380 ~ 415 Vac
380 ~ 415 Vac
380 ~ 415 Vac
220 ~ 240 Vac
220 ~ 240 Vac
220 ~ 240 Vac
380 ~ 440V / 3 / 50-60 Hz
220 ~ 240V / 3 / 50-60 Hz
380 ~ 415V / 3N / 50-60 Hz 220 ~ 240V / 1N / 50-60 Hz
380 ~ 415 Vac
380 ~ 415 Vac
380 ~ 415 Vac
220 ~ 240 Vac
220 ~ 240 Vac
220 ~ 240 Vac
30
G
Line - INSTALLATION MANUAL
ELECTRICAL CONNECTIONS
DANGER!
Electrical connections must be carried out by fully qualified engineers.
DANGER!
When the main switch mounted on the ironer is in position 0, there is still tension on the ironer supply terminals.
Turn off the ciruit breaker before carrying out any operation on the electric circuit.
The manufacturer cannot be held responsible should safety regulations not be observed.
Before connecting the ironer, check that the supply voltage corresponds to that indicated on the serial number plate, which
is situated on the rear of the machine.
To ensure safe connection to the mains use a cable as specified in the Table 3 and an automatic cut-out protective device
(differential magneto-thermal switch Idn = 0.03 A).
The differential magneto-thermal switch must have characteristics of section and insulation complying with European
norms EN 60947-2 e EN 60947-3 and must be adequate to the ironer absorption.
This device and the connecting cable are not provided with the equipment.
The ironer must be connected to an individual circuit breaker.
IMPORTANT!
Grounding is necessary
.
To guarantee protection against electrical shock, ironer MUST BE grounded.
To the purpose, only use the dedicated yellow/green terminal mounted on the ironer main supply terminals.
The earthing system must comply with national legal requirements.
Never connect ground wire and neutral on the same line.
G.50 models only.
When first starting the ironer, verify the correct phases connection checking the rotation sense of fan motor (it must turn
clockwise).
In case of wrong connection disconnect the machine from the power supply and invert two phases in the supply terminals.
MODELS WITH NEUTRAL
MODELS WITHOUT NEUTRAL