator Setting Set the heat anticipator on the room thermostat to 0 4 amps to obtain the proper number of h...

Страница 12: ...r having a scale range from 0 to 12 inches of water should be used for this measurement The manifold pressure must be measured with the burners operating To adjust the pressure regulator remove the ad...

Страница 13: ...nutes of operation by blocking the return air grille s 1 After several minutes the main burners must go OFF Blower will continue to run 2 Remove air restrictions and main burners will relight after a...

Страница 14: ...supply for over five seconds If the diagnostic LED indicates an external lockout perform the following checks Check the supply and manifold pressures Check the gas orifices for debris Check gas valve...

Страница 15: ...many hardware stores Permanent filters should last several years However should one become torn or uncleanable it should be replaced CABINET FINISH MAINTENANCE Use a fine grade automotive wax on the...

Страница 16: ...onnect electrical power and gas supply LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION ALWAYS VERIFY PROPER OPERATION AFTER SERV...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Отзывы: