background image

 

D1048 

- SIL 3 Digital Output Driver NE Loads Loop Powered 

G.M. International ISM0096-4 

 

Configuration 

Configuration DIP switches are located on component side of pcb. These switches allows the configuration of override input and fault detection functions. 

SW2

 dip switch configuration 

SW2 

Override 

control input 

Disabled 

Enabled 

4

4

ON 

OFF 

1

2

3

4

ON

Not used

ON 

SW2 

Side A Panel View 

SW1 

ON 

Side B Panel View 

SW1

 dip switch configuration 

1

2

3

4

ON

Not used

SW1 

Field line and 

load fault detection 

1

OFF 

1

ON 

Disabled 

Enabled 

 

 

Содержание D1048S

Страница 1: ...D1048 SIL 3 Digital Output Driver NE Loads Loop Powered ISM0096 4 D1048S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 3 Digital Output Driver NE Loads Loop Powered DIN Rail Model D1048S ...

Страница 2: ...tage I S Out In 1 5 KV I S Out Override 1 5 KV I S Out Fault 1 5 KV In Fault 500 V In Override 500 V Fault Override 500 V Output 45 mA at 13 0 V 21 0 V no load 174 Ω series resistance at terminals 13 16 Out A 45 mA at 10 2 V 21 0 V no load 236 Ω series resistance at terminals 14 16 Out B 45 mA at 8 5 V 21 0 V no load 275 Ω series resistance at terminals 15 16 Out C Short circuit current 50 mA 55 m...

Страница 3: ...nput Output Fault EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx FM FM C Certifications High Reliability SMD components Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Output A for Solenoid Valve Terminal block connections HAZARDOUS AREA SAFE AR...

Страница 4: ...Po Po 907 mW Pi Pi Out A 13 16 Out B 14 16 Po Po 667 mW Out C 15 16 Po Po 571 mW Out A 13 16 Out B 14 16 Out C 15 16 Co Ca 113 nF Co Ca 860 nF Co Ca 3 05 µF IIB C IIA D IIC A B Li Ri device and L cable R cable Lo Ro 39 2 µH Ω Lo Ro 156 8 µH Ω Lo Ro 313 6 µH Ω IIB C IIA D IIC A B Lo Ro 53 3 µH Ω Lo Ro 213 5 µH Ω Lo Ro 427 0 µH Ω IIB C IIA D IIC A B Lo Ro 62 3 µH Ω Lo Ro 249 4 µH Ω Lo Ro 498 9 µH Ω ...

Страница 5: ...DIVISION 1 GROUPS E F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 Use only one output at a time Out A or Out B or Out C MODEL D1048S 15 16 5 6 Solenoid Valve In 1 Control 14 13 Out 1 Solenoid Valve Solenoid Valve 1 2 Transistor Fault Out Out C Out B Out A Load Diag 7 8 ...

Страница 6: ... for driving solenoid valves visual or audible alarms to alert a plant operator or other process control devices in Hazardous Area from a driving signal in Safe Area It can also be used as a controllable supply to power measuring or process control equipment Its use is allowed in applications requiring up to SIL 3 level according to IEC 61508 in safety related systems for high risk industries The ...

Страница 7: ...ous before servicing The wiring cables have to be proportionate in base to the current and the length of the cable On the section Function Diagram and enclosure side a block diagram identifies all connections and configuration DIP switches Identify the function and location of each connection terminal using the wiring diagram on the corresponding section as an example Connect control input signal ...

Страница 8: ...pcb These switches allows the configuration of override input and fault detection functions SW2 dip switch configuration SW2 Override control input Disabled Enabled 4 4 ON OFF 1 2 3 4 ON Not used ON SW2 Side A Panel View SW1 ON Side B Panel View SW1 dip switch configuration 1 2 3 4 ON Not used SW1 Field line and load fault detection 1 OFF 1 ON Disabled Enabled ...

Отзывы: