Airflow data shown applies to non-communicating mode operation only. For a fully communicating
system, please see the outdoor unit’s installation instructions for cooling and pump heating airflow data. See
ComfortNet™ System - Airflow Consideration
section for details.
continuous fan speeds (25%, 50%, 75%, or 100%). " See installation manual
for details"
*the “S” number refers to one of four labeled dip switch section each containing 4
individual dip switches. The following number refers to the individual labeled dip
switch within that section
Model Tap Low Stage High Stage Low Stage High Stage
Cool Cool Heat Heat
A 520 800 1210 1725
B 715 1100 1225 1750
C 910 1400 1245 1775
D 1170 1800 1260 1800
A 553 850 1085 1550
B 748 1150 1155 1650
C 943 1450 1225 1750
D 1203 1850 1260 1800
A 390 600 875 1250
B 520 800 945 1350
C 715 1100 1015 1450
D 910 1400 1085 1550
A 390 600 735 1050
B 520 800 805 1150
C 650 1000 875 1250
D 780 1200 945 1350
A 520 800 945 1350
B 715 1100 1015 1450
C 910 1400 1085 1550
D 1170 1800 1155 1650
A 520 800 1050 1500
B 715 1100 1120 1600
C 910 1400 1190 1700
D 1170 1800 1260 1800
Speed Selection Dip Switches
the corresponding tap (A, B, C, or D). Set dip switches S3-1* and S3-2* to the
appropriate ON / OFF positions. (2) Select model and desired High Stage Heating
Airflow. Determine the corresponding tap (A, B, C, or D). Set dip switches S4-3* and
S4-4* to the appropriate ON / OFF positions. (3) Selecting Airflow Adjustment Factor:
For 0% trim set S5-2* to OFF (trim disabled). If trim is desired set S5-2* to ON (trim
enabled) and set S3-3* and S3-4* to appropriate ON / OFF positions. Tap A is +5%,
Tap B is -5%, Tap C is +10%, Tap D is -10%.
To Set Comfort Mode: Select Desired Comfort Mode profile (see profiles above). Set
Profiles Pre-Run Short-Run OFF Delay
Cool Adjust Profile Heat
Selection Selection Selection Selection
Switches Switches Switches Switches
A OFF OFF OFF OFF OFF OFF OFF OFF
Dehumidification: To enable, set switch S5-1* to ON. Cooling airflow will be reduced
to 85% of nominal value during cool call. To disable, set switch S5-1* to OFF.
D 30 sec/50% 7.5 min/82% 30 sec/50%
D ON ON ON ON ON ON ON ON
B ------- 30 sec/50% 60 sec/100%
C OFF ON OFF ON OFF ON OFF ON
B ON OFF ON OFF ON OFF ON OFF
TAP S3- 1 S3- 2 S3- 3 S3- 4 S4-1 S4-2 S4- 3 S4- 4
dip switches S4-1* and S4-2* to the appropriate ON / OFF positions.
A ------- -------- 60 sec/100%
C ------- 7.5 min/82% 60 sec/100%
To Set Airflow: (1) Select model and desired High Stage Cooling Airflow. Determine
*DVC81005C***
*DVC80805C***
*DVC80603B***
*MVC81005C***
*MVC80805C***
Continuous Fan Speed: Set dip switches S5-3* and S5-4* to select one of 4
0140F01170
*MVC80604B***