background image

23

TROUBLESHOOTING GUIDE

CONDITION (code#)

CAUSE

REMEDY

1

An open earth ground 
circuit to the ignition.

1) Check that the earth ground conductor is properly connected at the fuse box or 

breaker panel and the water heater.

2) Check that the grounding conductors on the water heater are properly connected 

and secure.

2

A wiring error or a high 
resistance to earth ground.

1) Check for proper connection of the line neutral and line hot wires. 
2) Check that the water heater is securely connected to earth ground.

3

The pressure switch remained
closed longer than 5 seconds
after the call for heat began.

1) The pressure switch wiring is incorrect.
2) The pressure switch is defective and must be replaced.

4

The exhaust pressure switch 
remained open longer than 5 
seconds (or the inlet pressure 
switch opened) after the power 
venter was energized.

1) The pressure switch wiring is incorrect.
2) The pressure switch tubings are not properly connected.
3) There are obstructions or restrictions in the water heater air intake or exhaust 

flue.

5

The self diagnostic test has 
detected an error in the  
hot surface ignitor circuit.

1) Check the wiring is correct and secure.
2) Disconnect the ignitor connector and measure the ignitor resistance with 

an accurate ohmmeter between pins 1 and 2. Resistance should be between 
11.5 and 18.8 ohms. If the reading is incorrect, replace the hot surface ignitor.

3) If the above checks are good, replace the gas control valve.

6

The maximum number of igni-
tion 
retries or recycles has been 
reached and the system is in 
lock-out mode.

1) Check if the gas supply is off or too low to operate.
2) Check the flame sensor rod to see that it is properly located and free from con-

tamination. Reposition the flame sensor rod or lightly clean it with an abrasive 
cloth.

3) The hot surface ignitor may not be properly positioned. Reposition as necessary.
4) Check that the hot surface ignitor and flame sensor rod are properly wired and in 

good working condition.

5) Low voltage to the water heater. Check and repair.

7

The gas valve driver circuit.

1) Turn off the power to the water heater for 10 seconds and then back on.
2) If the above step did not clear the error, replace the gas control valve.

8

The internal microcomputer.

1) Turn off the power to the water heater for 10 seconds and then back on.
2) If the above step did not clear the error, replace the gas control valve.

9

The internal circuit.

1) Turn off the power to the water heater for 10 seconds and then back on
2) If the above step did not clear the error, replace the gas control valve.

10

Flame signal sensed out of 
proper sequence.

Replace the gas control valve.

11

The high temperature thermal
cut-off is open.

Replace the gas control valve.

12

One of the temperature adjust 
buttons is stuck closed.

1) Make sure that there are no objects leaning against the front of the control.
2) Lightly press and release each of the buttons once.
3) If the above actions do not clear the error, the control will continue to regulate 

the water temperature at the last setting, but you will not be able to change set-
tings unless you replace the gas control valve.

13

The water temperature sensor 
is either open or short-circuited.

1) Check that all of the wiring is correct and that there are no open or short circuits.
2) If no wiring problems are found, the gas control valve must be replaced.

14

The self-diagnostic test found 
a problem with the flammable 
vapour sensor.

1) Check that all wiring is correct and that there are no open or short circuits.
2) If no wiring problems are found, the Flammable vapour sensor must be replaced.

15

The control detected the pres-
ence of flammable vapours near 
the appliance and entered the 
lock-out mode.

1) Identify the source of the flammable vapours and remove it from the area sur-

rounding  the water heater.

2) Contact a qualified service technician or the gas supplier to have the water heater 

inspected immediately.

WARNING

Disconnect the electrical power before servicing the water heater. Service should only be performed by a 
qualified service technician. Failure to follow these instructions can result in personal injury and/or death.

Содержание UG50 series

Страница 1: ...quids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building From a neigh...

Страница 2: ...er inspected immediately by a qualified service technician or the gas supplier WARNING Safety Information 3 Installation Instructions 4 Altitude 4 Location 4 Minimum Clearances 4 Venting 4 Venting Con...

Страница 3: ...This symbol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death c...

Страница 4: ...vered by the panel Minimum Clearances The minimum clearances from combustible material for this water heater are Two 2 inches 5 1 cm from the sides and rear four 4 inches 10 2 cm from the front and ei...

Страница 5: ...d States see Figure 4 This water heater must be vented directly to the outdoors either horizontally through the wall or vertically through the roof The venting must not be attached to an existing chim...

Страница 6: ...2 X 3 is necessary for a three 3 inch 7 6 cm venting system This coupling must be installed as close as possible after the rubber transition fitting and in every case before the first elbow Vent Syste...

Страница 7: ...orch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door that may be opened 12 inches 30 cm 9 inches 23 cm or 12 inches 30 cm C Clearance to outside corner D Clearance to ins...

Страница 8: ...or wall same atmospheric pressure zone The air intake equivalent vent length must be equal to or less than the exhaust equivalent vent length and the air intake termination elbow shall be equipped wit...

Страница 9: ...ke terminal must be at a minimum of eighteen 18 inches 45 7 cm from the exterior surface of the roof or anticipated snow accumulation level see Figure 2 The vertical terminations should be sealed with...

Страница 10: ...ssemble parts while cement is fluid If you wait too long re coat pipe fitting 8 Push the vent pipe completely into the coupling turning as it goes until it bottoms out 9 Hold pipe and fitting together...

Страница 11: ...ent system from IPEX be sure to install the two 2 inch 5 1 cm black restrictor screen from 0 to twenty five 25 feet 7 6 m If using the three 3 inch 7 6 cm concentric vent system from IPEX be sure to i...

Страница 12: ...an result in property damage personal injury or death To protect from excessive pressure and or temperature the manufacturer has installed a temperature and pressure relief valve that meets the requir...

Страница 13: ...roved for natural and propane gases It is mandatory that a readily accessible manual shut off valve be installed in the gas supply line The gas supply manual shut off valve must be close to the water...

Страница 14: ...1o F 105o C Installation Instructions for Water Heaters Approved for Combination Space Heating and Potable Water Heating see Figure 11 A water heater cannot be used for space heating only When using a...

Страница 15: ...er is equipped with a check valve water meter or pressure reducing valve an expansion tank must be installed in the system This will prevent weeping from the water heater relief valve and premature fa...

Страница 16: ...he appropriate primer and solvent based cement when necessary Has the venting been supported at the proper intervals Have precautions been taken against condensation flowing into the power venter Wate...

Страница 17: ...ter immediately contact a qualified installer service agency or the gas sup plier WARNING DO NOT light this water heater if It is not full of water The gas supplied does not match the type listed on t...

Страница 18: ...he COOLER button until you have reached the desired setting HOLDING DOWN THE BUTTON WILL NOT CONTINUE TO LOWER THE SETTING The button must be pressed and released for each tempera ture change desired...

Страница 19: ...switch to lock out mode and prevent the water heater from lighting After a flammable vapour incident has occurred and the flam mable vapours have dissipated the FV sensor is designed to automatically...

Страница 20: ...common observation is hot water that smells like rotten eggs This phenomenon is the result of the reaction between the anode and hydrogen sulfide gas dissolved in the water which occurs frequently in...

Страница 21: ...listed in the Troubleshooting Guide does not solve the problem or if your particular problem is not listed in the guide contact the installer of the water heater or the local gas utility 3 If you sti...

Страница 22: ...r Access Doors 7 Outer Access Door 8 Drain Valve 9 Overflow Tube 10 Dip tube 11 Magnesium Anode 12 Temperature Pressure Relief Valve 13 Baffle 14 Inlet Rubber Adaptor 15 Vacuum Switch Inlet 16 Vacuum...

Страница 23: ...ion 5 Low voltage to the water heater Check and repair 7 The gas valve driver circuit 1 Turn off the power to the water heater for 10 seconds and then back on 2 If the above step did not clear the err...

Страница 24: ...re Check with gas utility company Defective gas control valve Replace with new gas control valve High operating costs Gas control valve set too high Turn temperature dial to desired temperature Sedime...

Страница 25: ...ter filled for first time Let water heater warm up Problem should go away If it per sists check all plumbing connections for leaks Heavy draws of hot water with very cold refill water Let water heater...

Страница 26: ...in in the event of water leakage 10 If the heater is operated at water temperatures exceeding the maximum setting of the operating or high limit control or the heater is not supplied with potable wate...

Страница 27: ...xed to the heater any non factory made or factory approved replace ment part s such as elements controls dip tubes relief valves etc 9 To any damage caused by not having the water heater installed adj...

Страница 28: ...___________________________________________________________ ________________________________________________________________________________ ___________________________________________________________...

Отзывы: