Sensing Edge Wiring
Consult the installation instructions supplied by manufacturer of the
Sensing Edge
device and determine
whether the contacts are normally open (N/O) or normally closed (N/C) .
Always disconnect power to unit BEFORE making any setting changes.
CAUTION:
Sensing Edge
devices are recommended as a supplementary safety system. If required, 12 or 24 VDC
power may be sourced from terminals
5 & 6 of J3
. Ensure jumper
JP2
is confi gured to match required
voltage of sensing edge. Refer to page 11.
Glidermatic™
Commercial Door Operator
User Manual
10
Connect the two wires from the
Sensing Edge
terminals marked
EDGE
on terminal block
J5.
If the
Sensing Edge
contacts are
normally open
, move jumper on
JP3
from
OFF
to
N/O.
If the
Sensing Edge
features
normally closed
contacts,
move jumper on
JP3
from
OFF
to
N/C.
N/C
N/O
OFF
MOVE
N/C
N/O
OFF
TO
N/C
N/O
OFF
TO