14
UGTC Series Manual
Comply with the exhaust clearances found in the Giant Operation and Installation Manual.
Only one appliance can be attached to the vent system.
Install the system according to the Centrotherm installation instructions.
Use the 3”/5” concentric to twin pipe adaptor and 3” diameter venting.
The vent termination and air intake must be in the same pressure zone.
Do not exceed maximum straight vent length with number of elbows as shown in the tables on the next
page.
Maintain the clearances shown in the figures below.
WARNING
DO NOT use PVC on the exhaust venting. PVC is allowed on the intake only.
Horizontal Termination
Vertical Termination
11
”
5”
Intake
Optional
Vent
Flue Installation with Centrotherm Venting
Install the venting termination according to the diagrams and instructions below.