Mounting

The SP-33 and SP-33D controls are designed for
mounting indoors, protected from the weather and
with non-condensing humidity.  For outdoor use
or in moist environments use a Goldine RE-1
raintight enclosure.  Use the mounting screws
supplied or optional mounting bracket (consult IE
factory).

Sensor Mounting and Wiring

To maximize temperature measurement accuracy
securely mount the sensor and then insulate it to
protect it from the effects of ambient temperature.
18 AWG twisted pair wire should be used for
normal indoor runs.  Sensor wiring run outdoors
must be rated for outdoor use and ensure that wire
connections are protected from the weather.  For
long runs or runs near other electrical wiring use
shielded cable (Belden 8760 for indoor use or
Belden 8428 for outdoor use).  Ground the shields
to one of the control's cover screws.  If the SW

sensor supplied with the control does not meet
your needs, contact your distributor for informa-
tion on the wide range of interchangeable Gold-
line temperature sensors.

The temperature sensor wires run back to the
control should be connected to the screw termi-
nals labeled "3" and "4".  See diagram on page 5.

Power input

The SP-33 and SP-33D controls require power to
operate. Either 24VAC, 24VDC, 115 or 208/
240VAC can be used. Be sure to only power the
control with ONE power input.  Connect 24VAC
to the “R” and “C” terminals; 24VDC to the “R”
(+) and “C” (-); 115VAC to the terminals marked
“115VAC” or 208/240VAC to the terminals
marked “240VAC”.  Connect grounds to the green
screw provided or use grounding clips (eg Steel
City “Gee clips” or Raco #975).  Refer to wiring
diagram below.

{

{

S e n s o r

S e n s o r

S e n s o r

S e n s o r

Содержание SP-33

Страница 1: ...oint on page 7 The SP 33 and SP 33D also features a plug in connector for a TD 30 Digital Display Monitor The TD 30 snaps into the cover for easy mounting and displays both sensor and setpoint tempera...

Страница 2: ...g jumpers located on the circuit board see diagram below Set these jumpers based on your application before attempting to install or wire the control The jumper functions and appropriate positions are...

Страница 3: ...For long runs or runs near other electrical wiring use shielded cable Belden 8760 for indoor use or Belden 8428 for outdoor use Ground the shields to one of the control s cover screws If the SW senso...

Страница 4: ...r to the sample diagrams shown below SP 33D The SP 33D provides two sets of iso lated SPDT relay outputs If you are directly controlling a load eg pump blower valve etc you must connect a source of po...

Страница 5: ...nting the Output LED will blink NOTE When input power is first applied to the control the Anti Cycle internal timer automati cally starts and will prevent the output relay s from energizing until afte...

Страница 6: ...the Operation Operation Operation Operation Operation Continued Continued Continued Continued Continued RSP 33 is labeled 1 2 and 3 similar to the screw terminal located under R and C on the SP 33 33...

Страница 7: ...9 297 130 3 049 180 1 171 230 511 280 248 19 159 696 31 33 590 81 9 076 131 2 987 181 1 150 231 503 281 244 18 154 347 32 32 648 82 8 861 132 2 926 182 1 130 232 496 282 241 17 149 197 33 31 737 83 8...

Отзывы: