background image

4

Altitude

This water heater is approved for altitudes up to 5,000 feet 
(1,524 m).

Location

This water heater should be located close enough to the 
outside wall so that it is within the venting requirements
listed in these installation instructions and as close as 
possible to the main use of hot water. This location must not 
be subject to freezing temperatures. The water heater should 
be positioned, so that there is easy access to the burner, 
gas control valve, and drain valve. It must be located close 
to a suitable free-flowing floor drain. Where a floor drain is 
not adjacent to the water heater, a suitable drain pan must 
be installed under the water heater (

see Figure 8

). This drain 

pan should be at least four (4) inches (10.2 cm) larger than the 
diameter of the water heater, and at least one (1) inch (2.5 
cm) deep, providing access to the drain valve. This pan must 
be piped to a suitable drain to prevent damage to property in 
the event of a water leak from the piping, the relief valve, or 
the water heater.

Sooner or later, all water heaters leak. The 
manufacturer, based on national building codes, 
has given the necessary instructions to prevent 
damage to the building. Under no circumstances 
is the manufacturer to be held liable for any water 
damage, in connection with this water heater. 

This water heater is approved for installation on either a com-
bustible or non-combustible floor. However, should this water 
heater be installed directly on carpeting, the carpeting must be 
protected by a wood or metal panel beneath the water heater. 
This panel must extend at least three (3) inches (7.6 cm) 
beyond the width and depth of the water heater. Should the 
water heater be installed in an alcove or closet, the entire floor 
area must be covered by the panel. 

Minimum Clearances

The minimum clearances from combustible material for this 
water heater are:  Two (2) inches (5.1 cm) from the sides 
and rear, four (4) inches (10.2 cm) from the front, and eigh-
teen (18) inches (45.7 cm) from the top (

see Figure 1

).

Figure 1

18''

min.

2'' min.

2'' min.

4'' min.

2'' min.

Venting

DANGER

When installing the venting system, make sure to follow 
all local codes or, in the absence of local codes, CAN/CSA 
B149.1, Natural Gas and Propane Gas Installation Code, in 
Canada and/or the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, in the United States. Never operate the water heat-
er unless it is properly ventilated to the outdoors and has 
adequate air supply for proper operation. Failure to properly 
install the venting system could result in property damage, 
personal injury, or death.

INSTALLATION INSTRUCTIONS

IMPORTANT 

 

These instructions have been written as a guide for the proper installation and operation of your water heater, and the manufac-
turer of this water heater will not accept any liability where these instructions have not been followed. However, for your safety 
and to avoid damage caused by improper installation, this water heater must be installed by a Certified Licensed Professional, 
and meet all local codes or, in the absence of local codes, the latest edition of CAN/CSA B149.1, Natural Gas and Propane Gas 
Installation Code, in Canada, and/or the latest edition of  the National Fuel Gas Code, ANSI Z223.1/NFPA 54, in the United States.

Before proceeding with the installation instructions:

1)

 Inspect the water heater and its component parts for possible damage. 

DO NOT 

install or attempt to repair any 

damaged component parts. If you detect any damage, contact the dealer where the water heater was purchased or 
the manufacturer listed on the warranty card.

2)

 Verify that the type of gas being supplied corresponds to that which is marked on the rating plate and gas control 

valve of the water heater. 

Содержание UG50 series

Страница 1: ...quids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building From a neigh...

Страница 2: ...er inspected immediately by a qualified service technician or the gas supplier WARNING Safety Information 3 Installation Instructions 4 Altitude 4 Location 4 Minimum Clearances 4 Venting 4 Venting Con...

Страница 3: ...This symbol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death c...

Страница 4: ...vered by the panel Minimum Clearances The minimum clearances from combustible material for this water heater are Two 2 inches 5 1 cm from the sides and rear four 4 inches 10 2 cm from the front and ei...

Страница 5: ...d States see Figure 4 This water heater must be vented directly to the outdoors either horizontally through the wall or vertically through the roof The venting must not be attached to an existing chim...

Страница 6: ...2 X 3 is necessary for a three 3 inch 7 6 cm venting system This coupling must be installed as close as possible after the rubber transition fitting and in every case before the first elbow Vent Syste...

Страница 7: ...orch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door that may be opened 12 inches 30 cm 9 inches 23 cm or 12 inches 30 cm C Clearance to outside corner D Clearance to ins...

Страница 8: ...or wall same atmospheric pressure zone The air intake equivalent vent length must be equal to or less than the exhaust equivalent vent length and the air intake termination elbow shall be equipped wit...

Страница 9: ...ke terminal must be at a minimum of eighteen 18 inches 45 7 cm from the exterior surface of the roof or anticipated snow accumulation level see Figure 2 The vertical terminations should be sealed with...

Страница 10: ...ssemble parts while cement is fluid If you wait too long re coat pipe fitting 8 Push the vent pipe completely into the coupling turning as it goes until it bottoms out 9 Hold pipe and fitting together...

Страница 11: ...ent system from IPEX be sure to install the two 2 inch 5 1 cm black restrictor screen from 0 to twenty five 25 feet 7 6 m If using the three 3 inch 7 6 cm concentric vent system from IPEX be sure to i...

Страница 12: ...an result in property damage personal injury or death To protect from excessive pressure and or temperature the manufacturer has installed a temperature and pressure relief valve that meets the requir...

Страница 13: ...roved for natural and propane gases It is mandatory that a readily accessible manual shut off valve be installed in the gas supply line The gas supply manual shut off valve must be close to the water...

Страница 14: ...1o F 105o C Installation Instructions for Water Heaters Approved for Combination Space Heating and Potable Water Heating see Figure 11 A water heater cannot be used for space heating only When using a...

Страница 15: ...er is equipped with a check valve water meter or pressure reducing valve an expansion tank must be installed in the system This will prevent weeping from the water heater relief valve and premature fa...

Страница 16: ...he appropriate primer and solvent based cement when necessary Has the venting been supported at the proper intervals Have precautions been taken against condensation flowing into the power venter Wate...

Страница 17: ...ter immediately contact a qualified installer service agency or the gas sup plier WARNING DO NOT light this water heater if It is not full of water The gas supplied does not match the type listed on t...

Страница 18: ...he COOLER button until you have reached the desired setting HOLDING DOWN THE BUTTON WILL NOT CONTINUE TO LOWER THE SETTING The button must be pressed and released for each tempera ture change desired...

Страница 19: ...switch to lock out mode and prevent the water heater from lighting After a flammable vapour incident has occurred and the flam mable vapours have dissipated the FV sensor is designed to automatically...

Страница 20: ...common observation is hot water that smells like rotten eggs This phenomenon is the result of the reaction between the anode and hydrogen sulfide gas dissolved in the water which occurs frequently in...

Страница 21: ...listed in the Troubleshooting Guide does not solve the problem or if your particular problem is not listed in the guide contact the installer of the water heater or the local gas utility 3 If you sti...

Страница 22: ...r Access Doors 7 Outer Access Door 8 Drain Valve 9 Overflow Tube 10 Dip tube 11 Magnesium Anode 12 Temperature Pressure Relief Valve 13 Baffle 14 Inlet Rubber Adaptor 15 Vacuum Switch Inlet 16 Vacuum...

Страница 23: ...ion 5 Low voltage to the water heater Check and repair 7 The gas valve driver circuit 1 Turn off the power to the water heater for 10 seconds and then back on 2 If the above step did not clear the err...

Страница 24: ...re Check with gas utility company Defective gas control valve Replace with new gas control valve High operating costs Gas control valve set too high Turn temperature dial to desired temperature Sedime...

Страница 25: ...ter filled for first time Let water heater warm up Problem should go away If it per sists check all plumbing connections for leaks Heavy draws of hot water with very cold refill water Let water heater...

Страница 26: ...in in the event of water leakage 10 If the heater is operated at water temperatures exceeding the maximum setting of the operating or high limit control or the heater is not supplied with potable wate...

Страница 27: ...xed to the heater any non factory made or factory approved replace ment part s such as elements controls dip tubes relief valves etc 9 To any damage caused by not having the water heater installed adj...

Страница 28: ...___________________________________________________________ ________________________________________________________________________________ ___________________________________________________________...

Отзывы: