D1048 

- SIL 3 Digital Output Driver NE Loads Loop Powered 

G.M. International ISM0096-4 

General Description: 

The single channel DIN-Rail Loop Powered Digital Output Isolator, D1048S, is suitable for driving solenoid valves, visual or audible alarms to alert a plant operator, 

or other process control devices in Hazardous Area from a driving signal in Safe Area. It can also be used as a controllable supply to power measuring or process control equipment. 
Its use is allowed in applications requiring up to SIL 3 level (according to IEC 61508) in safety related systems for high risk industries. 
The Safety PLC or DCS driving signal powers the field device through the D1048S, which provides isolation and is capable of monitoring the conditions of the line. 
Short and open circuit diagnostic monitoring, dip-switch selectable and active when input power is present, provides LED indication and NC transistor output signaling. 
When fault is detected output is de-energized until normal condition is restored. Line short and open output circuit fault detection is also reflected on the PLC / DCS input circuit 
providing less than 10 mA consumption. 
An override input, dip-switch selectable, is provided to permit a safety system to override the control signal. When enabled, a low input voltage always de-energizes the field device 
regardless of the input signal. 
Three basic output circuits are selectable, with different safety parameters, to interface the majority of devices on the market. The selection among the three output characteristics 
is obtained by connecting the field device to a different terminal block. 

Function: 

1 channel I.S. digital output to operate Hazardous Area normally energized loads from PLC or DCS drive logics in Safe Area, providing 3 port isolation (input/output/fault). 

Signalling LEDs: 

Output status (yellow), fault condition (red). 

Field Configurability: 

Line Fault Detection enable or disable and Override Control Input enable or disable. 

EMC: 

Fully compliant with CE marking applicable requirements. 

 

Characteristics 

Loop Input: 

loop powered control signal. 

Loop Supply:

 

24 Vdc nom (20 to 30 Vdc) reverse polarity protected, 2 A time lag fuse internally protected. Supplies also diagnostic monitoring control circuit. 

Current consumption @ 24 V:

 65 mA with 45 mA output typical in normal operation, 

 10 mA when fault circuit enabled and fault condition detected. 

Power dissipation:

 1.1 W with 24 V supply, output energized at 45 mA nominal load. 

Max. power consumption:

 at 30 V supply voltage, 1.8 W. 

Override Input: 

override control signal de-energizes output when enabled by dip-switch. 

Override range:

 

24 Vdc nom (20 to 30 Vdc) to disable (field device controlled by input), 0 to 5 Vdc to de-energize field device, reverse polarity protected. 

Current consumption @ 24 V:

 5 mA. 

Isolation (Test Voltage): 

I.S. Out/In 1.5 KV; I.S. Out/Override 1.5 KV; I.S. Out/Fault 1.5 KV; In/Fault 500 V; In/Override 500 V; Fault/Override 500 V. 

Output:

 

45 mA at 13.0 V (21.0 V no load, 174 

 series resistance) at terminals 13-16 Out A. 

45 mA at 10.2 V (21.0 V no load, 236 

 series resistance) at terminals 14-16 Out B. 

45 mA at 8.5 V (21.0 V no load, 275 

 series resistance) at terminals 15-16 Out C. 

Short circuit current: 

 50 mA (55 mA typical). 

Response time: 

75 ms. 

Fault detection: 

field device and wiring open circuit or short circuit detection dip-switch selectable. When fault is detected output is de-energized until normal condition is restored.

 

Short output detection: 

load resistance 

 50 

 (

 2 mA forcing to detect fault). 

Open output detection: 

load resistance > 10 K

Fault signalling: 

voltage free NE SPST optocoupled open-collector transistor (output de-energized in fault condition and when input power not present). 

Open-collector rating: 

100 mA at 35 Vdc (

 1.5 V voltage drop). 

Leakage current: 

 50 µA at 35 Vdc. 

Loop input consumption: 

 10 mA when fault detected. 

Response time: 

 5 ms. 

Compatibility: 

 

CE mark compliant, conforms to 94/9/EC Atex Directive and to 2004/108/CE EMC Directive. 

Environmental conditions: 

Operating:

 temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. 

Storage:

 temperature limits – 45 to + 80 °C. 

Safety Description: 

ATEX:

 II 3(1) G Ex nA [ia Ga] IIC T4 Gc, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I 

IECEx:

 Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, 

associated apparatus and non-sparking electrical equipment. 

Uo/Voc = 24.8 V, Io/Isc = 147 mA, Po/Po = 907 mW at terminals 13-16 Out A. 

Uo/Voc = 24.8 V, Io/Isc = 108 mA, Po/Po = 667 mW at terminals 14-16 Out B. 

Uo/Voc = 24.8 V, Io/Isc = 93 mA, Po/Po = 571 mW at terminals 15-16 Out C. 

Um = 250 Vrms, -20 °C 

 Ta 

 60 °C. 

Approvals: 

DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-15, EN60079-26, EN61241-11, 

IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-15, IEC60079-26, IEC61241-11, 

FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15. 

TUV Certificate No. C-IS-204194-01, SIL 3 conforms to IEC61508. Please refer to Functional Safety Manual for SIL applications. 

Mounting:

 T35 DIN Rail according to EN50022. 

Weight:

 about 130 g. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm

2

Location:

 Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. 

Protection class:

 IP 20. 

Dimensions:

 Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

 

Technical Data 

2

4

6

8

10

12

14

16

18

20

22

13

V (V)

I (mA)

0

D1048 Output Diagram

Rout 

 174 

Ω 

(Out A)

10

0

20

30

40

50

21

10.2

8.5

45

Vo 

 21.0 V (no load)

Rout 

 236 

Ω 

(Out B)

Rout 

 275 

Ω 

(Out C)

Ilim 

 50 mA

Out A

Out B

Out C

For Safety Related System and SIL2, SIL3 Applications according IEC61508 & IEC61511 Standards refer to “Functional Safety Manual” document number ISM0071 

 

SIL Applications 

 

Содержание D1048S

Страница 1: ...D1048 SIL 3 Digital Output Driver NE Loads Loop Powered ISM0096 4 D1048S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 3 Digital Output Driver NE Loads Loop Powered DIN Rail Model D1048S ...

Страница 2: ...tage I S Out In 1 5 KV I S Out Override 1 5 KV I S Out Fault 1 5 KV In Fault 500 V In Override 500 V Fault Override 500 V Output 45 mA at 13 0 V 21 0 V no load 174 Ω series resistance at terminals 13 16 Out A 45 mA at 10 2 V 21 0 V no load 236 Ω series resistance at terminals 14 16 Out B 45 mA at 8 5 V 21 0 V no load 275 Ω series resistance at terminals 15 16 Out C Short circuit current 50 mA 55 m...

Страница 3: ...nput Output Fault EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx FM FM C Certifications High Reliability SMD components Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Output A for Solenoid Valve Terminal block connections HAZARDOUS AREA SAFE AR...

Страница 4: ...Po Po 907 mW Pi Pi Out A 13 16 Out B 14 16 Po Po 667 mW Out C 15 16 Po Po 571 mW Out A 13 16 Out B 14 16 Out C 15 16 Co Ca 113 nF Co Ca 860 nF Co Ca 3 05 µF IIB C IIA D IIC A B Li Ri device and L cable R cable Lo Ro 39 2 µH Ω Lo Ro 156 8 µH Ω Lo Ro 313 6 µH Ω IIB C IIA D IIC A B Lo Ro 53 3 µH Ω Lo Ro 213 5 µH Ω Lo Ro 427 0 µH Ω IIB C IIA D IIC A B Lo Ro 62 3 µH Ω Lo Ro 249 4 µH Ω Lo Ro 498 9 µH Ω ...

Страница 5: ...DIVISION 1 GROUPS E F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 Use only one output at a time Out A or Out B or Out C MODEL D1048S 15 16 5 6 Solenoid Valve In 1 Control 14 13 Out 1 Solenoid Valve Solenoid Valve 1 2 Transistor Fault Out Out C Out B Out A Load Diag 7 8 ...

Страница 6: ... for driving solenoid valves visual or audible alarms to alert a plant operator or other process control devices in Hazardous Area from a driving signal in Safe Area It can also be used as a controllable supply to power measuring or process control equipment Its use is allowed in applications requiring up to SIL 3 level according to IEC 61508 in safety related systems for high risk industries The ...

Страница 7: ...ous before servicing The wiring cables have to be proportionate in base to the current and the length of the cable On the section Function Diagram and enclosure side a block diagram identifies all connections and configuration DIP switches Identify the function and location of each connection terminal using the wiring diagram on the corresponding section as an example Connect control input signal ...

Страница 8: ...pcb These switches allows the configuration of override input and fault detection functions SW2 dip switch configuration SW2 Override control input Disabled Enabled 4 4 ON OFF 1 2 3 4 ON Not used ON SW2 Side A Panel View SW1 ON Side B Panel View SW1 dip switch configuration 1 2 3 4 ON Not used SW1 Field line and load fault detection 1 OFF 1 ON Disabled Enabled ...

Отзывы: