Installation Guidelines
7
Location Considerations
The chiller must be installed with enough clearance for service and for unrestricted air intake and exhaust. The
chiller must be located sufficiently close to the process to ensure adequate flow rate of coolant by not exceeding
the capabilities of the chil
ler’s pumps. The following sections outline recommended installation practices.
The
chiller has potential for misuse that could result in unplanned downtime. The main disconnect, drain, and field
installed service valves can be operated by unauthorized personnel. If unauthorized operation is a concern, then
a security fence should be provided to reduce the potential for misuse. Fencing must not obstruct airflow and
must leave room or be removable for service
. The chiller’s air intake and exhaust clearances must adhere to the
following:
Table 4: Chiller Air Intake and Exhaust Requirements
Criterion
Value
Vertical clearance
≥ 8ft (2.4m)
Horizontal clearance (Door, Enclosure, and Rear Sides)
≥ 3ft (.9m)
Horizontal clearance (Air intake side)
≥ 6ft (1.8m)
Exhaust air must be freely discharged by the chiller’s fans. This air must not be recirculated to the air intake side
of the chiller. Avoid installing deflectors that redirect air to the air intake side of the chiller or installing ducting
that directly connects to the chiller’s top. The chiller uses axial fans that are not compatible with exhausting air
through ducting. Ducting increases the pressure drop of the fans severely and lowers the volumetric air flow.
NOTICE
Improper air intake and exhaust clearances can lead to reduced capacity, thermal
overloading of the fan motors and/or compressors, high pressure refrigeration
faults, and/or rendering the chiller inoperable.
If ducting must be installed at the chiller’s location a suitable duct auxiliary fan
must be provided. Consult the factory for guidelines and recommendations.
Make sure the unit is placed, on a level, hard surface. The chiller must be level or less than ½ inch of slope per 10
feet. Use shims to correct level if needed. If the chiller is mounted on a concrete slab, the slab should be 4-inch
thick and at least 5 feet x 12 feet. If the chiller is roof mounted, two I-beam runners are typically provided to
support the chiller feet at both ends. For rooftop mounting, chiller should be anchored through the mounting
holes provided in the feet. When the chiller is mounted above an office space, optional vibration mounting
springs can be used to isolate the chiller from the building structure.
Содержание Koolant Koolers WO2-2-10000
Страница 1: ...Original Instructions 800 968 5665 dimplexthermal com User Manual...
Страница 17: ...Installation 11 Figure 7 Removal or Doors Blockers 3 8 DOOR BOLT 3 8 BLOCKER BOLT BLOCKER DOOR...
Страница 18: ...Installation 12 Figure 8 Removal of Lower Doors LATCHES...
Страница 28: ...Operation 22 Figure 10 Controller Restart Warning Figure 11 Controller Home Page...
Страница 30: ...Operation 24 Figure 15 Controller On Off Menu Figure 16 Controller Pump Enable Disable Menu...
Страница 31: ...Operation 25 Figure 17 Controller Setpoint Menu Figure 18 Controller Alarm Menu...
Страница 37: ...Internal Components 31 Figure 20 Door Side PUMP 2 PUMP 1 FLOAT SWITCH...
Страница 44: ...Appendix A Plumbing 38 Appendix A Plumbing...
Страница 45: ...Appendix B Pump Curve 39 Appendix B Pump Curve...
Страница 46: ...Appendix C Refrigeration WO2 2 5000 40 Appendix C Refrigeration WO2 2 5000...
Страница 47: ...Appendix C Refrigeration WO2 2 7500 41 WO2 2 7500...
Страница 48: ...Appendix C Refrigeration WO2 2 10000 42 WO2 2 10000...
Страница 53: ...Appendix G Chiller Registration 47...