Entry and Exit of Caretaker Test Mode
Press the QUEUE REVIEW - TEST
first, then the CONTROLS - LAMP TEST
momentarily.
(The FAULTS - PROC FAULT
button
button
LED will light momentarily, this is OK).
Test mode can be activated at anytime except when:
·
There is a FIRE
·
SOUND ALARMS have been activated
·
Something is already in TEST MODE (Test Sounders or Test Zones)
·
You are in Programming Mode
·
You are Installation Mode
When Caretaker Test Mode is entered 'INITIALISING' may be displayed for up to 20 seconds
depending on the system size.
Caretaker Test Mode is exited by pressing
.
·
The TEST LED will be lit
·
The buzzer will sound for 0.5 seconds every 5 seconds (same as FAULT indication).
·
The message “ DETECTOR TEST MODE “ will be displayed on the LCD
·
The Zones in test mode will be displayed on the LCD - “ ALL ZONES “
SYSTEM RESET
Indication of Caretaker Test Mode
ALARM SILENCE will not stop this.
·
STATUS
QUEUE REVIEW
ZONES
FAULTS
KEYPAD
CONTROLS
DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
ENTER
ESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/ SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
DISABLED
TEST
FAULT
FIRE
1
2
3
4
5
6
7
8
MANUFACTURED IN THE E.U. TO THE
REQUIREMENTS OF EN54 Pt 2 & Pt 4 1999
OPERATION
1.9 CARETAKER TEST MODE
- Authorised User Access
(One-Man Walk-Through Test)
G L O B A L
F I R E
E Q U I P M E N T
JUNiOr
10
JUNIOR V3 - OPERATION & MAINTENANCE MANUAL - REVISION 2.3 - 17-SEP-2005