The SP-33 and SP-33D use 2 LED indicators to
display the status of the control.  The diagram on
page 2 shows the location of each LED.  Refer to
the chart below for LED information.

Anti-Cycle

This feature is used to prevent the output from
turning on within 4 minutes of output turning off,
regardless of temperature.  An internal timer starts
counting immediately after the control "satisfies"

(output relay(s) turn off).  The output relay(s) are
only allowed to energize AFTER the timer has
completed counting.  If the timer hasn't finished
counting, the Output  LED will blink.

NOTE: When input power is first applied to the
control, the Anti-Cycle internal timer automati-
cally starts and will prevent the output relay(s)
from energizing until after the timer has finished
counting.

The SP-33 and SP-33D operation is straightfor-
ward.

Cool mode:  The control output will turn on when
the sensor temperature rises to the setpoint tem-
perature plus the differential amount. The control
output will  turn off when the sensor temperature
reaches the setpoint temperature.

Heat mode: The control output will turn on when
the sensor temperature falls to the setpoint tem-
perature minus the differential amount.  The con-
trol output will turn off when the sensor tempera-
ture reaches the setpoint temperature.

Some sample diagrams of the control logic are
shown below.

Содержание SP-33

Страница 1: ...oint on page 7 The SP 33 and SP 33D also features a plug in connector for a TD 30 Digital Display Monitor The TD 30 snaps into the cover for easy mounting and displays both sensor and setpoint tempera...

Страница 2: ...g jumpers located on the circuit board see diagram below Set these jumpers based on your application before attempting to install or wire the control The jumper functions and appropriate positions are...

Страница 3: ...For long runs or runs near other electrical wiring use shielded cable Belden 8760 for indoor use or Belden 8428 for outdoor use Ground the shields to one of the control s cover screws If the SW senso...

Страница 4: ...r to the sample diagrams shown below SP 33D The SP 33D provides two sets of iso lated SPDT relay outputs If you are directly controlling a load eg pump blower valve etc you must connect a source of po...

Страница 5: ...nting the Output LED will blink NOTE When input power is first applied to the control the Anti Cycle internal timer automati cally starts and will prevent the output relay s from energizing until afte...

Страница 6: ...the Operation Operation Operation Operation Operation Continued Continued Continued Continued Continued RSP 33 is labeled 1 2 and 3 similar to the screw terminal located under R and C on the SP 33 33...

Страница 7: ...9 297 130 3 049 180 1 171 230 511 280 248 19 159 696 31 33 590 81 9 076 131 2 987 181 1 150 231 503 281 244 18 154 347 32 32 648 82 8 861 132 2 926 182 1 130 232 496 282 241 17 149 197 33 31 737 83 8...

Отзывы: