background image

Alarm Function

The Glidermatic operator can be connected to a security system to activate an alarm when an attempt is made 

to open a closed door. 

Glidermatic™

Commercial Door Operator

User Manual

13

Always disconnect power to unit BEFORE making any setting changes.

CAUTION:

Consult the installation instructions supplied by the manufacturer of the alarm being used for connection 

and relay details

Alarm Wiring

A 5 volt DC signal is sent to terminal 

J4

 in the event an 

attempt is made to force the door open. This is designed 

to interface to an alarm panel.

5V

GND

~ 1 SEC

ALARM PULSE 

OUTPUT

TIME

~

www.garagedoorsonline.co.uk

01926 463888

Содержание Glidermatic

Страница 1: ...Glidermatic Commercial Door Operator Opening doors around the world www garagedoorsonline co uk 01926 463888...

Страница 2: ...utomatic Close function or Radio Transmitters are being used a Sensing Edge or Photo Electric Cell must be correctly fitted and tested on a regular basis If SAFETY features do not operate correctly DI...

Страница 3: ...the DRIVE UNIT and CONTROL UNIT not the installation of the door Exploded Parts Diagram 1 Drive unit 1 2 HP DC motor s 2 Gear Heads 3 Planetary gear housing 4 Drum wheel 5 Open and close limit switche...

Страница 4: ...ential that the CONTROL UNIT be securely attached to the wall or structure involved through the mounting holes provided Connect the CONTROL UNIT to a 240 volt single phase AC 5 0 AMP power source bein...

Страница 5: ...ever all units as standard factory issue are configured to Right Hand operation If required the handing of the operator may be changed by setting jumper JP6 1 Set jumper JP6 according to whether the o...

Страница 6: ...roken springs may allow the door to fall rapidly causing severe injury or even death In all cases stand clear of the door In the event that the door appears to fall a qualified service technician will...

Страница 7: ...pening height manually raise the door to the desired open position ensure the bottom bar is short of contacting the head stop observing the direction of rotation of the outer cam Rotate the outer cam...

Страница 8: ...se the unit will not operate unless a supplementary safety device is fitted and the jumpers at JP3 and JP5 set accordingly Refer to pages 9 and 10 Glidermatic Commercial Door Operator User Manual 7 DO...

Страница 9: ...erate discontinue use and contact a qualified service technician Glidermatic Commercial Door Operator User Manual 8 Torque Setting The Glidermatic operator is designed to stop and reverse downward ope...

Страница 10: ...erminals 5 6 of J3 Ensure jumper JP2 is configured to match required voltage of photo electric cell Refer to page 11 Glidermatic Commercial Door Operator User Manual 9 Connect the two wires from the P...

Страница 11: ...2 or 24 VDC power may be sourced from terminals 5 6 of J3 Ensure jumper JP2 is configured to match required voltage of sensing edge Refer to page 11 Glidermatic Commercial Door Operator User Manual 10...

Страница 12: ...is v 6 is ground Ensure Jumper JP2 is configured to match required voltage of radio control receiver 5 12 or 24VDC Single Up Down Output Type Receiver Connect output of receiver to terminal 4 of J3 Op...

Страница 13: ...The Glidermatic operator can be configured to automatically close the door after a prescribed period of time up to 12 minutes Enable Automatic Close JP4 To enable the Automatic Close Function move Ju...

Страница 14: ...power to unit BEFORE making any setting changes CAUTION Consult the installation instructions supplied by the manufacturer of the alarm being used for connection and relay details Alarm Wiring A 5 vol...

Отзывы: