For counterflow installations, the air conditioning coil
must be downstream from the heat exchanger of the
furnace.

Counterflow installation over a noncombustible floor.
Before setting the furnace over the plenum opening,
ensure the surface around the opening is smooth and
level. A tight seal should be made between the furnace
base and floor by using a silicon rubber caulking
compound or cement grout.

Counterflow installation over a combustible floor. If
installation over a combustible floor becomes
necessary, use an accessory subbase (see
Specification Sheet applicable to your model for details).
A special accessory subbase must be used for upright
counterflow unit installations over any combustible
material including wood. Follow the instructions with
the subbase for proper installations. Do not install the
furnace directly on carpeting, tile, or other combustible
material other than wood flooring. (

NOTE

: The subbase

will not be required if an air conditioning coil is installed
between the supply air opening on the furnace and
the floor.

   

 

 

 

 

Top - 1"

Side
Clearance - 1"

Back - 0"

Front Clearance - 3"

Vent Pipe Clearance to Combustibles-
6" using Single Wall Connector or 1"
using B-1 vent.

Adequate combustion/ventilation air must be supplied
to the closet.

Furnace must be 

completely

 sealed to floor or base.

Combustion/ ventilation air supply pipes must
terminate 12" from top of closet and 12" from floor of
closet. DO NOT remove solid base plate for side
return.

Return air ducts must be 

completely

 sealed to the

furnace and terminate outside the enclosure surfaces.

Ensure the temperature of the return air entering the
furnace is between 55°F and 100°F when the furnace
is heating.

Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of flue pipe could be a limiting factor in
locating the furnace.

Ensure adequate combustion air is available for the
furnace.  Improper or insufficient combustion air can
expose building occupants to gas combustion products
that could include carbon monoxide.  Refer to

Combustion and Ventilation Air Requirements 

section

.

The furnace must be level. If the furnace is to be set on
a floor that may become wet or damp at times, the
furnace should be supported above the floor on a
concrete base sized approximately 1-1/2" larger than
the base of the furnace.

Ensure upflow or horizontal furnaces are not installed
directly on carpeting, or any other combustible material.
The only combustible material allowed is wood.

Exposure to contaminated combustion air will result
in safety and performance-related problems.  Do not
install the furnace where the combustion air is exposed
to the following substances:

chlorinated waxes or cleaners

chlorine-based swimming pool chemicals

water softening chemicals
deicing salts or chemicals

carbon tetrachloride

halogen type refrigerants

cleaning solutions (such as perchloroethylene)

printing inks

paint removers

varnishes

hydrochloric acid

cements and glues

antistatic fabric softeners for clothes dryers

and masonry acid washing materials

If the furnace is used in connection with a cooling unit,
install the furnace upstream or in parallel with the
cooling unit coil.  Premature heat exchanger failure
will result if the cooling unit coil is placed ahead of the
furnace.

If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition
source are located not less than 18 inches (457 mm)
above the floor.  Protect the furnace from physical
damage by vehicles.

If the furnace is installed horizontally, the furnace
access doors must be vertical so that the burners fire
horizontally into the heat exchanger.  Do not install
the unit with the access doors on the “up/top” or “down/
bottom” side of the furnace.

Do not connect this furnace to a chimney flue that
serves a separate appliance designed to burn solid
fuel.

Содержание DVC8

Страница 1: ...ng Most dealers have a list of specific good safety practices follow them The precautions listed in this Installation Manual are intended as supplemental to existing practices However if there is a di...

Страница 2: ...ITION 13 CHECK 6 DILUTION AIR 14 CHECK 7 COMPLETE THE INSTALLATION 14 FIX 1 LINER TERMINATION 14 FIX 2 CHANGE VENTING ARRANGEMENTS 14 FIX 3 REBUILD THE CROWN 15 FIX 4 RELINING 15 ELECTRICAL CONNECTION...

Страница 3: ...MMUNICATING THERMOSTAT 33 NETWORK TROUBLESHOOTING 34 SYSTEM TROUBLESHOOTING 34 NORMAL SEQUENCE OF OPERATION 34 POWER UP 34 HEATING MODE 35 COOLING MODE 36 FAN ONLY MODE 36 OPERATIONAL CHECKS 36 SAFETY...

Страница 4: ...furnace may be used as a construction site heater only if certain conditions are met These conditions are listed in the PRODUCT APPLICATION section of this manual TO PREVENT PERSONAL INJURY OR DEATH D...

Страница 5: ...TO EXTREMELY LOW RETURN AIR TEMPERATURES AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERES WARNING TO PREVENT PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION THIS FURNACE MUST BE CATEGORY I VENTED DO N...

Страница 6: ...CAUTIONS NOTE Discharge body s static electricity before touching unit An electrostatic discharge can adversely affect electrical com ponents Use the following precautions during furnace installation...

Страница 7: ...anual J Load Cal culations published by the Air Conditioning Contractors of America In the USA this furnace MUST be installed in accordance with the latest edition of the ANSI Z223 1 booklet entitled...

Страница 8: ...g the furnace Ensure adequate combustion air is available for the furnace Improper or insufficient combustion air can expose building occupants to gas combustion products that could include carbon mon...

Страница 9: ...3 Latest Edition Section 1 23 1 The following steps shall be followed with each appliance connected to the venting system placed in operation while any other appliances connected to the venting syste...

Страница 10: ...the furnace area by means of ventilation grilles or ducts connecting directly to the outdoors or spaces open to the outdoors such as attics or crawl spaces CATEGORY I VENTING VERTICAL VENTING TO PREV...

Страница 11: ...e power to furnace Counterflow units are shipped with the induced draft blower discharging from the top of the furnace Top as viewed for a counterflow installation Vent the furnace in accordance with...

Страница 12: ...ghest connected equip ment draft hood outlet or flue collar Wash Clay Tile Size 8 x 8 x12 Each x 24 Length 1 2 to 1 Air Space Second Floor First Floor Attic Floor Roof Line Throat Damper Breech Clean...

Страница 13: ...he lowest existing vent connector and examine the inside of the elbow or tee at the base of the liner Asmall amount of soot may be considered acceptable provided the installer vacuums it away If ruste...

Страница 14: ...lly with a B Vent Under some conditions a 90 furnace could be installed rather than an 80 furnace The 90 furnace can be vented hori zontally or vertically through PVC pipe Next use a flashlight and sm...

Страница 15: ...teel liners were developed for use with oil or solid fuel appliances They are not suitable for use with gas fired appliances Flexible liners specifically intended and tested for gas applications are l...

Страница 16: ...val or routine maintenance JUNCTION BOX RELOCATION EDGES OF SHEET METAL HOLES MAY BE SHARP USE GLOVES AS A PRECAUTION WHEN REMOVING HOLE PLUGS WARNING Line voltage connections can be made through eith...

Страница 17: ...facilitate use with most cooling equipment Consult the wiring diagram located on the blower compartment door for further details of 115 Volt and 24 Volt wiring NOTE For single stage cooling applicati...

Страница 18: ...HUM TRIM ENABLE Move to the ON position to enable dehumidification ON OFF S5 FOSSIL FUEL APPLICATIONS This furnace can be used in conjunction with a heat pump in a fossil fuel application A fossil fue...

Страница 19: ...feeding one of the HUM terminals with a field installed wire from the R terminal or by connecting to the NO side of the low fire pressure switch AUXILIARY ALARM SWITCH The control is equipped with a 2...

Страница 20: ...TO ENSURE SAFE AND PROPER FURNACE OPERATION ALL CONVERSIONS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE AGENCY This unit is configured for natural gas The appropriate manufacturer s propane...

Страница 21: ...with masonry plaster or insulation or subjected to repeated wetting by liquids such as water except rain water detergents or sewage Gas line entrance Right side gas entrance alternate General Furnace...

Страница 22: ...propane gas pressure must be 10 inch WC at the furnace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on tem...

Страница 23: ...at or cool position When the furnace is installed without a cooling coil it is rec ommended that a removable access panel be provided in the outlet air duct This opening shall be accessible when the f...

Страница 24: ...EDURE AND ADJUSTMENT Furnace must have a 115 VAC power supply properly connected and grounded Proper polarity must be maintained for correct operation In addition to the following start up and adjustm...

Страница 25: ...Ft until high capacity 100 is achieved Once achieved the display will show Ft without flashing A 5 minute timer will be started to al low sufficient opportunity for the gas pressure to be tested 5 If...

Страница 26: ...10 0 w c Propane Gas Minimum 11 0 w c Maximum 13 0 w c INLET GAS SUPPLY PRESSURE If supply pressure differs from table make the necessary ad justments to pressure regulator gas piping size etc and or...

Страница 27: ...cubic foot sec ft3 of gas being delivered to the furnace If the dial is a one cubic foot dial divide the number of seconds recorded in step 2 by one If the dial is a two cubic foot dial divide the num...

Страница 28: ...ing 4 individual dip switches The following number refers to the individual labeled dip switch within that section Model Tap Low Stage High Stage Low Stage High Stage Cool Cool Heat Heat A 520 800 121...

Страница 29: ...cooling air flow determined in step 2 and find the required cooling speed and adjustment setting Example A MVC80604BX furnace installed with a 2 5 ton air conditioning system The air flow needed is 10...

Страница 30: ...demands are managed differently in a fully communi cating system than they are in a non communicating wired system The system operating mode as determined by the thermostat determines which unit calcu...

Страница 31: ...thaComfortNet com patible heat pump in a fossil fuel application Afossil fuel applica tion refers to a combined gas furnace and heat pump installation which uses an outdoor temperature sensor to deter...

Страница 32: ...ge AC ComfortNet G W1 W2 Y1 Y2 O 1 2 R C 4 Position Connectors from CTK0 Thermostat Kit System Wiring between Furnace and Non Communicating CompatibleSingleStageAirConditioner COMFORTNET SYSTEM ADVANC...

Страница 33: ...difiable Model Number MOD NUM Displays the furnace model number Serial Number SER NUM Displays the furnace serial number Optional Software SOFTWARE Displays the application software revision IDENTIFIC...

Страница 34: ...wards ground and when data 1 is decreasing towards ground data 2 is increasing towards 5V Typically the data 1 line is approximately 2 6Vdc and the data 2 transmission line is ap proximately 2 3Vdc Th...

Страница 35: ...d Rapid Flashing Normal network traffc On Solid Data 1 Data 2 miss wire Possible Cause Corrective Action Comments None None None Communications Failure Depress Learn Button Verify that bus BIAS and TE...

Страница 36: ...ontrol module performs safety circuit checks Outdoor fan and compressor are energized to their appropriate speed Circulator blower is energized on the appropriate cool speed at the level and time dete...

Страница 37: ...t electrical components Use the following precautions during furnace installation and servicing to protect the integrated control module from dam age By putting the furnace the control and the person...

Страница 38: ...ck for blockage and or leakage Check hose connections at and internal to furnace Wiring Check electrical connections for tightness and or corrosion Check wires for damage Filters FILTERS TO ENSURE PRO...

Страница 39: ...in cleanout cable Attach a variable speed reversible drill to the other end of the cable Slowly rotate the cable with the drill and insert it into one of the heat exchanger tubes While reversing the d...

Страница 40: ...Call for Service icon illuminated ComfortNet thermostat scrolls Check Furnace message E0 Furnace lockout due to an excessive number of ignition retries 3 total LOCKOUT E0 Failure to establish fame Ca...

Страница 41: ...rs and ductwork for blockage Clean flters or remove obstruction Check circulator blower speed and performance Correct speed or replace blower motor if necessary Check burners for proper alignment Chec...

Страница 42: ...d improperly Blocked fue and or inlet air pipe blocked drain system or weak induced draft blower Incorrect pressure switch set point or malfunctioning switch contacts Loose or improperly connected wir...

Страница 43: ...ontrol module has lost communications with circulator blower motor MOTOR COMM b1 Loose wiring connection at circulator motor control leads Failed circulator blower motor Failed integrated control modu...

Страница 44: ...t scrolls Check Furnace message b7 MOTOR PARAMS b7 Furnace operates at reduced performance or Integrated control module LED display provides b9 error code b9 LOW ID AIRFLOW B9 Blocked filters Restrict...

Страница 45: ...D 115 VAC POLARITY DATANOT YET ON NETWORK INVALID MEMORYCARD DATA BLOWER MOTOR NOT RUNNING BLOWER COMMUNICATION ERROR BLOWER HP MIS MATCH BLOWER MOTOR OPERATING IN POWER TEMPERATURE OR SPEED LIMIT BLO...

Страница 46: ...D Set dip switches S3 1 and S3 2 to the appropriate ON OFF positions 2 Select model and desired High Stage Heating Airflow Determine the corresponding tap A B C or D Set dip switches S4 3 and S4 4 to...

Страница 47: ...D On On Add 5 Off Off Minus 5 On Off Add 10 Off On Minus 10 On On A Off Off B On Off C Off On D On On A Off Off B On Off C Off On D On On Disabled Off Enabled On Disabled Off Enabled On 25 Off Off 50...

Страница 48: ...PU 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF C USE COPPER CONDUCTORS ONLY RD INTEGRATED CONTR...

Отзывы: