background image

INSTALLATION INSTRUCTIONS

When assembling the hot and cold piping to the 
water heater, use Teflon™ tape or a good food grade 
of pipe joint compound, and ensure all fittings are 
tight. It is imperative that open flame is not applied 
to the inlet and outlet fittings, as heat will damage 
or destroy the plastic lined fittings. This will result 
in premature failure of the fittings, which is not 
covered by the warranty.

Temperature and Pressure-Relief Valve

DO NOT

 plug the temperature and pressure-relief 

valve or its discharge line. 

DO NOT

 remove the 

relief valve. Make sure the relief valve is properly 
sized for the water heater. If the relief valve 
continuously discharges water, call a qualified 
service technician to correct the problem. Failure 
to follow these instructions can result in property 
damage, personal injury, or death.

 

To protect from excessive pressure and/or temperature, 
the manufacturer has installed a temperature and 
pressure-relief valve that meets the requirements of the 
Standard for Relief Valves and Automatic Gas Shut-
Off Devices for Hot Water Supply Systems, CSA 4.4 
in Canada and ANSI Z21.22 in the United States. This 
relief valve has a maximum set pressure  that does not 
exceed the hydrostatic working pressure of the water 
heater (150 psi = 1,035 kPa) and a Btuh rating equal 
to or greater than the input rating, as shown on the 
water heater rating plate. It should never be plugged or 
removed from the opening marked for it on the water 
heater. 

Should this relief valve need to be replaced, use 
only a new temperature and pressure-relief valve. 
Never install an old or existing relief valve as it 
may be damaged or inadequate for the working 
requirements of the new water heater. This new relief 
valve must meet all local codes or, at a minimum, the 
requirements listed above. Never install any other type 
of valve between the relief valve and the water heater.

8

  1)  Vent pipe
  2)  Draft hood
  3)  Union
  4)  Cold water  
 

manual shut-off valve

  5)  Cold water inlet
  6)  Expansion tank
  7)  Temperature  
 

& pressure-relief valve

  8)  Overflow tube
  9)  Drain valve
10) Combustion 
 

air intake holes

11)  Drain pan
12)  Free-flowing floor drain
13)  Sight glass
14) Resettable 
 

thermal switch

15)  Inner access door

16)  Outer access door
17) Cap
18)  Drip leg (Sediment trap)
19)  Gas supply 
 

manual shut-off valve

20) Union
21)  Gas control
22)  Rating plate
23)  Piezo igniter
24)  Dip tube
25)  Hot water outlet
26) Union
27) Burner
28)  Main burner orifice
29) Pilot
30) Thermocouple
31) Electrode
32)  Manifold Spring
 

(on some models)

Figure 8

1

2

5

6

3

4

24

7

8

23

9

10 11

12

16

15

14 13

20

17

18

19

21

22

25

26

Minimum Slope

1/4”/foot (21mm/m)

27

29

31

30

28

32

Содержание UG30

Страница 1: ...n may result causing property damage personal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL...

Страница 2: ...eplacement Parts 16 Troubleshooting Guide 17 Warranty 19 FVIR technology equipped with flame arrestor This water heater is equipped with the new FVIR technology In the event that gasoline or other fla...

Страница 3: ...ol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death can occur...

Страница 4: ...structions to prevent damage to the building Under no circumstances is the manufacturer to be held liable for any water damage in connection with this water heater This water heater is approved for in...

Страница 5: ...ll appliances and shall communicate directly with one or more rooms of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space for all the appliances ins...

Страница 6: ...f the total input rating of all gas appliances in the confined space see Figure 6 Install above insulation Attic air inlet Outlet air to attic 1 sq in 4 000 Btuh Confined Space Inlet air duct 1 sq in...

Страница 7: ...pipe and or combined venting with other appliances Consult the vent tables in the CSA B149 1 in Canada and or the National Fuel Gas Code ANSI Z223 1 in the United States to correctly size the vent pi...

Страница 8: ...hydrostatic working pressure of the water heater 150 psi 1 035 kPa and a Btuh rating equal to or greater than the input rating as shown on the water heater rating plate It should never be plugged or...

Страница 9: ...etely full of water open hot water faucets to let the air out of the water heater and plumbing system Leave the faucets open until a constant flow of water is obtained 4 Check all of the plumbing conn...

Страница 10: ...e past treated with chemicals for cleaning or sealing the system 3 If this water heater is to be used for space heating make sure that all safety codes are respected Pay special attention to safety va...

Страница 11: ...hood been installed correctly L Is the vent piping made of an approved material and sized correctly L Has the venting been installed with 1 4 inch rise per foot 21 mm m of horizontal run L Has all th...

Страница 12: ...mmediately call a qualified service technician to inspect the water heater and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety informati...

Страница 13: ...Turn the temperature dial clockwise to decrease the temperature or counterclockwise to increase the temperature The reference mark on the temperature dial indicated by a large triangle represents 130...

Страница 14: ...connections to make sure they are not leaking Main Burner Pilot Every three 3 months check the main burner and pilot flame Remove the outer access door and look through the sight glass to examine the...

Страница 15: ...2 Depress slightly and turn the gas control knob clockwise to the OFF position 3 Close the gas supply manual shut off valve 4 Close the cold water supply manual shut off valve 5 Connect one end of a g...

Страница 16: ...tube 8 Baffle 9 Flue reducer 10 Draft hood 11 Anode 12 Dip tube 13 Temperature pressure relief valve 1 Manifold Spring on some models 2 Manifold 3 Inner Left Door 4 Access Door 5 Thermal High Limit S...

Страница 17: ...control The flame burns at the orifice Low gas pressure Check with gas utility company Defective gas control Replace with new gas control The pilot will not light or remain lit No gas Check with gas u...

Страница 18: ...Condensation Water drips from the relief valve Heater stacking Lower gas control setting Excessive water pressure Install a pressure reducing valve Thermal expansion in a closed water system Install...

Страница 19: ...10 To any damage caused by not having the unit installed adjacent to a free flowing drain or in a pan or basin connected to such free flowing drain 11 For all equipment operated at water temperatures...

Страница 20: ...cted to such free flowing drain 11 For all equipment operated at water temperatures exceeding the maximum operating setting of the thermostat and or the high limit control at a pressure exceeding the...

Отзывы: