Testing procedure at T-proof 

The proof test must be performed to reveal dangerous faults which cannot be otherwise detected. This means that it is necessary to specify how dangerous undetected faults, which 
have been noted during the FMEDA analysis, can be revealed during the proof test. 
The 

Proof test

 consists of the following steps. 

 

This test reveals almost 99 % of all possible Dangerous Undetected failures in the digital relay module. 

Steps

 

Action

 

1

 

Bypass the Safety-related PLC or take any other appropriate action to avoid a false trip. 

2

 

For the single channel, verify the input to output channel functionality: 
a)  For the NO contact, the output load is normally energized (NE) when the input channel is ON, while the de-activation (Fail-Safe State) of the input 

channel de-energizes the load; 

b)  For the NC contact, the output load is normally de-energized (ND) when the input channel is ON, while the de-activation (Fail-Safe State) of the 

input channel energizes the load. 

The channel functionality must be verified in the 20 to 30 Vdc supply voltage range of the module. Connect a DC power supply to the input terminals, in 
order to enable or disable the input channel. In order to check the ohmic continuity of the NO and NC contacts, connect an ohmmeter in series with the 
NO-COM output contact and another one in series with the NC-COM output contact. Perform the following procedure: 

1. 

Do not enable (DC power supply voltage 

 1V) the input channel (terminals “5” - “6” or “7” - “8”) of the unit under test and verify that the ohmic 

continuity is absent at the NO-COM output contact (terminals “13/14” - “15” or “9/10” - “11”), while it is present at the NC-COM output contact 
(terminals “16” - “15” or “12” - “11”);

 

2. 

Enable (DC power supply voltage 

 6V) the input channel (terminals “5” - “6” or “7” - “8”) of the unit under test and verify that the ohmic continuity is 

present at the NO-COM output contact (terminals “13/14” - “15” or “9/10” - “11”), while it is absent at the NC-COM output contact  
(terminals “16” - “15” or “12” - “11”).

 

3

 

Remove the bypass from the safety-related PLC or restore normal operation. 

D1044 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/Non Hazardous Locations or Zone 2, Group IIC, 
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous 
Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, 
and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1044 associated apparatus shall be accomplished 
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1044 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or 
unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock 
when connected to live hazardous potential. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

 

D1044 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

FM Approved under Entity Concept,

or third party approval

Hazardous (Classified) Locations

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

Class I, Zone 0, Group IIC, IIB, IIA

Intrinsically 

Safe Equipment

Must not use or generate

more than 250 Vrms or Vdc

Unclassified Locations

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

Non-incendive 

Equipment

Unclassified Locations

16

13/14

Power Supply

3
4

Must not use or generate

more than 250 Vrms or Vdc

15

Intrinsically 

Safe Equipment

9/10

11

12

Non-incendive 

Equipment

Power Supply

5
6

Control 

Equipment

7
8

Control 

Equipment

+

-

16

13/14

15

12

9/10

11

6

5

Control 

Equipment

8

7

Control 

Equipment

+

-

3
4

D1044 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Содержание D1044D

Страница 1: ...D1044 SIL 2 SIL 3 Digital Relay Output ISM0080 10 D1044S D1044D INSTRUCTION SAFETY MANUAL SIL 2 SIL 3 Digital Relay Output Loop Bus Powered DIN Rail Models D1044S D1044D...

Страница 2: ...nel D1044S Isolation Test Voltage I S Out In 1 5 KV I S Out Supply 1 5 KV I S Out I S Out 500 V In Supply 500 V In In 500 V Input switch contact logic level Trip voltage levels OFF status 1 0 V ON sta...

Страница 3: ...Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 ATEX IECEx FM FM C INMETRO EAC EX UKR n 898 T V Certifications T V Functional Safety Certification Type Approval Certificate...

Страница 4: ...hat maximum allowable voltage current Ui Vmax Ii Imax of the D1044 Associated Apparatus are not exceeded by the safety parameters Uo Voc Io Isc of the Intrinsically Safe device indicated in the table...

Страница 5: ...D1044D Bus powered independent channels NC 16 3 4 5 6 Supply 24 Vdc SIL 2 Out 1 7 8 NO 13 14 COM 15 NC 12 NO 9 10 COM 11 In 1 Control SIL 2 Out 2 In 2 Control MODEL D1044D Bus powered 1oo2 channel ar...

Страница 6: ...AZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 Relay contact shown in de energized position MODEL D1044D Loop powered 1oo2 channel architecture NC 16 3 4 5...

Страница 7: ...OUPS E F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1044S Bus...

Страница 8: ...lure mode is not taken into account fail Not part failure mode of a component that is not part of the safety function but part of the circuit diagram and is listed for completeness When calculating th...

Страница 9: ...Failure rate date taken from Siemens Standard SN29500 Failure rate table Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 99 with determinat...

Страница 10: ...N29500 Failure rate table Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 99 with determination of SIL supposing module contributes 10 of t...

Страница 11: ...ken into account Failure rate date taken from Siemens Standard SN29500 Failure rate table Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 9...

Страница 12: ...Siemens Standard SN29500 Failure rate table Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 99 with determination of SIL supposing module c...

Страница 13: ...connections or another acceptable Division 2 Zone 2 wiring method according to the NEC and the CEC Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respe...

Страница 14: ...nsistent with the effective operating environment of the specific installation Units must be protected against dirt dust extreme mechanical e g vibration impact and shock and thermal stress and casual...

Отзывы: