P
rodUCt
s
PeCiFiCations
P
rodUCt
s
PeCiFiCations
6 www.goodmanmfg.com
SS-CPG36-72
P
rodUCt
s
PeCiFiCations
— CPG048 (
Cont
.)
CPG048
1151D***B*
CPG048
1153D***B*
CPG048
1153B***B*
CPG048
1154B***B*
CPG048
1157B***B*
Cooling Capacity
Total BTU/h
45,500
45,500
45,500
45,500
45,500
Sensible BTU/h
35,000
35,000
35,000
35,000
35,000
SEER / EER
13.0 / 11.3
13.0 / 11.3
13.0 / 11.3
13.0 / 11.3
13.0 / 11.3
Decibels
78
78
78
78
78
AHRI Reference #s
4385062
4385063
4385063
4385064
4397608
Heating Capacity
High Input /Output kBTU/h
115 / 92
115 / 92
115 / 92
115 / 92
115 / 92
Low Input /Output kBTU/h
86.25 / 69
86.25 / 69
86.25 / 69
86.25 / 69
86.25 / 69
Steady State Efficiency (AFUE)
80
80
80
80
80
Temperature Rise Range (°F) Hi / Low
40-70 / 25-55
40-70 / 25-55
40-70 / 25-55
40-70 / 25-55
40-70 / 25-55
No. of Burners
5
5
5
5
5
Evaporator Motor / Coil
Motor Type
Direct Drive
Direct Drive
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
1,600
1,600
1,600
1,600
1,600
Motor Speed Tap (Cooling)
Medium
Medium
--
--
--
Indoor Motor FLA (Cooling)
2.87
2.87
3.8
1.9
2.3
Horsepower - RPM
½ - 1,000
½ - 1,000
1.0 / 1,725
1.0 / 1,725
1½ / 1,725
Piston Size (Cooling)
0.076
0.076
0.076
0.076
0.076
Filter Size (#)
14 x 20 x 2 (4)
14 x 20 x 2 (4)
14 x 20 x 2 (4)
14 x 20 x 2 (4)
14 x 20 x 2 (4)
Drain Size (NPT)
¾”
¾”
¾”
¾”
¾”
R-410A Refrigerant Charge Cir #1(oz.)
103
103
103
103
105
Evaporator Coil Face Area (ft²)
7.0
7.0
7.0
7.0
7.0
Rows Deep / Fins per Inch
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
Belt Drive Evap Fan Data
# of Wheels (D” x W”)
---
---
(1) 11 x 10
(1) 11 x 10
(1) 11 x 10
Motor Sheave / Blower Sheave
---
---
VL44 X ⅝ / AK66 X 1
Belt
---
---
AX55
AX55
AX55
Condenser Fan / Coil
Quantity of Condenser Fan Motors
1
1
1
1
1
Horsepower - RPM
¼ - 1,090
¼ - 1,090
¼ - 1,090
¼ - 890
¼ - 1,075
Fan Diameter / # Fan Blades
22 / 4
22 / 4
22 / 4
22 / 4
22 / 4
Outdoor Nominal CFM
3,800
3,800
3,800
3,800
3,800
Face Area (ft²)
17.0
17.0
17.0
17.0
17.0
Rows Deep/ Fins per Inch
1 / 24
1 / 24
1 / 24
1 / 24
1 / 24
Compressor
Quantity / Stage
1 / Single
1 / Single
1 / Single
1 / Single
1 / Single
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Compressor RLA / LRA
19.9 / 109
13.1 / 83.1
13.1 / 83.1
6.1 / 41
4.4 / 33
Electrical Data
Voltage-Phase-Frequency
208/230-1-60
208/230-3-60
208/230-3-60
460-3-60
575-3-60
Outdoor Fan FLA
1.40
1.40
1.40
0.80
0.60
Total Unit Amps
24.1
17.4
18.3
8.8
7.3
Min. Circuit Ampacity¹
29
21
22
10
8
Max. Overcurrent Protection (amps)²
45
30
30
15
15
Power Supply Conduit Hole
1.125
1.125
1.125
1.125
1.125
Low-Voltage Conduit Hole
½”
½”
½”
½”
½”
Operating Weight (lbs)
580
580
580
580
580
Ship Weight (lbs)
605
605
605
605
605
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.