P
rodUCt
s
PeCiFiCations
P
rodUCt
s
PeCiFiCations
8 www.goodmanmfg.com
SS-CPG36-72
P
rodUCt
s
PeCiFiCations
— CPG060 (
Cont
.)
CPG060
1401D***B*
CPG060
1403D***B*
CPG060
1403B***B*
CPG060
1404B***B*
CPG060
1407B***B*
Cooling Capacity
Total BTU/h
59,500
59,500
59,500
59,500
59,500
Sensible BTU/h
43,200
43,200
43,200
43,200
43,200
SEER / EER
13 / 11.0
13 / 11.0
13 / 11.0
13 / 11.0
13 / 11.0
Decibels
78
78
78
78
78
AHRI Nos.
4385065
4385066
4385066
4385067
4397609
Gas Heating Capacity
High Input / Output kBTU/h
138 / 110.4
138 / 110.4
138 / 110.4
138 / 110.4
138 / 110.4
Low. Input / Output kBTU/h
103 / 83
103 / 83
103 / 83
103 / 83
103 / 83
Steady State Efficiency (AFUE)
80
80
80
80
80
Temperature Rise Range (°F) Hi / Low
35-65 / 25-55
35-65 / 25-55
35-65 / 25-55
35-65 / 25-55
35-65 / 25-55
No. of Burners
6
6
6
6
6
Evaporator Motor / Coil
Motor Type
Direct
Direct
Belt
Belt
Belt
Indoor Nominal CFM
1,900
1,900
1,900
1,900
1,900
Piston Size (Cooling)
0.086
0.086
0.086
0.086
0.086
Filter Size (#)
14 x 20 x 2 (4)
14 x 20 x 2 (4)
14 x 20 x 2 (4)
14 x 20 x 2 (4)
14 x 20 x 2 (4)
Drain Size (NPT)
¾”
¾”
¾”
¾”
¾"
R-410A Refrigerant Charge (oz.)
162
162
162
162
162
Face Area (ft²)
7.8
7.8
7.8
7.8
7.8
Rows Deep/ Fins per Inch
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
Tube Diameter - Material
5/16 - Copper
5/16 - Copper
5/16 - Copper
5/16 - Copper
5/16 - Copper
Belt Drive Evap Fan Data
# of Wheels (D x W)
---
---
1 (11” x 10”)
1 (11” x 10”)
1 (11" x 10")
Motor Sheave / Blower Sheave
---
---
VL44 X ⅝ / AK61 X 1
Belt
---
---
AX53
AX53
AX53
Condenser Fan / Coil
Horsepower / RPM
¼ / 1,090
¼ / 1,090
¼ / 1,090
¼ / 1,090
¼ / 1,075
Fan Diameter/ # Fan Blades
22 / 4
22 / 4
22 / 4
22 / 4
22 / 1
Outdoor Nominal CFM
3,800
3,800
3,800
3,800
3,800
Face Area (ft²)
17.0
17.0
17.0
17.0
17½
Rows Deep/ Fins per Inch
2 / 18
2 / 18
2 / 18
2 / 18
2 / 18
Tube Diameter - Material
5/16 - Copper
5/16 - Copper
5/16 - Copper
5/16 - Copper
5/16 - Copper
Compressor
Quantity / Stage
1 / Single
1 / Single
1 / Single
1 / Single
1 / Single
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Compressor RLA / LRA
26.4 / 134
16 / 110
16 / 110
7.8 / 52
5.7 / 38.9
Electrical Data
Voltage-Phase-Frequency
208/230-1-60
208/230-3-60
208/230-3-60
460-3-60
575-3-60
Indoor Blower HP / FLA (STD Static)
1.0 / 7.6
1.0 / 7.6
1.0 / 3.8
1.0 / 1.9
1.5 / 2.3
Indoor Blower LRA
----
----
24
13
12
Outdoor Fan HP / FLA
¼ / 1.40
¼ / 1.40
¼ / 1.40
¼ / 0.8
¼ / 0.6
Min. Circuit Ampacity¹
42
29
25
12
10
Max. Overcurrent Protection (amps)²
60
40
40
20
15
Power Supply Conduit Hole
1.125
1.125
1.125
1.125
1.125
Low-Voltage Conduit Hole
½”
½”
½”
½”
½"
Operating Weight (lbs)
630
630
630
630
630
Ship Weight (lbs)
655
655
655
655
655
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.