background image

9

C

LEARANCES

 

AND

 A

CCESSIBILITY

Unobstructed front clearance of 24" 

for servicing

 is recom-

mended.

T O P

B1-V EN T

SIN G LE

(P LEN U M )

1"

6"

1"

3"

0"

1"

VE N T

SID ES

FR O N T

B AC K

Top clearance for horizontal configuration - 1"

I

NSTALLATION

 P

OSITIONS

An upflow furnace may be installed in an upright position or
horizontal on either the left or right side panel. Do not install
this furnace on its back. For vertically installed

 upflow 

furnaces,

return air ductwork may be attached to the side panel(s) and/or
basepan. For 

horizontally 

installed 

upflow 

furnaces, return air

ductwork must be attached to the basepan. For 

counterflow

furnaces, return ductwork must be attached to the top end of
the blower compartment.

NOTE: 

Ductwork must never be attached to the back of the

furnace.

H

ORIZONTAL

 I

NSTALLATION

 (*MVC8 M

ODELS

 O

NLY

)

Line contact to framing is permitted when installed in the hori-
zontal configuration. Line contact is defined as the portion of
the cabinet that is formed by the intersection of the top and
side.  ACCESSIBILITY CLEARANCE, WHERE GREATER,
SHOULD TAKE PRECEDENCE OVER MINIMUM FIRE PRO-
TECTION CLEARANCE.  A gas-fired furnace for installation in
a residential garage must be installed so that the ignition source
and burners are located not less than eighteen inches (18")
above the floor and is protected or located to prevent physical
damage by vehicles.  A gas furnace must not be installed di-
rectly on carpeting, tile, or other combustible materials other
than wood flooring.

F

URNACE

 S

USPENSION

If suspending the furnace from rafters or joist, use 3/8" threaded
rod and 2”x2”x3/8” angle iron as shown below.  The length of
rod will depend on the application and the clearances neces-
sary.

Suspended Furnace

E

XISTING

 F

URNACE

 R

EMOVAL

NOTE:

 When an existing furnace is removed from a venting

system serving other appliances,

 

the venting system may be

too large to properly vent the remaining attached appliances.

The following vent testing procedure is reproduced from the

American National Standard/National Standard of Canada
for Gas-Fired Central Furnaces ANSI Z21.47-Latest Edi-
tion, CSA-2.3-Latest Edition Section 1.23.1.

  The following

steps shall be followed with each appliance connected to the
venting system placed in operation, while any other appliances
connected to the venting system are not in operation:

a.

Seal any unused openings in the venting system;

b.

Inspect the venting system for proper size and
horizontal pitch, as required by the National Fuel Gas
Code, ANSI Z223.1 or the CAN/CSA B149 Installation
Codes and these instructions. Determine that there is
no blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition;

c.

In so far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building. Turn on
clothes dryers and any appliance not connected to
the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they shall
operate at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers;

d.

Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously;

e.

Test for draft hood equipped appliance spillage at the
draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle;

f.

After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas
burning appliance to their previous conditions of use;

g.

If improper venting is observed during any of the above
tests, the common venting system must be corrected.

Corrections must be in accordance with the latest edition of
the National Fuel Gas Code NFPA 54/ANSI Z223.1 and/or CAN/
CSA B149 Installation Codes.

If resizing is required on any portion of the venting system, use
the appropriate table in Appendix G in the latest edition of the
National Fuel Gas Code ANSI Z223.1 and/or CAN/CSA B149
Installation Codes.

T

HERMOSTAT

 L

OCATION

In an area having good air circulation, locate the thermostat
about five feet high on a vibration-free inside wall.  Do not install
the thermostat where it may be influenced by any of the follow-
ing:

Содержание DVC8

Страница 1: ...ng Most dealers have a list of specific good safety practices follow them The precautions listed in this Installation Manual are intended as supplemental to existing practices However if there is a di...

Страница 2: ...ITION 13 CHECK 6 DILUTION AIR 14 CHECK 7 COMPLETE THE INSTALLATION 14 FIX 1 LINER TERMINATION 14 FIX 2 CHANGE VENTING ARRANGEMENTS 14 FIX 3 REBUILD THE CROWN 15 FIX 4 RELINING 15 ELECTRICAL CONNECTION...

Страница 3: ...MMUNICATING THERMOSTAT 33 NETWORK TROUBLESHOOTING 34 SYSTEM TROUBLESHOOTING 34 NORMAL SEQUENCE OF OPERATION 34 POWER UP 34 HEATING MODE 35 COOLING MODE 36 FAN ONLY MODE 36 OPERATIONAL CHECKS 36 SAFETY...

Страница 4: ...furnace may be used as a construction site heater only if certain conditions are met These conditions are listed in the PRODUCT APPLICATION section of this manual TO PREVENT PERSONAL INJURY OR DEATH D...

Страница 5: ...TO EXTREMELY LOW RETURN AIR TEMPERATURES AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERES WARNING TO PREVENT PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION THIS FURNACE MUST BE CATEGORY I VENTED DO N...

Страница 6: ...CAUTIONS NOTE Discharge body s static electricity before touching unit An electrostatic discharge can adversely affect electrical com ponents Use the following precautions during furnace installation...

Страница 7: ...anual J Load Cal culations published by the Air Conditioning Contractors of America In the USA this furnace MUST be installed in accordance with the latest edition of the ANSI Z223 1 booklet entitled...

Страница 8: ...g the furnace Ensure adequate combustion air is available for the furnace Improper or insufficient combustion air can expose building occupants to gas combustion products that could include carbon mon...

Страница 9: ...3 Latest Edition Section 1 23 1 The following steps shall be followed with each appliance connected to the venting system placed in operation while any other appliances connected to the venting syste...

Страница 10: ...the furnace area by means of ventilation grilles or ducts connecting directly to the outdoors or spaces open to the outdoors such as attics or crawl spaces CATEGORY I VENTING VERTICAL VENTING TO PREV...

Страница 11: ...e power to furnace Counterflow units are shipped with the induced draft blower discharging from the top of the furnace Top as viewed for a counterflow installation Vent the furnace in accordance with...

Страница 12: ...ghest connected equip ment draft hood outlet or flue collar Wash Clay Tile Size 8 x 8 x12 Each x 24 Length 1 2 to 1 Air Space Second Floor First Floor Attic Floor Roof Line Throat Damper Breech Clean...

Страница 13: ...he lowest existing vent connector and examine the inside of the elbow or tee at the base of the liner Asmall amount of soot may be considered acceptable provided the installer vacuums it away If ruste...

Страница 14: ...lly with a B Vent Under some conditions a 90 furnace could be installed rather than an 80 furnace The 90 furnace can be vented hori zontally or vertically through PVC pipe Next use a flashlight and sm...

Страница 15: ...teel liners were developed for use with oil or solid fuel appliances They are not suitable for use with gas fired appliances Flexible liners specifically intended and tested for gas applications are l...

Страница 16: ...val or routine maintenance JUNCTION BOX RELOCATION EDGES OF SHEET METAL HOLES MAY BE SHARP USE GLOVES AS A PRECAUTION WHEN REMOVING HOLE PLUGS WARNING Line voltage connections can be made through eith...

Страница 17: ...facilitate use with most cooling equipment Consult the wiring diagram located on the blower compartment door for further details of 115 Volt and 24 Volt wiring NOTE For single stage cooling applicati...

Страница 18: ...HUM TRIM ENABLE Move to the ON position to enable dehumidification ON OFF S5 FOSSIL FUEL APPLICATIONS This furnace can be used in conjunction with a heat pump in a fossil fuel application A fossil fue...

Страница 19: ...feeding one of the HUM terminals with a field installed wire from the R terminal or by connecting to the NO side of the low fire pressure switch AUXILIARY ALARM SWITCH The control is equipped with a 2...

Страница 20: ...TO ENSURE SAFE AND PROPER FURNACE OPERATION ALL CONVERSIONS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE AGENCY This unit is configured for natural gas The appropriate manufacturer s propane...

Страница 21: ...with masonry plaster or insulation or subjected to repeated wetting by liquids such as water except rain water detergents or sewage Gas line entrance Right side gas entrance alternate General Furnace...

Страница 22: ...propane gas pressure must be 10 inch WC at the furnace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on tem...

Страница 23: ...at or cool position When the furnace is installed without a cooling coil it is rec ommended that a removable access panel be provided in the outlet air duct This opening shall be accessible when the f...

Страница 24: ...EDURE AND ADJUSTMENT Furnace must have a 115 VAC power supply properly connected and grounded Proper polarity must be maintained for correct operation In addition to the following start up and adjustm...

Страница 25: ...Ft until high capacity 100 is achieved Once achieved the display will show Ft without flashing A 5 minute timer will be started to al low sufficient opportunity for the gas pressure to be tested 5 If...

Страница 26: ...10 0 w c Propane Gas Minimum 11 0 w c Maximum 13 0 w c INLET GAS SUPPLY PRESSURE If supply pressure differs from table make the necessary ad justments to pressure regulator gas piping size etc and or...

Страница 27: ...cubic foot sec ft3 of gas being delivered to the furnace If the dial is a one cubic foot dial divide the number of seconds recorded in step 2 by one If the dial is a two cubic foot dial divide the num...

Страница 28: ...ing 4 individual dip switches The following number refers to the individual labeled dip switch within that section Model Tap Low Stage High Stage Low Stage High Stage Cool Cool Heat Heat A 520 800 121...

Страница 29: ...cooling air flow determined in step 2 and find the required cooling speed and adjustment setting Example A MVC80604BX furnace installed with a 2 5 ton air conditioning system The air flow needed is 10...

Страница 30: ...demands are managed differently in a fully communi cating system than they are in a non communicating wired system The system operating mode as determined by the thermostat determines which unit calcu...

Страница 31: ...thaComfortNet com patible heat pump in a fossil fuel application Afossil fuel applica tion refers to a combined gas furnace and heat pump installation which uses an outdoor temperature sensor to deter...

Страница 32: ...ge AC ComfortNet G W1 W2 Y1 Y2 O 1 2 R C 4 Position Connectors from CTK0 Thermostat Kit System Wiring between Furnace and Non Communicating CompatibleSingleStageAirConditioner COMFORTNET SYSTEM ADVANC...

Страница 33: ...difiable Model Number MOD NUM Displays the furnace model number Serial Number SER NUM Displays the furnace serial number Optional Software SOFTWARE Displays the application software revision IDENTIFIC...

Страница 34: ...wards ground and when data 1 is decreasing towards ground data 2 is increasing towards 5V Typically the data 1 line is approximately 2 6Vdc and the data 2 transmission line is ap proximately 2 3Vdc Th...

Страница 35: ...d Rapid Flashing Normal network traffc On Solid Data 1 Data 2 miss wire Possible Cause Corrective Action Comments None None None Communications Failure Depress Learn Button Verify that bus BIAS and TE...

Страница 36: ...ontrol module performs safety circuit checks Outdoor fan and compressor are energized to their appropriate speed Circulator blower is energized on the appropriate cool speed at the level and time dete...

Страница 37: ...t electrical components Use the following precautions during furnace installation and servicing to protect the integrated control module from dam age By putting the furnace the control and the person...

Страница 38: ...ck for blockage and or leakage Check hose connections at and internal to furnace Wiring Check electrical connections for tightness and or corrosion Check wires for damage Filters FILTERS TO ENSURE PRO...

Страница 39: ...in cleanout cable Attach a variable speed reversible drill to the other end of the cable Slowly rotate the cable with the drill and insert it into one of the heat exchanger tubes While reversing the d...

Страница 40: ...Call for Service icon illuminated ComfortNet thermostat scrolls Check Furnace message E0 Furnace lockout due to an excessive number of ignition retries 3 total LOCKOUT E0 Failure to establish fame Ca...

Страница 41: ...rs and ductwork for blockage Clean flters or remove obstruction Check circulator blower speed and performance Correct speed or replace blower motor if necessary Check burners for proper alignment Chec...

Страница 42: ...d improperly Blocked fue and or inlet air pipe blocked drain system or weak induced draft blower Incorrect pressure switch set point or malfunctioning switch contacts Loose or improperly connected wir...

Страница 43: ...ontrol module has lost communications with circulator blower motor MOTOR COMM b1 Loose wiring connection at circulator motor control leads Failed circulator blower motor Failed integrated control modu...

Страница 44: ...t scrolls Check Furnace message b7 MOTOR PARAMS b7 Furnace operates at reduced performance or Integrated control module LED display provides b9 error code b9 LOW ID AIRFLOW B9 Blocked filters Restrict...

Страница 45: ...D 115 VAC POLARITY DATANOT YET ON NETWORK INVALID MEMORYCARD DATA BLOWER MOTOR NOT RUNNING BLOWER COMMUNICATION ERROR BLOWER HP MIS MATCH BLOWER MOTOR OPERATING IN POWER TEMPERATURE OR SPEED LIMIT BLO...

Страница 46: ...D Set dip switches S3 1 and S3 2 to the appropriate ON OFF positions 2 Select model and desired High Stage Heating Airflow Determine the corresponding tap A B C or D Set dip switches S4 3 and S4 4 to...

Страница 47: ...D On On Add 5 Off Off Minus 5 On Off Add 10 Off On Minus 10 On On A Off Off B On Off C Off On D On On A Off Off B On Off C Off On D On On Disabled Off Enabled On Disabled Off Enabled On 25 Off Off 50...

Страница 48: ...PU 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF C USE COPPER CONDUCTORS ONLY RD INTEGRATED CONTR...

Отзывы: