4 www.goodmanmfg.com
SS-CPG36-72
P
roduct
S
PecificationS
— cPG036 (
cont
.)
CPG036
0901D***B*
CPG036
0903D***B*
CPG036
0903B***B*
CPG036
0904B***B*
CPG036
0907B***B*
Cooling Capacity
Total BTU/h
34,600
34,600
34,600
34,600
34,600
Sensible BTU/h
25,600
25,600
25,600
25,600
25,900
SEER / EER
13 / 11.0
13 / 11.0
13 / 11.0
13 / 11.0
13 / 11.0
Decibels
78
78
78
78
78
AHRI #s
4385059
4385060
4385060
4385061
4397607
Heating Capacity
High Input / Output BTU/h
92 / 74
92 / 74
92 / 74
92 / 74
92 / 74
Low. Input / Output kBTU/h
69 / 55
69 / 55
69 / 55
69 / 55
69 / 55
Steady State Efficiency (AFUE)
80
80
80
80
80
Temperature Rise Range (°F) Hi / Low
40-70 / 30-60
40-70 / 30-60
40-70 / 30-60
40-70 / 30-60
40-70 / 30-60
No. of Burners
4
4
4
4
3
Evaporator Motor / Coil
Motor Type
Direct Drive
Direct Drive
Belt Drive
Belt Drive
Belt Drive
# of Wheels (D x W)
1 (10” x 9”)
1 (10” x 9”)
1 (11” x 10”)
1 (11” x 10”)
1 (11” x 10”)
Indoor Nominal CFM
1,200
1,200
1,200
1,200
1,200
Motor Speed Tap (Cooling)
Low Speed
Low Speed
---
---
---
Indoor Motor FLA (Cooling)
2.50
2.50
3.8
1.9
1.9
Horsepower - RPM
⅓ - 890
⅓ - 890
1.0 - 1,725
1.0 - 1,725
1.0 - 1,725
Piston Size (Cooling)
0.068
0.068
0.068
0.068
0.068
Filter Size (“)
(1) 24 x 24 x 2
(1) 24 x 24 x 2
(1) 24 x 24 x 2
(1) 24 x 24 x 2
(1) 24 x 24 x 2
Drain Size (NPT)
¾”
¾”
¾”
¾”
¾”
R-410A Refrigerant Charge Cir #1(oz.)
90
83
83
90
90
Evaporator Coil Face Area (ft²)
5.4
5.4
5.4
5.4
5.4
Rows Deep / Fins per Inch
3 / 16
3 / 16
3 / 16
3 / 16
3 / 16
Belt Drive Evap Fan Data
# of Wheels (D x W)
---
---
1 (11” x 10”)
1 (11” x 10”)
1 (11” x 10”)
Motor Sheave / Blower Sheave
---
---
1VL40 X ⅝ / AK69 X 1
Belt
---
---
AX55
AX55
AX55
Condenser Fan / Coil
Quantity of Condenser Fan Motors
1
1
1
1
1
Horsepower - RPM
¼ / 1,090
¼ / 1,090
¼ / 1,090
¼ - 890
¼ - 1,075
Fan Diameter/ # Fan Blades
22 / 4
22 / 4
22 / 4
22 / 4
22 / 4
Outdoor Nominal CFM
3,800
3,800
3,800
3,800
3,800
Face Area (ft²)
18.0
18.0
18
18
13
Rows Deep/ Fins per Inch
1 / 22
1 / 22
1 / 22
1 / 22
2 / 16
Compressor
Quantity / Stage
1 / Single
1 / Single
1 / Single
1 / Single
1 / Single
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Compressor RLA / LRA
16.7 / 79.0
10.4 / 73.0
10.4 / 73.0
5.8 / 38.0
3.8 / 36.5
Electrical Data
Voltage-Phase-Frequency
208/230-1-60
208/230-3-60
208/230-3-60
460-3-60
575-3-60
Indoor Blower HP / FLA
⅓ / 2.5
⅓ / 2.5
1 / 3.8
1 / 1.9
1 / 1.9
Outdoor Fan HP / FLA
¼ / 1.4
¼ / 1.4
¼ / 1.4
¼ / 0.8
¼ / 0.8
Total Unit Amps
20.57
14.35
15.65
8.47
6.68
Min. Circuit Ampacity¹
25
17
18
10
8
Max. Overcurrent Protection (amps)²
40
25
25
15
15
Power Supply Conduit Hole
1.125
1.125
1.125
1.125
1.125
Low-Voltage Conduit Hole
½”
½”
½”
½”
½”
Operating Weight (lbs)
535
535
535
535
535
Ship Weight (lbs)
560
560
560
560
560
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.