background image

Safety Reversing

An inherent safety feature of the Glidermatic operator is the overload function. This ensures that a closing door 

will stop and reverse motion if an obstruction is encountered

Always disconnect power to unit BEFORE making any setting changes.

CAUTION:

The overload function should be tested on a regular monthly basis to ensure the door will reverse on its 

downward motion when an obstruction is encountered. If this function does not operate discontinue use 

and contact a qualifi ed service technician.

Glidermatic™

Commercial Door Operator

User Manual

8

Torque Setting

The Glidermatic operator is designed to stop and

 reverse

  

downward

 operation if it encounters an obstruction. This is set by 

adjusting 

JP1 

to the lowest current that will allow the door to close 

during normal operation.

Start by testing with the jumper 

JP1 

set at 

4

. If the door will not 

close, proceed testing with 

JP1

 set at 

3. 

Continue setting 

JP1

 until 

the door will completely close.

The current settings are:

1. 7.5 amps (largest door)

2. 6.5 amps

3. 5.5 amps

4. 4.5 amps (smallest door)

www.garagedoorsonline.co.uk

01926 463888

Содержание Glidermatic

Страница 1: ...Glidermatic Commercial Door Operator Opening doors around the world www garagedoorsonline co uk 01926 463888...

Страница 2: ...utomatic Close function or Radio Transmitters are being used a Sensing Edge or Photo Electric Cell must be correctly fitted and tested on a regular basis If SAFETY features do not operate correctly DI...

Страница 3: ...the DRIVE UNIT and CONTROL UNIT not the installation of the door Exploded Parts Diagram 1 Drive unit 1 2 HP DC motor s 2 Gear Heads 3 Planetary gear housing 4 Drum wheel 5 Open and close limit switche...

Страница 4: ...ential that the CONTROL UNIT be securely attached to the wall or structure involved through the mounting holes provided Connect the CONTROL UNIT to a 240 volt single phase AC 5 0 AMP power source bein...

Страница 5: ...ever all units as standard factory issue are configured to Right Hand operation If required the handing of the operator may be changed by setting jumper JP6 1 Set jumper JP6 according to whether the o...

Страница 6: ...roken springs may allow the door to fall rapidly causing severe injury or even death In all cases stand clear of the door In the event that the door appears to fall a qualified service technician will...

Страница 7: ...pening height manually raise the door to the desired open position ensure the bottom bar is short of contacting the head stop observing the direction of rotation of the outer cam Rotate the outer cam...

Страница 8: ...se the unit will not operate unless a supplementary safety device is fitted and the jumpers at JP3 and JP5 set accordingly Refer to pages 9 and 10 Glidermatic Commercial Door Operator User Manual 7 DO...

Страница 9: ...erate discontinue use and contact a qualified service technician Glidermatic Commercial Door Operator User Manual 8 Torque Setting The Glidermatic operator is designed to stop and reverse downward ope...

Страница 10: ...erminals 5 6 of J3 Ensure jumper JP2 is configured to match required voltage of photo electric cell Refer to page 11 Glidermatic Commercial Door Operator User Manual 9 Connect the two wires from the P...

Страница 11: ...2 or 24 VDC power may be sourced from terminals 5 6 of J3 Ensure jumper JP2 is configured to match required voltage of sensing edge Refer to page 11 Glidermatic Commercial Door Operator User Manual 10...

Страница 12: ...is v 6 is ground Ensure Jumper JP2 is configured to match required voltage of radio control receiver 5 12 or 24VDC Single Up Down Output Type Receiver Connect output of receiver to terminal 4 of J3 Op...

Страница 13: ...The Glidermatic operator can be configured to automatically close the door after a prescribed period of time up to 12 minutes Enable Automatic Close JP4 To enable the Automatic Close Function move Ju...

Страница 14: ...power to unit BEFORE making any setting changes CAUTION Consult the installation instructions supplied by the manufacturer of the alarm being used for connection and relay details Alarm Wiring A 5 vol...

Отзывы: