background image

 

D1048 

- SIL 3 Digital Output Driver NE Loads Loop Powered 

G.M. International ISM0096-4 

Power Dissipation of D1048 Isolators

 

Section “Technical Data” of D1048 isolator specifies the current consumption (maximum current from the nominal power supply, typical 24 Vdc, in normal operation); 
this data serves to dimension the current rating of the power supply unit. Section “Technical Data” indicates also the maximum power consumption (maximum power required from the 
power supply in the worst (abnormal) operating conditions like for example supply voltage at 30 Vdc, short circuit on the outputs terminals. 
The power dissipated 

Pd

 inside the enclosure is: 

Pd = Current Consumption (A) * Supply Voltage (V) - Power Dissipated into the output load 

Isolators are not running at the maximum current all at the same time, the average power consumption of a multitude of isolators can be considered to be only 70 % of the value obtained  
from the section “Technical Data”. Considering the power dissipated by the load (typical 1/3 of input power), and the 70 % above discussed, the power effectively dissipated internally 
by the isolators can therefore become ½ of the actual power delivered by the power supply. 
The following tables give advises for DIN-Rail orientation (vertical or horizontal) of barriers mounting, or installation on custom board assembly. 

A) 

Cabinet with Natural Ventilation 

Maximum recommended ambient temperature in °C depending on installation method: 

 

Installation in Cabinet 

 

Start-up 

 

Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. 
Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts. 
Activate the control signal, the “status” yellow led must be lit, fault led must be in accordance with condition of the corresponding output line. 
If possible change the status of driving signal and connection line one at time checking the corresponding status and fault leds condition as well as output to be correct. 

Installation 

 

D1048 is a digital output isolator housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022. 
D1048 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet" 
Instruction Manual D1000 series for detailed instructions. 
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit 
without suffering or causing any damage 

(for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing). 

The wiring cables have to be proportionate in base to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections and configuration DIP switches. 
Identify the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example: 
Connect control input signal positive at terminal “5” and negative at terminal “6”. 
Connect fault open collector transistor output positive at terminal “1” and negative at terminal “2”. 
Connect override input at terminal “7” positive and at terminal “8” negative. 
Connect positive output at terminal “13” and negative output at “16” using “Out A” diagram or positive output at terminal “14” and negative at terminal “16” using “Out B” diagram or 
positive output at terminal “15” and negative at “16” using “Out C” diagram. 
NOTE: use only one output at a time, Out A or Out B or Out C not contemporary. 
 
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards 
(e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection. 
Connect SPST output transistors checking the load rating to be within the maximum rating (100 mA, 35 Vdc resistive load). 
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation 
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1048 must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 

 

 

 

 

Any orientation 

Vertical 

Horizontal 

Installation of Multiple units with DIN-Rail Bus 

Single unit Installation 

 

Type of Isolator 

 

 

 

Vertical 

Horizontal 

Installation on Custom Boards 

B) 

Cabinet with Forced Ventilation 

Maximum recommended ambient temperature in °C depending on installation method: 

 

 

 

Any orientation 

Vertical 

Horizontal 

Installation of Multiple units with DIN-Rail Bus 

Single unit Installation 

 

Type of Isolator 

 

60°C 

45°C 

50°C 

Vertical 

Horizontal 

Installation on Custom Boards 

50°C 

60°C 

 

 

D1048S 

60°C 

35°C 

40°C 

D1048S 

40°C 

45°C 

Содержание D1048S

Страница 1: ...D1048 SIL 3 Digital Output Driver NE Loads Loop Powered ISM0096 4 D1048S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 3 Digital Output Driver NE Loads Loop Powered DIN Rail Model D1048S ...

Страница 2: ...tage I S Out In 1 5 KV I S Out Override 1 5 KV I S Out Fault 1 5 KV In Fault 500 V In Override 500 V Fault Override 500 V Output 45 mA at 13 0 V 21 0 V no load 174 Ω series resistance at terminals 13 16 Out A 45 mA at 10 2 V 21 0 V no load 236 Ω series resistance at terminals 14 16 Out B 45 mA at 8 5 V 21 0 V no load 275 Ω series resistance at terminals 15 16 Out C Short circuit current 50 mA 55 m...

Страница 3: ...nput Output Fault EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx FM FM C Certifications High Reliability SMD components Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Output A for Solenoid Valve Terminal block connections HAZARDOUS AREA SAFE AR...

Страница 4: ...Po Po 907 mW Pi Pi Out A 13 16 Out B 14 16 Po Po 667 mW Out C 15 16 Po Po 571 mW Out A 13 16 Out B 14 16 Out C 15 16 Co Ca 113 nF Co Ca 860 nF Co Ca 3 05 µF IIB C IIA D IIC A B Li Ri device and L cable R cable Lo Ro 39 2 µH Ω Lo Ro 156 8 µH Ω Lo Ro 313 6 µH Ω IIB C IIA D IIC A B Lo Ro 53 3 µH Ω Lo Ro 213 5 µH Ω Lo Ro 427 0 µH Ω IIB C IIA D IIC A B Lo Ro 62 3 µH Ω Lo Ro 249 4 µH Ω Lo Ro 498 9 µH Ω ...

Страница 5: ...DIVISION 1 GROUPS E F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 Use only one output at a time Out A or Out B or Out C MODEL D1048S 15 16 5 6 Solenoid Valve In 1 Control 14 13 Out 1 Solenoid Valve Solenoid Valve 1 2 Transistor Fault Out Out C Out B Out A Load Diag 7 8 ...

Страница 6: ... for driving solenoid valves visual or audible alarms to alert a plant operator or other process control devices in Hazardous Area from a driving signal in Safe Area It can also be used as a controllable supply to power measuring or process control equipment Its use is allowed in applications requiring up to SIL 3 level according to IEC 61508 in safety related systems for high risk industries The ...

Страница 7: ...ous before servicing The wiring cables have to be proportionate in base to the current and the length of the cable On the section Function Diagram and enclosure side a block diagram identifies all connections and configuration DIP switches Identify the function and location of each connection terminal using the wiring diagram on the corresponding section as an example Connect control input signal ...

Страница 8: ...pcb These switches allows the configuration of override input and fault detection functions SW2 dip switch configuration SW2 Override control input Disabled Enabled 4 4 ON OFF 1 2 3 4 ON Not used ON SW2 Side A Panel View SW1 ON Side B Panel View SW1 dip switch configuration 1 2 3 4 ON Not used SW1 Field line and load fault detection 1 OFF 1 ON Disabled Enabled ...

Отзывы: