D1048 

- SIL 3 Digital Output Driver NE Loads Loop Powered 

G.M. International ISM0096-4 

D1048 is an isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/Non Hazardous Locations or 
Zone 2, Group IIC, Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 
Hazardous Area/Hazardous Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) 
within the specified operating temperature limits Tamb -20 to +60 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1048 associated apparatus shall be accomplished 
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1048 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or 
unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

The single channel DIN-Rail Loop Powered Digital Output Isolator, D1048S, is suitable for driving solenoid valves, visual or audible alarms to alert a plant operator, or 
other process control devices in Hazardous Area from a driving signal in Safe Area. It can also be used as a controllable supply to power measuring or process control equipment. 
Its use is allowed in applications requiring up to SIL 3 level (according to IEC 61508) in safety related systems for high risk industries. 
The Safety PLC or DCS driving signal powers the field device through the D1048S, which provides isolation and is capable of monitoring the conditions of the line. 
Short and open circuit diagnostic monitoring, dip-switch selectable and active when input power is present, provides LED indication and NC transistor output signaling. 
When fault is detected output is de-energized until normal condition is restored. Line short and open output circuit fault detection is also reflected on the PLC / DCS input circuit 
providing less than 10 mA consumption. 
An override input, dip-switch selectable, is provided to permit a safety system to override the control signal. When enabled, a low input voltage always de-energizes the field device 
regardless of the input signal. 
Three basic output circuits are selectable, with different safety parameters, to interface the majority of devices on the market. The selection among the three output characteristics 
is obtained by connecting the field device to a different terminal block. 
Presence of output, as well as integrity or fault condition of device and connecting line are displayed by signaling LEDs (yellow for status, red for fault). 

Operation 

 

 

D1048 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

FM Approved under Entity Concept,

or third party approval

Hazardous (Classified) Locations

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

Class I, Zone 0, Group IIC, IIB, IIA

Must not use or generate

more than 250 Vrms or Vdc

Unclassified Locations

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

Unclassified Locations

Must not use or generate

more than 250 Vrms or Vdc

-

16

Intrinsically 

Safe Equipment

+

15

14

13

+

+
+

+

+

14

-

+

16

15

+

13

8

-

-

+

7

+

+

-

Control 

Equipment

Control 

Equipment

Control 

Equipment

Non-incendive

Equipment

5
6

1
2

2

1

-

+

7
8

+

-

6

5

-

+

Control 

Equipment

Control 

Equipment

Control 

Equipment

D1048 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Содержание D1048S

Страница 1: ...D1048 SIL 3 Digital Output Driver NE Loads Loop Powered ISM0096 4 D1048S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 3 Digital Output Driver NE Loads Loop Powered DIN Rail Model D1048S ...

Страница 2: ...tage I S Out In 1 5 KV I S Out Override 1 5 KV I S Out Fault 1 5 KV In Fault 500 V In Override 500 V Fault Override 500 V Output 45 mA at 13 0 V 21 0 V no load 174 Ω series resistance at terminals 13 16 Out A 45 mA at 10 2 V 21 0 V no load 236 Ω series resistance at terminals 14 16 Out B 45 mA at 8 5 V 21 0 V no load 275 Ω series resistance at terminals 15 16 Out C Short circuit current 50 mA 55 m...

Страница 3: ...nput Output Fault EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx FM FM C Certifications High Reliability SMD components Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Output A for Solenoid Valve Terminal block connections HAZARDOUS AREA SAFE AR...

Страница 4: ...Po Po 907 mW Pi Pi Out A 13 16 Out B 14 16 Po Po 667 mW Out C 15 16 Po Po 571 mW Out A 13 16 Out B 14 16 Out C 15 16 Co Ca 113 nF Co Ca 860 nF Co Ca 3 05 µF IIB C IIA D IIC A B Li Ri device and L cable R cable Lo Ro 39 2 µH Ω Lo Ro 156 8 µH Ω Lo Ro 313 6 µH Ω IIB C IIA D IIC A B Lo Ro 53 3 µH Ω Lo Ro 213 5 µH Ω Lo Ro 427 0 µH Ω IIB C IIA D IIC A B Lo Ro 62 3 µH Ω Lo Ro 249 4 µH Ω Lo Ro 498 9 µH Ω ...

Страница 5: ...DIVISION 1 GROUPS E F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 Use only one output at a time Out A or Out B or Out C MODEL D1048S 15 16 5 6 Solenoid Valve In 1 Control 14 13 Out 1 Solenoid Valve Solenoid Valve 1 2 Transistor Fault Out Out C Out B Out A Load Diag 7 8 ...

Страница 6: ... for driving solenoid valves visual or audible alarms to alert a plant operator or other process control devices in Hazardous Area from a driving signal in Safe Area It can also be used as a controllable supply to power measuring or process control equipment Its use is allowed in applications requiring up to SIL 3 level according to IEC 61508 in safety related systems for high risk industries The ...

Страница 7: ...ous before servicing The wiring cables have to be proportionate in base to the current and the length of the cable On the section Function Diagram and enclosure side a block diagram identifies all connections and configuration DIP switches Identify the function and location of each connection terminal using the wiring diagram on the corresponding section as an example Connect control input signal ...

Страница 8: ...pcb These switches allows the configuration of override input and fault detection functions SW2 dip switch configuration SW2 Override control input Disabled Enabled 4 4 ON OFF 1 2 3 4 ON Not used ON SW2 Side A Panel View SW1 ON Side B Panel View SW1 dip switch configuration 1 2 3 4 ON Not used SW1 Field line and load fault detection 1 OFF 1 ON Disabled Enabled ...

Отзывы: